Modelling 500 km as medium, 50 km as long
Short answer
Modeling a500 km line with medium-line model yields inaccurate voltage, regulation, and Ferranti rise because distributed capacitance is ignored; the exact long-line model must be used. Modeling a50 km line with the long-line model gives correct but unnecessarily complex results; short-line approximation suffices.
What will happen if a 500 km long transmission line is modeled using the medium length transmission line model and a 50 km long line is represented by the long length model?
500 km line modelled as a medium line (nominal-Π or T)
- A 500 km line is a long line. Its parameters are distributed, and is large (about 0.5 rad at 50 Hz), so and are no longer close to and .
- The nominal model lumps all capacitance at one or two points. This gives errors in , , and hence in the sending-end voltage, current, power factor, regulation and losses. The error grows rapidly with length.
- The Ferranti rise at light load and the reactive power generated by the line are wrongly estimated, so the size of shunt reactors and the insulation level may be chosen wrongly.
- The results are therefore inaccurate and unsafe for design. The exact long-line model (or its equivalent-Π) must be used.
50 km line modelled by the long-line model
- The long-line equations are exact for any length, so the results will be correct.
- For 50 km, is very small, so , , . The answers become almost the same as the short-line model (, , ).
- The only cost is unnecessary calculation with complex hyperbolic functions, for no practical gain.
| Case | Accuracy | Practical effect |
|---|---|---|
| 500 km on medium model | Poor | Wrong , , regulation |
| 50 km on long model | Exact | Correct but more effort |
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Long line by short model and vice versa · Power System Analysis I, chapter 5 · asked 2×
- Equivalent-T of 300 km long line · Power System Analysis I, chapter 5
- Nominal-T 100 km line, 50 MVA at 132 kV · Power System Analysis I, chapter 6
- 280 km, 60 Hz line: nominal-π vs long line · Power System Analysis I, chapter 5 · asked 2×
- Equivalent-π model of a long line · Power System Analysis I, chapter 5
- 150 km line by T-model, 60 MW · Power System Analysis I, chapter 5
- Incremental model of a transmission line · Telecommunications, chapter 2
- Design: 230 m head plant, 20 km line · Power Plant Design, chapter 4 · asked 14×
- Design: 230 m head plant, 55 km line · Power Plant Design, chapter 4 · asked 12×
- 6° phase shift per 100 km of lossless line · High Voltage Engineering, chapter 3