250/500 V test; equivalent circuit, max efficiency output

Short answer

Equivalent circuit referred to 250 V primary: R0=781 Ω, X0=264 Ω, Req=0.174 Ω, Xeq=0.379 Ω. Maximum efficiency occurs at x=√(80/100)=0.8944 of rated kVA, i.e. 5.37 kVA; at 0.9 pf lagging output is 4.83 kW. Efficiency there is 96.8%.

Test data on a 1-phase, 250/500 V, 50 Hz transformer are: O.C. Test: 250 V, 1 A, 80 W (carried on L.V. side) S.C. Test: 20 V, 12 A, 100 W (carried on H.V. side) Then draw the equivalent circuit referred to primary side and find out the output power to obtain maximum efficiency at 0.9 lag p.f.

Given: 250/500 V, 50 Hz. Primary = 250 V (LV), K=2K = 2. The kVA rating is not given, so the SC-test current (12 A on the HV side) is taken as the rated current, giving S=500×12=6S = 500\times12 = 6 kVA. (The output at maximum efficiency found below does not actually depend on this assumption.)

Open-circuit test (on the LV side)

The no-load power is almost entirely core loss, so the shunt branch is found from it.

cos⁡ϕ0=P0V0I0=80250×1=0.32Iw=I0cos⁡ϕ0=0.32 A,Iμ=I02−Iw2=0.9474 AR0=V0Iw=781.25 Ω,X0=V0Iμ=263.9 Ω(on the LV side)\begin{aligned} \cos\phi_0 &= \frac{P_0}{V_0I_0} = \frac{80}{250\times1} = 0.32 \\ I_w &= I_0\cos\phi_0 = 0.32\ \text{A},\qquad I_\mu = \sqrt{I_0^2 - I_w^2} = 0.9474\ \text{A} \\ R_0 &= \frac{V_0}{I_w} = 781.25\ \Omega,\qquad X_0 = \frac{V_0}{I_\mu} = 263.9\ \Omega\quad(\text{on the LV side}) \end{aligned}

Short-circuit test (on the HV side)

At the reduced test voltage the core loss is negligible, so the wattmeter reading is the copper loss.

Zsc=VscIsc=2012=1.667 ΩRsc=PscIsc2=100122=0.6944 ΩXsc=Zsc2−Rsc2=1.515 Ω(on the HV side)\begin{aligned} Z_{sc} &= \frac{V_{sc}}{I_{sc}} = \frac{20}{12} = 1.667\ \Omega \\ R_{sc} &= \frac{P_{sc}}{I_{sc}^2} = \frac{100}{12^2} = 0.6944\ \Omega \\ X_{sc} &= \sqrt{Z_{sc}^2 - R_{sc}^2} = 1.515\ \Omega\quad(\text{on the HV side}) \end{aligned}

Referring to the LV side

The turns ratio is K=500/250=2K = 500/250 = 2, so K2=4K^2 = 4. Impedances are multiplied by K2K^2 when moved from LV to HV, and divided by K2K^2 when moved from HV to LV.

Req=0.6944÷4=0.1736 ΩXeq=1.515÷4=0.3788 Ω\begin{aligned} R_{eq} &= 0.6944 \div 4 = 0.1736\ \Omega \\ X_{eq} &= 1.515 \div 4 = 0.3788\ \Omega \end{aligned}

Equivalent circuit referred to the LV side

   Req=0.174 ohm   Xeq=0.379 ohm
 o--+-----/\/\/\-----UUUU------o
    |                          
   [R0=781.25] [X0=263.9]   Load
    |      (in parallel)
 o--+---------------------------o

Req=0.1736 ΩR_{eq} = 0.1736\ \Omega, Xeq=0.3788 ΩX_{eq} = 0.3788\ \Omega (Zeq=0.4167 ΩZ_{eq} = 0.4167\ \Omega), shunt branch R0=781.25 ΩR_0 = 781.25\ \Omega in parallel with X0=263.9 ΩX_0 = 263.9\ \Omega.

Output power for maximum efficiency at 0.9 lag

The core loss is the OC wattmeter reading, Pi=80P_i = 80 W. The copper loss at the SC-test current is the SC wattmeter reading, 100 W, which is taken as the full-load copper loss Pcu,flP_{cu,fl}.

Maximum efficiency occurs when copper loss equals iron loss:

x2Pcu,fl=Pi⇒x=80100=0.8944kVA at ηmax=0.8944×6=5.367 kVAPout=5.367×0.9=4.830 kW\begin{aligned} x^2P_{cu,fl} &= P_i \Rightarrow x = \sqrt{\frac{80}{100}} = 0.8944 \\ \text{kVA at } \eta_{max} &= 0.8944\times6 = 5.367\ \text{kVA} \\ P_{out} &= 5.367\times0.9 = 4.830\ \text{kW} \end{aligned}

Without assuming a rating: at maximum efficiency the copper loss must equal 80 W, so the HV current is 120.8=10.7312\sqrt{0.8} = 10.73 A and Pout=500×10.73×0.9=4.83P_{out} = 500\times10.73\times0.9 = 4.83 kW, the same result.

Check of efficiency: ηmax=48304830+2×80×100=96.8%\eta_{max} = \dfrac{4830}{4830 + 2\times80}\times100 = 96.8\%.

Answer: output power at maximum efficiency ≈4.83\approx 4.83 kW (5.37 kVA at 0.9 pf lagging); equivalent circuit parameters are as above