- 2068 Magh · 8 marks
250/500 V test; equivalent circuit, max efficiency output
Short answer
Equivalent circuit referred to 250 V primary: R0=781 Ω, X0=264 Ω, Req=0.174 Ω, Xeq=0.379 Ω. Maximum efficiency occurs at x=√(80/100)=0.8944 of rated kVA, i.e. 5.37 kVA; at 0.9 pf lagging output is 4.83 kW. Efficiency there is 96.8%.
Test data on a 1-phase, 250/500 V, 50 Hz transformer are: O.C. Test: 250 V, 1 A, 80 W (carried on L.V. side) S.C. Test: 20 V, 12 A, 100 W (carried on H.V. side) Then draw the equivalent circuit referred to primary side and find out the output power to obtain maximum efficiency at 0.9 lag p.f.
Given: 250/500 V, 50 Hz. Primary = 250 V (LV), . The kVA rating is not given, so the SC-test current (12 A on the HV side) is taken as the rated current, giving kVA. (The output at maximum efficiency found below does not actually depend on this assumption.)
Open-circuit test (on the LV side)
The no-load power is almost entirely core loss, so the shunt branch is found from it.
Short-circuit test (on the HV side)
At the reduced test voltage the core loss is negligible, so the wattmeter reading is the copper loss.
Referring to the LV side
The turns ratio is , so . Impedances are multiplied by when moved from LV to HV, and divided by when moved from HV to LV.
Equivalent circuit referred to the LV side
Req=0.174 ohm Xeq=0.379 ohm
o--+-----/\/\/\-----UUUU------o
|
[R0=781.25] [X0=263.9] Load
| (in parallel)
o--+---------------------------o
, (), shunt branch in parallel with .
Output power for maximum efficiency at 0.9 lag
The core loss is the OC wattmeter reading, W. The copper loss at the SC-test current is the SC wattmeter reading, 100 W, which is taken as the full-load copper loss .
Maximum efficiency occurs when copper loss equals iron loss:
Without assuming a rating: at maximum efficiency the copper loss must equal 80 W, so the HV current is A and kW, the same result.
Check of efficiency: .
Answer: output power at maximum efficiency kW (5.37 kVA at 0.9 pf lagging); equivalent circuit parameters are as above
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 250/500 V transformer test, equivalent circuit · Electrical Machines, chapter 2
- Equivalent circuit and half-load efficiency of 50 kVA transformer · Electrical Machines I, chapter 2
- Transformer equivalent circuit referred to primary · Electrical Machines I, chapter 2
- 20 kVA 250/2500 V tests, equivalent circuit · Electrical Machines, chapter 2 · asked 2×
- Equivalent circuit of 20 kVA 250/2500 V transformer from tests · Electrical Machines I, chapter 2 · asked 3×
- Equivalent circuit, efficiency and regulation of 5 kVA transformer · Electrical Machines I, chapter 2
- 250/500 V transformer: max-efficiency output · Electrical Machine, chapter 2
- 20 kVA 250/2500 V test parameters · Electrical Machine, chapter 2 · asked 2×
- Iron loss and maximum efficiency of 20 kVA 250/2500 V transformer · Electrical Machines I, chapter 2 · asked 2×
- Equivalent circuit of 8 kVA 400/120 V transformer · Electrical Machines I, chapter 2