Y‑bus: diagonal 4.0701 − j17.1798 pu, off‑diagonal −2.0351 + j8.6099 pu. Generator reactive power Q2 = 0.2236 pu. V2 = 1.0300∠2.76° pu, V3 = 0.9891∠−2.05° pu. Total real power loss = 0.0290 pu.
A 3-bus power system is shown in figure. The series impedance and shunt admittance of each line are 0.026+j0.11 pu and j0.04 pu respectively. The bus specification, power and bus voltage are as under. (PG, QG, PL, QL and bus voltages are in pu). [Figure: three buses with lines 1-2, 1-3 and 2-3]
Bus No.
PG
QG
PL
QL
Bus voltage
Bus type
1
?
?
1.0
0.5
1.03∠0°
Slack
2
1.5
?
0.5
0
1.03
PV
3
0
0
1.2
0.5
?
PQ
i) Form YBUS ii) Generator reactive power at bus 2 using Gauss-Seidel method (up to first iteration) iii) Voltage at bus 2 and 3 using Gauss-Seidel method (up to first iteration) iv) Total network real power loss (after first iteration)
Bus 1 is the slack bus, bus 2 a PV bus and bus 3 a PQ bus. The line shunt admittance j0.04 pu is taken as the total line-charging admittance of each line, so j0.02 pu is placed at each end (nominal-π model). Gauss-Seidel is used with no acceleration factor.
k=1∑3Y2kVkQ2(1)=0.0611−j0.2171=−Im{V2∗∑kY2kVk}=0.2236puV2(1)V2∗P2−jQ2∑k=2Y2kVkV2(1)δ2=Y221[V2∗P2−jQ2−Y21V1−Y23V3]=1.03001.0000−j0.2236=0.9709−j0.2171=−4.1312+j17.4781=4.0701−j17.1798(0.9709−j0.2171)−(−4.1312+j17.4781)=1.0419+j0.0501=2.7554∘⇒V2(1)=1.0300∠2.7554∘=1.0288+j0.0495(magnitude reset to 1.03)V3(1)V3∗P3−jQ3∑k=3Y3kVkV3(1)=Y331[V3∗P3−jQ3−Y31V1−Y32V2]=1.0000−1.2000+j0.5000=−1.2000+j0.5000=−4.6161+j17.6254=4.0701−j17.1798(−1.2000+j0.5000)−(−4.6161+j17.6254)=0.9885−j0.0353=0.9891∠−2.0473∘pu
So V2(1)=1.0300∠2.7554∘ pu and V3(1)=0.9891∠−2.0473∘ pu.
iv) Total network real power loss (after first iteration)
Slack bus power with the first-iteration voltages: