- 2068 Baisakh (old course) · 16 marks
Lead compensator for 4/[s(s+2)], Mp≤16.3%, ts≤2 s
Short answer
Cancel the plant pole at -2 with a compensator zero; for 30° lead, place the pole at -4. Gain Kc=4 gives Gc(s)=4(s+2)/(s+4). Closed-loop ωn=4 rad/s, ζ=0.5 yields Mp=16.3% and ts=2 s.
Design a lead compensator for a system having open loop transfer function 4/[s(s+2)], such that the designed system should have %Mp ≤ 16.3% and settling time (ts) ≤ 2 sec.
A lead compensator is designed by the root locus method: find the desired dominant poles, find the angle the compensator must add, place its zero and pole, then find its gain.
Step 1: Desired closed-loop poles
Peak overshoot:
Settling time (2% criterion):
Step 2: Uncompensated system
Closed-loop characteristic equation: , so , .
- (already correct), s (too slow).
- .
So the poles must move further left along the same line, which needs a lead compensator.
Step 3: Angle deficiency
At :
The compensator must add at .
Step 4: Locate zero and pole (bisector method)
Let . At point P draw a horizontal line PA to the left and the line PO to the origin. Angle APO . Draw its bisector PB, then two lines at from PB; they cut the real axis at the zero and the pole.
P (-2, j3.46)
/|\
/ | \ bisector +-15 deg
/ | \
-------x---o--x------x-----o---> Re
-5.46 -2.93 -2 0
pole zero plant plant
The lines from P make angles (zero) and (pole) with the positive real axis:
Check: zero angle , pole angle , net lead .
Step 5: Gain
.
Closed-loop poles: and . The closed-loop zero at is not close enough to the third pole to cancel it, so a step simulation gives , s, slightly above the limits.
Step 6: Final design (pole–zero cancellation)
To meet exactly, place the zero on the plant pole at . The pole must give :
Closed loop: , so , .
| Quantity | Uncompensated | Bisector design | Final design |
|---|---|---|---|
| 1 | |||
| 16.3% | about 21% | 16.3% | |
| 4 s | about 2.04 s | 2 s | |
| 2 | 5.07 | 4 |
Answer: lead compensator gives and s with .
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Compensator for 4/[s(s+2)]: Mp 16.3%, ts, Kv · Control Systems, chapter 7
- Lead compensator for 10/[s(s+1)], ts=2 s, Mp=5% · Control Systems, chapter 7
- Lead compensator for 4/[s(s+2)], ts=2 s · Control Systems, chapter 7 · asked 2×
- (1+aTs)/(1+Ts) as lead or lag compensator · Control Systems, chapter 7
- Compensator for 4/[s(s+2)], ts=2 s, Kv=2 · Control Systems, chapter 7 · asked 2×
- Lead compensator for k/[s(1+0.1s)(1+0.001s)], Kv = 1000 · Control Systems, chapter 7 · asked 3×
- Lead compensator for satellite position control · Digital Control System, chapter 4
- Root-locus design: ζ = 0.5, ts = 2 s, plant 1/(s(s+2)) · Digital Control System, chapter 4 · asked 5×
- Root-locus design: ζ = 0.5, ts = 2 s, plant 1/(s(s+1)) · Digital Control System, chapter 4 · asked 5×
- Open-loop automobile cruise controller design · Embedded System, chapter 7 · asked 3×