- 2075 Bhadra · 8 marks
Guard ring sizing for 3-unit string at 20 kV
Short answer
The line-end unit voltage is 7.06 kV (top unit 5.88 kV, middle unit 7.06 kV). The required ring-to-pin capacitance is 0.367C (or 11C/30).
In a transmission line, each conductor is at 20 kV and supported by a string of 3 suspension insulators. The air-capacitance between each cap-pin junction and tower is 1/5th of the capacitance C of each insulator unit. A guard ring, effectively only over the line end insulator unit, is fitted so that the voltages on the two units nearest the line-end are equal. (i) Calculate the voltage on the line-end unit. (ii) Calculate the value of capacitance between the ring and pin.
The guard ring adds a capacitance between the ring (at line potential) and the link pin at the top of the line-end unit. This capacitance is chosen so that the two units nearest the line share the voltage equally.
Tower ─[C]─ A ─[C]─ B ─[C]─ Line (20 kV)
| | \
C/5 C/5 Cx (ring to pin B)
| |
earth earth
Units: 1 (tower end), 2, 3 (line end), with voltages . The shunt capacitance is , and the condition is .
Junction A (no guard ring capacitance)
Junction B (guard ring capacitance to line)
The voltage of B to earth is , and to the line it is :
With :
(i) Voltage on the line-end unit
String efficiency .
(ii) Capacitance between ring and pin
Answer: (i) The line-end unit carries 7.06 kV (top unit 5.88 kV, middle unit 7.06 kV). (ii) The ring-to-pin capacitance is .
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 3-unit string with guard ring: redistribution of voltage · Power System Analysis I, chapter 2
- 4-unit string with guard ring (10% and 6%) · Power System Analysis I, chapter 2 · asked 2×
- 4-unit string with guard ring (10% and 5%) · Power System Analysis I, chapter 2 · asked 2×
- Greatest working voltage of 3-unit string, 20 kV limit · Power System Analysis I, chapter 2
- String of 4 insulators at 66 kV, ratio 10 · Power System Analysis I, chapter 2
- String of 5 insulators on 100 kV, ratio 0.1 · Power System Analysis I, chapter 2
- Voltage distribution of 3-unit string with guard ring · High Voltage Engineering, chapter 5
- Guard ring capacitances for 5-disc string · High Voltage Engineering, chapter 5
- Insulator discs per string, 180 MW over 200 km · Transmission and Distribution System Design, chapter 3
- Classify insulators; string insulator configurations · Transmission and Distribution System Design, chapter 3