T-N characteristics; effect of rotor resistance and voltage

Short answer

Torque-speed curve has moderate starting torque, rises to maximum at sm=R2/X2, then falls linearly to zero at synchronous speed; rated operation is on the stable falling part. Rotor resistance does not change Tmax but shifts the peak to lower speed; voltage changes torque as V^2 without changing sm.

Describe the torque speed characteristics of an induction motor. Discuss the effect of rotor resistance and applied voltage on T-N characteristics of such motors.

Torque-speed characteristics

The torque of an induction motor is

T=3ωs⋅sE22R2R22+(sX2)2T = \frac{3}{\omega_s}\cdot\frac{s E_2^2 R_2}{R_2^2 + (sX_2)^2}
 T
 |            Tmax
 |          _.-*-._
 |   Tst  /         \
 |    *--'            \
 |   /                  \
 +--+------+----------------+--> N
  N=0   N(Tmax)             Ns
  • At N=0N=0 the torque is the starting torque, which is moderate.
  • The torque rises as the motor accelerates until the maximum (breakdown) torque occurs at sm=R2/X2s_m = R_2/X_2.
  • From there to NsN_s the torque falls nearly linearly to zero. Rated operation is on this falling part at 2 to 5 % slip, so speed changes very little with load.
  • At NsN_s the torque is zero.
  • The part left of TmaxT_{max} is unstable; the part right of it is stable.

Effect of rotor resistance

  • Tmax=3E222ωsX2T_{max} = \frac{3E_2^2}{2\omega_s X_2} does not depend on R2R_2.
  • The slip at maximum torque sm=R2/X2s_m = R_2/X_2 increases with R2R_2, so the peak shifts to lower speed.
  • Starting torque rises with R2R_2 and is maximum when R2=X2R_2 = X_2.
  • Full-load speed falls and rotor copper loss rises (lower efficiency).
  • Used in wound-rotor motors for high-torque starting and speed control.
 T   R2 low   R2 med   R2 = X2
 |   peak at high N     peak at N = 0

Effect of applied voltage

E2∝V1E_2 \propto V_1, so T∝V12T \propto V_1^2 at any speed.

  • Both TstT_{st} and TmaxT_{max} vary as V2V^2 (a 10 % voltage drop gives about 19 % less torque).
  • sms_m does not change, so the peak stays at the same speed.
  • At a fixed load torque, a lower voltage gives a higher slip, a higher rotor current and more heating.
  • Reduced-voltage starting (star-delta, autotransformer) reduces starting current but also starting torque.

✓ Answer checked by Claude Opus 5.5 (high effort)