Efficiency variation with load and maximum efficiency condition

Short answer

Efficiency is output divided by output plus losses; iron loss is constant while copper loss varies as the square of load. Differentiating efficiency gives maximum when copper loss equals iron loss, at load fraction x=sqrt(Pi/Pcu,FL).

Explain how the efficiency of a transformer varies with load. Derive the condition for maximum efficiency.

Efficiency of a transformer is the ratio of output power to input power: η=outputoutput+losses\eta = \frac{\text{output}}{\text{output} + \text{losses}}. Because one loss is constant and the other depends on load, efficiency changes with load.

Losses in a transformer

  • Iron (core) loss PiP_i = hysteresis + eddy-current loss. It depends on voltage and frequency, which are constant, so PiP_i is constant at all loads.
  • Copper loss PcuP_{cu} = I12R1+I22R2=I22R02I_1^2R_1 + I_2^2R_2 = I_2^2R_{02}. It varies with the square of the load current. At a fraction xx of full load, Pcu=x2Pcu,FLP_{cu} = x^2 P_{cu,FL}.

Variation of efficiency with load

At fraction xx of full load:

η=x Scos⁡ϕx Scos⁡ϕ+Pi+x2Pcu,FL\eta = \frac{x\,S\cos\phi}{x\,S\cos\phi + P_i + x^2 P_{cu,FL}}
  • At no load, output is zero, so η=0\eta = 0.
  • At light load, the fixed iron loss is large compared with the output, so η\eta is low but rises quickly.
  • As load increases, η\eta rises to a maximum where copper loss equals iron loss.
  • Beyond that, copper loss (growing as x2x^2) dominates and η\eta falls slowly.
  • At lower power factor, output is smaller for the same current, so the whole curve is lower.
 eta
  ^        max (Pcu = Pi)
  |         ____
  |      .-'    '--..___   upf
  |    .'  ___...--''--.._  0.8 pf
  |   / .-'
  |  /.'
  | //
  +-------------------------> load (x)
  0      x_max        1.0

Condition for maximum efficiency

Write η\eta in terms of secondary current I2I_2 (with V2V_2 and cos⁡ϕ\cos\phi constant):

η=V2I2cos⁡ϕV2I2cos⁡ϕ+Pi+I22R02\eta = \frac{V_2 I_2 \cos\phi}{V_2 I_2\cos\phi + P_i + I_2^2 R_{02}}

Divide numerator and denominator by I2I_2:

η=V2cos⁡ϕV2cos⁡ϕ+PiI2+I2R02\eta = \frac{V_2\cos\phi}{V_2\cos\phi + \dfrac{P_i}{I_2} + I_2R_{02}}

η\eta is maximum when the denominator is minimum:

ddI2(V2cos⁡ϕ+PiI2+I2R02)=0−PiI22+R02=0I22R02=Pi\begin{aligned} \frac{d}{dI_2}\left(V_2\cos\phi + \frac{P_i}{I_2} + I_2R_{02}\right) &= 0 \\ -\frac{P_i}{I_2^2} + R_{02} &= 0 \\ I_2^2 R_{02} &= P_i \end{aligned}

So efficiency is maximum when copper loss equals iron loss (variable loss = constant loss).

The current and load at maximum efficiency are:

I2=PiR02,x=PiPcu,FLI_2 = \sqrt{\frac{P_i}{R_{02}}}, \qquad x = \sqrt{\frac{P_i}{P_{cu,FL}}} ηmax=x Scos⁡ϕx Scos⁡ϕ+2Pi\eta_{max} = \frac{x\,S\cos\phi}{x\,S\cos\phi + 2P_i}

Example: if Pi=400P_i = 400 W and Pcu,FL=1600P_{cu,FL} = 1600 W, maximum efficiency occurs at x=400/1600=0.5x = \sqrt{400/1600} = 0.5, i.e. at half load. Distribution transformers are designed with low iron loss so that the maximum efficiency occurs at the light loads they carry most of the day.