Transformer losses and condition for maximum efficiency

Describe the various losses in a transformer. When the efficiency of a transformer will be maximum? Derive it mathematically.

A transformer has no moving parts, so it has no friction or windage loss. Its losses are core (iron) losses and copper losses.

Losses in a transformer

  1. Core or iron loss (PiP_i) – occurs in the core due to the alternating flux. It depends on BmB_m and ff, which are almost constant, so it is a constant loss (the same at all loads). It is measured by the open-circuit test.
    • Hysteresis loss: Ph=ηBm1.6fVP_h = \eta B_m^{1.6} f V; reduced by using silicon steel / CRGO.
    • Eddy current loss: Pe=KeBm2f2t2VP_e = K_e B_m^2 f^2 t^2 V; reduced by thin insulated laminations.
  2. Copper loss (PcuP_{cu}) – I12R1+I22R2=I22R02I_1^2R_1 + I_2^2R_2 = I_2^2 R_{02} in the windings. It varies with the square of the load current, so it is a variable loss. The full-load value is measured by the short-circuit test. At a fraction x of full load, Pcu=x2Pcu,flP_{cu} = x^2 P_{cu,fl}.
  3. Stray loss – from leakage flux causing eddy currents in the tank, clamps and conductors. Usually small and included in copper loss.
  4. Dielectric loss – in the insulation (oil, paper); important only at very high voltage.

Efficiency

η=outputoutput+losses=V2I2cos⁡ϕ2V2I2cos⁡ϕ2+Pi+I22R02\eta = \frac{\text{output}}{\text{output} + \text{losses}} = \frac{V_2 I_2\cos\phi_2}{V_2 I_2\cos\phi_2 + P_i + I_2^2 R_{02}}

Condition for maximum efficiency

Take V2V_2 and cos⁡ϕ2\cos\phi_2 as constant. Dividing the numerator and denominator by I2I_2:

η=V2cos⁡ϕ2V2cos⁡ϕ2+PiI2+I2R02\eta = \frac{V_2\cos\phi_2}{V_2\cos\phi_2 + \dfrac{P_i}{I_2} + I_2R_{02}}

η is maximum when the varying part of the denominator, D=PiI2+I2R02D = \dfrac{P_i}{I_2} + I_2R_{02}, is minimum:

dDdI2=−PiI22+R02=0I22R02=Pi\begin{aligned} \frac{dD}{dI_2} &= -\frac{P_i}{I_2^2} + R_{02} = 0 \\ I_2^2 R_{02} &= P_i \end{aligned}

(d2D/dI22=2Pi/I23>0d^2D/dI_2^2 = 2P_i/I_2^3 > 0, so it is a minimum of D.)

Efficiency is maximum when variable copper loss equals constant iron loss.

Load at maximum efficiency

x=I2I2,fl=PiPcu,fl,kVA at ηmax=rated kVA×PiPcu,flx = \frac{I_2}{I_{2,fl}} = \sqrt{\frac{P_i}{P_{cu,fl}}}, \qquad \text{kVA at } \eta_{max} = \text{rated kVA}\times\sqrt{\frac{P_i}{P_{cu,fl}}} ηmax=xScos⁡ϕxScos⁡ϕ+2Pi\eta_{max} = \frac{x S\cos\phi}{x S\cos\phi + 2P_i}

Also, for a given kVA, η is highest at unity power factor.

Example: a transformer with Pi=1P_i = 1 kW and Pcu,fl=4P_{cu,fl} = 4 kW has maximum efficiency at x=1/4=0.5x = \sqrt{1/4} = 0.5, i.e. half load. Distribution transformers are designed with low PiP_i so that η is maximum at about 50–70% load, as they are lightly loaded for much of the day.