Transformer losses and maximum efficiency condition

Short answer

Transformer losses are constant core (iron) loss Pi and variable copper loss Pcu = I2^2 R02. Efficiency η = (V2 I2 cosφ2) / (V2 I2 cosφ2 + Pi + I2^2 R02). Maximum occurs when d/dI2 denominator zero, giving Pi = I2^2 R02, i.e., copper loss equals iron loss.

What are the different types of losses in a transformer? Derive the condition for maximum efficiency of the transformer.

Losses in a transformer

A transformer has no moving parts, so there are only two kinds of loss.

  1. Core (iron) losses PiP_i: present whenever the primary is energised at rated voltage and frequency. They are practically constant from no load to full load.
    • Hysteresis loss: Ph=ηBmax1.6fVP_h = \eta B_{max}^{1.6} f V, from the repeated reversal of magnetisation. It is reduced by using silicon steel.
    • Eddy current loss: Pe∝Bmax2f2t2P_e \propto B_{max}^2 f^2 t^2, from currents induced in the core. It is reduced by thin insulated laminations.
  2. Copper losses PcuP_{cu}: I12R1+I22R2=I22R02I_1^2R_1 + I_2^2R_2 = I_2^2R_{02} in the windings. They vary as the square of the load current.

Stray (leakage flux) and dielectric losses are small and usually ignored.

Condition for maximum efficiency

Let the load current be I2I_2, secondary voltage V2V_2 (assumed constant), power factor cos⁡ϕ2\cos\phi_2 and R02R_{02} the total resistance referred to the secondary.

η=V2I2cos⁡ϕ2V2I2cos⁡ϕ2+Pi+I22R02\eta = \frac{V_2I_2\cos\phi_2}{V_2I_2\cos\phi_2 + P_i + I_2^2R_{02}}

Divide numerator and denominator by I2I_2:

η=V2cos⁡ϕ2V2cos⁡ϕ2+PiI2+I2R02\eta = \frac{V_2\cos\phi_2}{V_2\cos\phi_2 + \dfrac{P_i}{I_2} + I_2R_{02}}

For constant V2V_2 and cos⁡ϕ2\cos\phi_2, η\eta is maximum when the denominator is minimum:

ddI2(PiI2+I2R02)=0⇒−PiI22+R02=0\frac{d}{dI_2}\left(\frac{P_i}{I_2} + I_2R_{02}\right) = 0 \Rightarrow -\frac{P_i}{I_2^2} + R_{02} = 0 Pi=I22R02P_i = I_2^2R_{02}

Condition: efficiency is maximum when the variable (copper) loss equals the constant (iron) loss.

Load at maximum efficiency, with Pcu,flP_{cu,fl} the full-load copper loss:

x=I2I2,fl=PiPcu,fl,kVA at max η=rated kVA×PiPcu,flx = \frac{I_2}{I_{2,fl}} = \sqrt{\frac{P_i}{P_{cu,fl}}},\qquad \text{kVA at max } \eta = \text{rated kVA}\times\sqrt{\frac{P_i}{P_{cu,fl}}}

The second derivative is positive, so this is a minimum of the denominator and a maximum of η\eta. The condition does not depend on the power factor, but the value of the maximum efficiency is higher at a higher power factor.