G-S first iteration with line charging

Short answer

Y‑bus: diagonal 4.0701 − j17.1798 pu, off‑diagonal −2.0351 + j8.6099 pu. Generator reactive power Q2 = 0.2236 pu. V2 = 1.0300∠2.76° pu, V3 = 0.9891∠−2.05° pu. Total real power loss = 0.0290 pu.

A 3-bus power system is shown in figure. The series impedance and shunt admittance of each line are 0.026+j0.11 pu and j0.04 pu respectively. The bus specification, power and bus voltage are as under. (PG, QG, PL, QL and bus voltages are in pu). [Figure: three buses with lines 1-2, 1-3 and 2-3]

Bus No.PGQGPLQLBus voltageBus type
1??1.00.51.03∠0°Slack
21.5?0.501.03PV
3001.20.5?PQ

i) Form YBUS ii) Generator reactive power at bus 2 using Gauss-Seidel method (up to first iteration) iii) Voltage at bus 2 and 3 using Gauss-Seidel method (up to first iteration) iv) Total network real power loss (after first iteration)

Bus 1 is the slack bus, bus 2 a PV bus and bus 3 a PQ bus. The line shunt admittance j0.04 pu is taken as the total line-charging admittance of each line, so j0.02j0.02 pu is placed at each end (nominal-π model). Gauss-Seidel is used with no acceleration factor.

Net injections: P2=1.5−0.5=1.0P_2 = 1.5 - 0.5 = 1.0 pu; P3=−1.2P_3 = -1.2 pu, Q3=−0.5Q_3 = -0.5 pu. Initial values: V2(0)=1.03∠0∘V_2^{(0)} = 1.03\angle 0^\circ, V3(0)=1∠0∘V_3^{(0)} = 1\angle 0^\circ.

i) Y-bus

yseries=10.026+j0.110=2.0351−j8.6099 puYii=2yseries+2(j0.02)=4.0701−j17.1798Yij=−yseries=−2.0351+j8.6099\begin{aligned} y_{series} &= \frac{1}{0.026 + j0.110} = 2.0351 - j8.6099\ \text{pu} \\ Y_{ii} &= 2y_{series} + 2(j0.02) = 4.0701 - j17.1798 \\ Y_{ij} &= -y_{series} = -2.0351 + j8.6099 \end{aligned} Ybus=[4.0701−j17.1798−2.0351+j8.6099−2.0351+j8.6099−2.0351+j8.60994.0701−j17.1798−2.0351+j8.6099−2.0351+j8.6099−2.0351+j8.60994.0701−j17.1798] puY_{bus} = \begin{bmatrix} 4.0701 - j17.1798 & -2.0351 + j8.6099 & -2.0351 + j8.6099 \\ -2.0351 + j8.6099 & 4.0701 - j17.1798 & -2.0351 + j8.6099 \\ -2.0351 + j8.6099 & -2.0351 + j8.6099 & 4.0701 - j17.1798 \end{bmatrix}\ \text{pu}

ii) Generator reactive power at bus 2 (first iteration)

∑kY2kVk(0)=0.0611−j0.2171Q2(1)=−Im{V2∗∑kY2kVk}=0.2236 puQG2=Q2+QL2=0.2236+0=0.2236 pu\begin{aligned} \textstyle\sum_k Y_{2k}V_k^{(0)} &= 0.0611 - j0.2171 \\ Q_2^{(1)} &= -\text{Im}\{V_2^{*}\textstyle\sum_k Y_{2k}V_k\} = 0.2236\ \text{pu} \\ Q_{G2} &= Q_2 + Q_{L2} = 0.2236 + 0 = 0.2236\ \text{pu} \end{aligned}

No Q-limits are given, so bus 2 remains a PV bus.

iii) Voltages at buses 2 and 3 (first iteration)

Iteration 1

∑k=13Y2kVk=0.0611−j0.2171Q2(1)=−Im{V2∗∑kY2kVk}=0.2236 pu\begin{aligned} \sum_{k=1}^{3} Y_{2k}V_k &= 0.0611 - j0.2171 \\ Q_2^{(1)} &= -\text{Im}\{V_2^{*}\textstyle\sum_k Y_{2k}V_k\} = 0.2236\ \text{pu} \end{aligned} V2(1)=1Y22[P2−jQ2V2∗−Y21V1−Y23V3]P2−jQ2V2∗=1.0000−j0.22361.0300=0.9709−j0.2171∑k≠2Y2kVk=−4.1312+j17.4781V2(1)=(0.9709−j0.2171)−(−4.1312+j17.4781)4.0701−j17.1798=1.0419+j0.0501δ2=2.7554∘⇒V2(1)=1.0300∠2.7554∘=1.0288+j0.0495 (magnitude reset to 1.03)\begin{aligned} V_2^{(1)} &= \frac{1}{Y_{22}}\left[\frac{P_2 - jQ_2}{V_2^{*}} - Y_{21}V_1 - Y_{23}V_3\right] \\ \frac{P_2 - jQ_2}{V_2^{*}} &= \frac{1.0000 - j0.2236}{1.0300} = 0.9709 - j0.2171 \\ \textstyle\sum_{k\ne 2} Y_{2k}V_k &= -4.1312 + j17.4781 \\ V_2^{(1)} &= \frac{(0.9709 - j0.2171) - (-4.1312 + j17.4781)}{4.0701 - j17.1798} = 1.0419 + j0.0501 \\ \delta_2 &= 2.7554^\circ \Rightarrow V_2^{(1)} = 1.0300\angle 2.7554^\circ = 1.0288 + j0.0495\ \text{(magnitude reset to }1.03\text{)} \end{aligned} V3(1)=1Y33[P3−jQ3V3∗−Y31V1−Y32V2]P3−jQ3V3∗=−1.2000+j0.50001.0000=−1.2000+j0.5000∑k≠3Y3kVk=−4.6161+j17.6254V3(1)=(−1.2000+j0.5000)−(−4.6161+j17.6254)4.0701−j17.1798=0.9885−j0.0353=0.9891∠−2.0473∘ pu\begin{aligned} V_3^{(1)} &= \frac{1}{Y_{33}}\left[\frac{P_3 - jQ_3}{V_3^{*}} - Y_{31}V_1 - Y_{32}V_2\right] \\ \frac{P_3 - jQ_3}{V_3^{*}} &= \frac{-1.2000 + j0.5000}{1.0000} = -1.2000 + j0.5000 \\ \textstyle\sum_{k\ne 3} Y_{3k}V_k &= -4.6161 + j17.6254 \\ V_3^{(1)} &= \frac{(-1.2000 + j0.5000) - (-4.6161 + j17.6254)}{4.0701 - j17.1798} = 0.9885 - j0.0353 \\ &= 0.9891\angle -2.0473^\circ\ \text{pu} \end{aligned}

So V2(1)=1.0300∠2.7554∘V_2^{(1)} = 1.0300\angle 2.7554^\circ pu and V3(1)=0.9891∠−2.0473∘V_3^{(1)} = 0.9891\angle -2.0473^\circ pu.

iv) Total network real power loss (after first iteration)

Slack bus power with the first-iteration voltages:

P1−jQ1=V1∗∑kY1kVk=(1.0300)(−0.0351−j0.3556)=−0.0362−j0.3662⇒P1=−0.0362 pu,Q1=0.3662 puPG1=P1+PL1=−0.0362+1.00=0.9638 puQG1=Q1+QL1=0.3662+0.50=0.8662 pu\begin{aligned} P_1 - jQ_1 &= V_1^{*}\textstyle\sum_k Y_{1k}V_k = (1.0300)(-0.0351 - j0.3556) \\ &= -0.0362 - j0.3662 \\ \Rightarrow P_1 &= -0.0362\ \text{pu},\quad Q_1 = 0.3662\ \text{pu} \\ P_{G1} &= P_1 + P_{L1} = -0.0362 + 1.00 = 0.9638\ \text{pu} \\ Q_{G1} &= Q_1 + Q_{L1} = 0.3662 + 0.50 = 0.8662\ \text{pu} \end{aligned}

Total loss = sum of the calculated net injections at all buses (equal to the sum of all line losses):

BusPiP_i (pu)QiQ_i (pu)
1-0.03620.3662
21.26900.0843
3-1.2038-0.4518
Sum0.0290-0.0013
Ploss=∑Pi=0.0290 puQloss=∑Qi=−0.0013 pu\begin{aligned} P_{loss} &= \textstyle\sum P_i = 0.0290\ \text{pu} \\ Q_{loss} &= \textstyle\sum Q_i = -0.0013\ \text{pu} \end{aligned}

Answer: QG2=0.2236Q_{G2} = 0.2236 pu, V2=1.0300∠2.7554∘V_2 = 1.0300\angle 2.7554^\circ pu, V3=0.9891∠−2.0473∘V_3 = 0.9891\angle -2.0473^\circ pu, total real power loss =0.0290= 0.0290 pu (about 2.90 MW on a 100 MVA base).

✓ Answer checked by Claude Sonnet 5.5