- Asked 2/21
- 2076 Baisakh · 14 marks
Intermediate beam for office hall 16 m x 6 m
Short answer
Provide ISMB 300. Factored moment 137.3 kN·m < moment capacity 152.4 kN·m; shear 87.2 kN < 303.1 kN; deflection 10.27 mm < L/300 = 21 mm. Lateral stability is ensured because the compression flange is continuously supported by the slab.
An office hall measuring 16m x 6m consists of beams spaced at 3m c/c. RCC slab of 12cm is cast over the beam. The imposed load is 3kN/m². The beam is supported on 300mm wall. The compression flange is supported throughout its length. Design intermediate beam and check for shear, deflection and lateral stability.
Data
- Steel Fe 410 (E250): N/mm², N/mm², N/mm², (IS 800:2007, Table 5). Limit state design.
- Effective span m, bearing length of support mm.
Loads and design forces
The hall is 6 m wide, so the beams span 6 m and are spaced 3 m c/c. With 300 mm wall bearing, effective span m. Unit weight of RCC kN/m³ (assumed); no floor finish is given.
- Slab: kN/m², per metre of beam kN/m
- Imposed load: kN/m
Factored load kN/m (plus self-weight).
Moment without self-weight kN·m, so cm³ (self-weight adds a little).
Trial section
Try ISMB 300 (IS 808): mm, mm, mm, mm, mm; cm⁴; cm³; cm³; mass kg/m.
Self-weight kN/m, factored kN/m. Total factored UDL kN/m.
Section classification (Table 2)
. Flange: . Web: (with mm). The section is plastic, so .
Moment capacity (cl. 8.2.1.2)
The compression flange is supported throughout its length by the slab, so lateral buckling is prevented (cl. 8.2.2); this is the check for lateral stability.
The smaller value governs: kN·m.
Shear capacity (cl. 8.4)
kN ; also kN, so the shear is low and the moment capacity is not reduced (cl. 9.2.1). Web shear buckling does not govern since (cl. 8.4.2.1).
Deflection (Table 6)
Deflection under unfactored service (imposed) loads, limit span/300 (floor and roof members, Table 6):
mm mm. OK.
Web buckling and bearing at support (cl. 8.7.3 and 8.7.4)
Stiff bearing length mm. Clear web depth mm; dispersion of load at 45° to mid-depth at an end support mm. Effective length (cl. 8.7.1.5), ; curve c gives N/mm².
Support reaction kN and . No web stiffener is needed.
Final design
Provide ISMB 300 (46.0 kg/m): kN·m kN·m, kN kN, mm mm.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Intermediate beam for 15 m x 6 m hall · Design of Steel and Timber Structure, chapter 7 · asked 2×
- Intermediate beam for 18 m x 6 m office hall · Design of Steel and Timber Structure, chapter 7
- I-section beam for 9 m x 24 m hall slab · Design of Steel and Timber Structure, chapter 7
- Beam supporting RCC slab, DL 25, IL 20 kN/m · Design of Steel and Timber Structure, chapter 7 · asked 2×
- Beam supporting RCC slab, DL 10 kN/m, IL 30 kN · Design of Steel and Timber Structure, chapter 7 · asked 2×
- RCC floor joist design, 15 m x 6 m hall · Design of Steel and Timber Structure, chapter 7
- Beam with slab, 20 kN/m, 350 mm wall · Design of Steel and Timber Structure, chapter 7
- Two-way slab on RCC beams, 4x6 m · Design of RCC Structure, chapter 9 · asked 2×
- Intermediate beam design for BM and deflection · Design of RCC Structure, chapter 4
- Slab continuous over three edges, 5x4 m (225 mm beam) · Design of RCC Structure, chapter 9
- Design T-beam with 150 mm slab · Design of RCC Structure, chapter 4
All Design of Steel and Timber Structure chapter 7 questions →