- 2079 Chaitra · 8 marks
Standard and series realization of a filter
Short answer
Standard: define w(k)=x(k)-0.6w(k-1)-0.7w(k-2)-0.5w(k-3) and y(k)=0.6w(k-1)+0.7w(k-2) using 3 delays. Series: factor as G(z)=0.6 * [1/(1+0.6697z^-1)] * [(z^-1+1.1667z^-2)/(1-0.0697z^-1+0.7467z^-2)], giving two cascaded first- and second-order blocks.
Consider the digital filter defined by G(z)=(6z²+7z)/(10z³+6z²+7z+5). Realize this filter in the standard and series scheme.
Divide by :
(a) Standard programming
Introduce an intermediate variable :
x(k)-->(S)------------o
^ |
| [z^-1]
| | w(k-1)
(S)<[-0.6]-----o--[0.6]------>(S)--> y(k)
^ | ^
| [z^-1] |
| | w(k-2) |
(S)<[-0.7]-----o--[0.7]--------+
^ |
| [z^-1]
| | w(k-3)
+<[-0.5]------o
Only delays are used, the minimum number.
(b) Series programming
Factor the denominator. Its real root, found numerically, is :
The quadratic has complex roots , so it is kept as one second-order block. The numerator is . So
Check: , and . ✔
Difference equations:
- , and
Block (with gain 0.6):
x(k)-->(S)------------o--[1]-------->(S)->[0.6]-> y1(k)
^ |
| [z^-1]
| | w1(k-1)
+<[-0.6697]---o
Block :
y1(k)-->(S)------------o
^ |
| [z^-1]
| | w2(k-1)
(S)<[0.0697]---o--[1]-------->(S)--> y(k)
^ | ^
| [z^-1] |
| | w2(k-2) |
+<[-0.7467]---o--[1.1667]-----+
The series form also uses 3 delays. Each block is first- or second-order, so it is less sensitive to coefficient rounding.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Jury test: 2z⁴+7z³+10z²+4z+1 · Digital Control System, chapter 3 · asked 8×
- Parallel and ladder realization of a filter · Digital Control System, chapter 4 · asked 8×
- Ladder realization of a second-order filter · Digital Control System, chapter 4 · asked 7×
- Parallel realization of a second-order filter · Digital Control System, chapter 4 · asked 2×
- Parallel programming of a digital filter · Digital Control System, chapter 4 · asked 2×
- Why decompose higher-order filters; ladder realization · Digital Control System, chapter 4
- Realization of matched filter · Communication Systems, chapter 9
- Standard rate trickling filter, 1.2 MLD, NRC · Sanitary Engineering, chapter 7 · asked 3×
- Standard rate trickling filter, 3 MLD, 300 mg/l · Sanitary Engineering, chapter 7 · asked 3×
- HR trickling filter, 2.5 MLD; change if standard · Sanitary Engineering, chapter 7