Skip to main content

Transformer losses and efficiency expression

Short answer

Losses: core loss (hysteresis and eddy current) constant Pi, copper loss I1^2 R1 + I2^2 R2 varies as square of load. Efficiency for load fraction x is η = (x S cosφ) / (x S cosφ + Pi + x^2 Pcu,fl) where S is rated VA.

What are different types of losses in transformer? Derive the expression of efficiency of transformer.

Losses in a transformer

LossCauseNature
Hysteresis Ph=ηBmax1.6fVP_h = \eta B_{max}^{1.6} f VRepeated reversal of core magnetisationConstant (fixed VV, ff)
Eddy current Pe∝Bmax2f2t2P_e \propto B_{max}^2f^2t^2Currents induced in the coreConstant
Copper I12R1+I22R2I_1^2R_1 + I_2^2R_2Resistance of the windingsVaries as (load current)2^2

The first two together are the iron (core) loss PiP_i. Stray load loss and dielectric loss are small and neglected. Because there is no rotating part, there is no friction or windage loss.

Expression for efficiency

η=output powerinput power=outputoutput+losses\eta = \frac{\text{output power}}{\text{input power}} = \frac{\text{output}}{\text{output} + \text{losses}}

For a load that takes a fraction xx of the full-load current, at power factor cos⁡ϕ\cos\phi and rated secondary voltage V2V_2:

Output=x Scos⁡ϕ(S=V2I2,fl rated VA)Pcu=x2Pcu,flLosses=Pi+x2Pcu,fl\begin{aligned} \text{Output} &= x\,S\cos\phi\quad (S = V_2I_{2,fl}\ \text{rated VA}) \\ P_{cu} &= x^2P_{cu,fl} \\ \text{Losses} &= P_i + x^2P_{cu,fl} \end{aligned} η=xScos⁡ϕxScos⁡ϕ+Pi+x2Pcu,fl×100%\boxed{\eta = \frac{xS\cos\phi}{xS\cos\phi + P_i + x^2P_{cu,fl}}\times100\%}

Remarks:

  • Efficiency is zero at no load, rises with load, reaches a maximum when Pi=x2Pcu,flP_i = x^2P_{cu,fl}, and then falls.
  • For a good power transformer η\eta is 95 to 99%.
  • The efficiency is higher at a higher power factor, since the output power is larger for the same losses.

✓ Answer checked by Claude Opus 5.5 (high effort)

All Electrical Machines chapter 2 questions →