Transformer losses, efficiency and maximum efficiency condition

Short answer

Core (iron) loss is constant; copper loss varies with load current squared. Efficiency = output/(output + iron loss + copper loss). Maximum efficiency occurs when copper loss equals iron loss, i.e., at load fraction x = √(Pi/Pcu,FL).

Explain the different power losses in the transformer and how the efficiency is calculated? Derive the condition at which the efficiency of transformer will be maximum.

A transformer has no moving parts, so it has no friction or windage loss. Its losses are of two kinds: core (iron) loss and copper loss.

1. Core or iron loss (PiP_i)

  • Hysteresis loss: energy lost in repeatedly magnetising the core in opposite directions. Ph=ηhBm1.6fVP_h = \eta_h B_m^{1.6} f V (Steinmetz). Reduced by using silicon steel (CRGO) with a narrow hysteresis loop.
  • Eddy current loss: circulating currents induced in the core. Pe=keBm2f2t2VP_e = k_e B_m^2 f^2 t^2 V, where tt is lamination thickness. Reduced by thin, insulated laminations (0.35-0.5 mm).
  • Since VV and ff are constant, BmB_m is constant, so iron loss is constant at all loads. It is measured by the open-circuit test.

2. Copper loss (PcuP_{cu})

  • I2RI^2R loss in primary and secondary windings: Pcu=I12R1+I22R2=I12R01=I22R02P_{cu} = I_1^2R_1 + I_2^2R_2 = I_1^2R_{01} = I_2^2R_{02}.
  • Varies with the square of load: at fraction xx of full load, Pcu=x2Pcu,FLP_{cu} = x^2P_{cu,FL}.
  • Measured by the short-circuit test.

Minor losses: stray loss (leakage flux in tank and clamps) and dielectric loss in insulation, usually neglected.

Calculating efficiency

η=OutputOutput+Losses=x Scos⁡ϕx Scos⁡ϕ+Pi+x2Pcu,FL×100\eta = \frac{\text{Output}}{\text{Output} + \text{Losses}} = \frac{x\,S\cos\phi}{x\,S\cos\phi + P_i + x^2P_{cu,FL}}\times 100

where SS = rated VA. Because efficiency is very high (95-99%), direct measurement of input and output is inaccurate; it is therefore found indirectly from the OC and SC test losses.

All-day efficiency (for distribution transformers) = output energy in kWh / input energy in kWh over 24 hours.

Condition for maximum efficiency

With V2V_2 and cos⁡ϕ\cos\phi constant:

η=V2I2cos⁡ϕV2I2cos⁡ϕ+Pi+I22R02\eta = \frac{V_2I_2\cos\phi}{V_2I_2\cos\phi + P_i + I_2^2R_{02}}

Dividing by I2I_2:

η=V2cos⁡ϕV2cos⁡ϕ+PiI2+I2R02\eta = \frac{V_2\cos\phi}{V_2\cos\phi + \dfrac{P_i}{I_2} + I_2R_{02}}

η\eta is maximum when the denominator is minimum, so

ddI2(PiI2+I2R02)=0−PiI22+R02=0Pi=I22R02=Pcu\begin{aligned} \frac{d}{dI_2}\left(\frac{P_i}{I_2} + I_2R_{02}\right) &= 0 \\ -\frac{P_i}{I_2^2} + R_{02} &= 0 \\ P_i &= I_2^2R_{02} = P_{cu} \end{aligned}

So efficiency is maximum when copper loss equals iron loss.

The load and current at maximum efficiency:

x=PiPcu,FL,I2=I2,FLPiPcu,FLx = \sqrt{\frac{P_i}{P_{cu,FL}}}, \qquad I_2 = I_{2,FL}\sqrt{\frac{P_i}{P_{cu,FL}}} ηmax=x Scos⁡ϕx Scos⁡ϕ+2Pi\eta_{max} = \frac{x\,S\cos\phi}{x\,S\cos\phi + 2P_i}

For a given load current, efficiency is highest at unity power factor.

Example: S=100S = 100 kVA, Pi=500P_i = 500 W, Pcu,FL=2000P_{cu,FL} = 2000 W: x=0.25=0.5x = \sqrt{0.25} = 0.5, so ηmax\eta_{max} at upf =5000050000+1000=98.04%= \frac{50000}{50000 + 1000} = 98.04\%.