Lead compensator for 4/[s(s+2)], ts=2 s
Short answer
A lead compensator designed via root locus method gives Gc(s) = 4.73 (s+2.93)/(s+5.46). The dominant closed-loop poles become -2 ± j3.464, achieving settling time 2 s with unchanged damping ratio 0.5 and approximately the same 16.3% overshoot.
For a unity feedback system with open loop transfer function G(s) = 4/[s(s+2)], design a Lead compensator such that settling time would become 2 seconds without change in maximum overshoot of the system.
The specification is in the time domain, so the lead compensator is designed by the root-locus method.
Step 1: Present system
Step 2: Desired poles
Same overshoot means same . New settling time 2 s:
Step 3: Angle deficiency
Step 4: Pole and zero by the bisector method
- Draw a horizontal line PA from to the left, and line PO to the origin. Angle APO .
- Bisect it: the bisector PB makes with PA (direction ).
- Draw PC and PD at from PB; they meet the real axis at the zero and pole.
Check: , , net lead ✓.
Step 5: Gain (magnitude condition)
Step 6: Compensated system
Closed-loop poles: (desired) and a third pole at , which lies close to the zero at , so its effect is small and the response is dominated by the desired pair.
jw
sd x | j3.46
\ |
--x---o--x---x--- sigma
-5.46 -2.93 -2 0
| Item | Before | After |
|---|---|---|
| 0.5 | 0.5 | |
| 2 rad/s | 4 rad/s | |
| 4 s | 2 s | |
| 16.3% | ≈16.3% | |
| 2 | 5.07 |
Alternative: placing the zero at (cancelling the plant pole) needs a pole at and gives with closed loop exactly .
Answer: ; dominant poles at −2 ± j3.46 give ts = 2 s with the same ζ = 0.5 (Mp ≈ 16%).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Compensator for 4/[s(s+2)], ts=2 s, Kv=2 · Control Systems, chapter 7 · asked 2×
- Lead compensator for 10/[s(s+1)], ts=2 s, Mp=5% · Control Systems, chapter 7
- Lead compensator for 4/[s(s+2)], Mp≤16.3%, ts≤2 s · Control Systems, chapter 7
- Transfer function from overshoot and settling time · Control Systems, chapter 3
- Overshoot, settling time and error for 50/[s(s+2)] · Control Systems, chapter 3
- Overshoot and settling time from pole plot · Control Systems, chapter 3
- Compensator for 4/[s(s+2)]: Mp 16.3%, ts, Kv · Control Systems, chapter 7
- Lead compensator for satellite position control · Digital Control System, chapter 4
- Root-locus design: ζ = 0.5, ts = 2 s, plant 1/(s(s+1)) · Digital Control System, chapter 4 · asked 5×
- Root-locus design: ζ = 0.5, ts = 2 s, plant 1/(s(s+2)) · Digital Control System, chapter 4 · asked 5×