Transposition and transposition cycle layouts
Short answer
Transposition balances phase inductances and capacitances in unsymmetrical spacing, reducing voltage unbalance and interference. A single-circuit cycle uses three sections, each conductor rotating through all positions. A double-circuit cycle transposes both circuits similarly while maintaining phase symmetry.
Why is transposition carried out in overhead transmission lines? Draw the schematic layout for a complete transposition cycle for 3-φ single circuit and 3-φ double circuit transmission lines.
Transposition is the exchange of the positions of the phase conductors at regular intervals along the line, so that each conductor occupies each position for an equal length.
Why transposition is done
- With unsymmetrical spacing, each phase has different flux linkages and charges, so the inductance and capacitance of the phases are unequal.
- This causes unequal voltage drops and unbalanced receiving-end voltages even for a balanced load.
- Transposition makes the average and of every phase equal, so the line is balanced and can be analysed per phase with .
- It reduces interference with nearby communication (telephone) lines, because the induced voltages from the three sections cancel.
- In practice transposition is done at switching stations or every few tens of km.
Complete transposition cycle: 3-φ single circuit
The line length is divided into three equal sections; each phase takes positions 1, 2 and 3 in turn.
Pos Sec I Sec II Sec III
1 a ------\ c ------\ b ------
2 b ------\ a ------\ c ------
3 c ------ b ------ a ------
|<-l/3->| |<-l/3->| |<-l/3->|
| Position | Section I | Section II | Section III |
|---|---|---|---|
| 1 | a | c | b |
| 2 | b | a | c |
| 3 | c | b | a |
Complete transposition cycle: 3-φ double circuit
Both circuits are transposed together, and the same pattern is kept in every section: the two middle conductors belong to the same phase, and the top conductor of each circuit is the same phase as the bottom conductor of the other (in Section I, a is opposite c', b opposite b', and c opposite a').
Sec I Sec II Sec III
a o o c' c o o b' b o o a'
b o o b' a o o a' c o o c'
c o o a' b o o c' a o o b'
|<--l/3-->| |<--l/3-->| |<--l/3-->|
| Row | Section I | Section II | Section III |
|---|---|---|---|
| Top | a, c' | c, b' | b, a' |
| Middle | b, b' | a, a' | c, c' |
| Bottom | c, a' | b, c' | a, b' |
In each section the phases shift by one position, and over the full cycle every phase of each circuit occupies every position once.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Transposition; single-phase capacitance with earth · Power System Analysis I, chapter 4
- Requirements of conductors for overhead lines · Power System Analysis I, chapter 2 · asked 2×
- Proximity effect in cables vs overhead lines · Power System Analysis I, chapter 4
- Inductance of transposed double circuit, 0.9 cm radius · Power System Analysis I, chapter 4
- Underground cables vs overhead lines · Power System Analysis I, chapter 2
- Proximity effect in overhead lines · Power System Analysis I, chapter 4
- T/F: double earth wire for 400 kV single circuit · Transmission and Distribution System Design, chapter 3
- T/F: tower height same for single/double circuit · Transmission and Distribution System Design, chapter 4
- Single vs double earth wire selection · Transmission and Distribution System Design, chapter 3
- Design: 250 m head plant, 66 kV double circuit · Power Plant Design, chapter 4 · asked 13×