- 2068 Bhadra (old course) · 5 marks
T/F: tower height same for single/double circuit
Short answer
FALSE. For the same voltage, a double-circuit tower is taller because it requires three cross-arm levels versus one or two for a single circuit, adding roughly one to two vertical spacing increments (e.g., about 4.9 m at 220 kV).
State whether the following statement is TRUE or FALSE and give reasons briefly: The height of tower is same for single circuit and double circuit for the same voltage level.
FALSE.
For the same voltage, a double-circuit tower is generally taller than a single-circuit tower.
- A single circuit has only 3 conductors. They can be placed horizontally (one cross-arm level) or in a triangle (two levels). The tower height is roughly ground clearance + maximum sag + one level of spacing + earth wire height.
- A double circuit has 6 conductors. They are normally arranged as two vertical circuits on either side of the tower, giving three cross-arm levels. The height becomes ground clearance + sag + + earth wire height, where is the vertical separation (about 4.9 m at 220 kV).
| Item (220 kV, same span) | Single circuit | Double circuit |
|---|---|---|
| Conductor levels | 1–2 | 3 |
| Typical tower height | ≈ 30–35 m | ≈ 40–45 m |
| Base width / weight | Smaller | Larger (about 1.5–1.8 times) |
The ground clearance and sag are the same for both, but the extra cross-arm levels add about one to two times to the double-circuit tower. Double-circuit towers also carry twice the conductor loads, so their base and weight are larger too.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- T/F: tower height function of voltage only · Transmission and Distribution System Design, chapter 4 · asked 2×
- T/F: double earth wire for 400 kV single circuit · Transmission and Distribution System Design, chapter 3
- T/F: tower height independent of span · Transmission and Distribution System Design, chapter 4 · asked 2×
- T/F: earth wire choice depends on circuit and voltage · Transmission and Distribution System Design, chapter 3
- Tower dimensions for 220 kV double circuit line · Transmission and Distribution System Design, chapter 4 · asked 2×
- Tower dimensions for 220 kV single circuit line · Transmission and Distribution System Design, chapter 4 · asked 2×
- True/false: load rejection raises terminal voltage · High Voltage Engineering, chapter 3
- True/false: cables suppress switching overvoltage · High Voltage Engineering, chapter 3
- True/false: protective ratio and grounding · High Voltage Engineering, chapter 4
- True/false: cross-arm length and string efficiency · High Voltage Engineering, chapter 5
All Transmission and Distribution System Design chapter 4 questions →