Transformer losses and efficiency expression

Short answer

Core (iron) losses are constant; copper loss varies as I². Efficiency η = x S cos φ / (x S cos φ + Pi + x² Pcu), where x is load fraction, S rating, Pi core loss, Pcu full-load copper loss. Full-load η = S cos φ / (S cos φ + Pi + Pcu).

What are different types of losses in transformer? Derive the expression of efficiency of transformer.

Types of losses

1. Core (iron) losses occur in the core and are practically constant from no-load to full load (since V1 and f are constant).

  • Hysteresis loss: Pₕ = ηₕ Bm^1.6 f V, reduced by using silicon steel / CRGO.
  • Eddy current loss: Pₑ = kₑ Bm² f² t² V, reduced by thin insulated laminations.

2. Copper (I²R) losses occur in the primary and secondary windings and vary as the square of the load current: Pcu = I1² R1 + I2² R2 = I1² R01.

3. Stray and dielectric losses (small): leakage-flux losses in the tank and structure, and insulation losses (insignificant at normal voltages).

Since a transformer has no moving part, there are no friction or windage losses, so efficiency is very high (95–99 %).

Efficiency expression

Efficiency η = output power / input power = output / (output + losses).

Let the transformer have rating S (VA), secondary voltage V2, and let a fraction x of full load be supplied at a load power factor cos φ.

Output power           = x S cos φ
Iron loss              = Pi  (constant)
Copper loss at x load  = x² Pcu   (Pcu = full-load copper loss)

η = x S cos φ / ( x S cos φ + Pi + x² Pcu )

At full load (x = 1):

η = S cos φ / (S cos φ + Pi + Pcu)

Equivalent form using currents: η = V2 I2 cos φ2 / (V2 I2 cos φ2 + Pi + I2² R02).

Observations:

  • Efficiency depends on the power factor; it is lower for lower power factor.
  • For a given power factor, efficiency is highest at the load where Pi = x² Pcu.
  • All-day efficiency matters for distribution transformers, which are on 24 hours but loaded only part of the day.

Example: 100 kVA, Pi = 1 kW, Pcu = 1.5 kW at unity pf, full load: η = 100/(100 + 1 + 1.5) = 97.6 %.