- 2072 Chaitra · 12 marks
Compensator for 4/[s(s+2)]: Mp 16.3%, ts, Kv
Short answer
Lead compensator: desired poles at -2 ± j3.464 (ζ=0.5, ω_n=4) for 16.3% overshoot and 2 s settling time. Cancel plant pole at -2 with a zero, place pole at -4 to add 30° phase. Gain Kc=4. Compensator: Gc(s)=4(s+2)/(s+4). Kv=4 s⁻¹.
Design a suitable compensator for a unity feedback system with its feed forward transfer function as G(s) = 4/[s(s+2)] such that its maximum percent overshoot is 16.3% and settling time 2 sec for its step response. Also velocity error constant should not be less than 2 per sec.
The settling time must be halved while keeping , so the dominant poles must move left; a lead compensator designed by the root locus method is used.
Step 1: Desired closed-loop poles
Peak overshoot:
Settling time (2% criterion):
Step 2: Uncompensated system
Closed-loop characteristic equation: , so , .
- (already correct), s (too slow).
- .
So the poles must move further left along the same line, which needs a lead compensator.
Step 3: Angle deficiency
At :
The compensator must add at .
Step 4: Place the zero and pole
Let . Put the zero at to cancel the plant pole at , so the zero gives . The pole must then give :
Step 5: Gain from the magnitude condition
The compensated open loop is :
Check: characteristic equation gives , . Correct.
Step 6: Check velocity error constant
Result
| Quantity | Uncompensated | Compensated |
|---|---|---|
| Closed-loop poles | ||
| , | 0.5, 2 rad/s | 0.5, 4 rad/s |
| 16.3% | 16.3% | |
| (2%) | 4 s | 2 s |
| 2 s | 4 s |
Answer: (lead compensator, zero at , pole at , ). All three specifications are met.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Lead compensator for 10/[s(s+1)], ts=2 s, Mp=5% · Control Systems, chapter 7
- Lead compensator for 4/[s(s+2)], Mp≤16.3%, ts≤2 s · Control Systems, chapter 7
- Overshoot, settling time and error for 50/[s(s+2)] · Control Systems, chapter 3
- Transfer function from overshoot and settling time · Control Systems, chapter 3
- Compensator for 4/[s(s+2)], ts=2 s, Kv=2 · Control Systems, chapter 7 · asked 2×
- Overshoot, settling and peak time of rotational system · Control Systems, chapter 3
- Controller design with 8 samples per cycle, step response and Kv · Digital Control System, chapter 4
- Digital PI design, plant e^(−5s)/(s+0.4), step response · Digital Control System, chapter 4
- Controller design for peak time 1.2 s (ζ = 0.55), Kv · Digital Control System, chapter 4 · asked 2×
- z-plane design with Kv, plant 1/(s(s+2)) · Digital Control System, chapter 4