- 2072 Magh · 8 marks
Annual savings of 90% vs 85% efficient motor
Short answer
Annual cost saving ≈ Rs 73,137, found from output 18.65 kW, input powers 21.94 kW (85%) and 20.72 kW (90%), giving 1.219 kW saving and 9752 kWh/year at Rs 7.5/kWh.
Calculate the annual cost savings of a 25 hp motor operating at 90% efficiency compared to 85% efficiency, if the operating hours is 8000 hrs/year and the energy cost is Rs 7.5 per kWh.
Energy saving comes from the lower input power of the more efficient motor for the same shaft output. Assume the motor runs at full rated output (25 hp) for all 8000 h.
Output power:
Po = 25 hp × 0.746 kW/hp = 18.65 kW
Input power at each efficiency (Pin = Po / η):
At 85 %: Pin1 = 18.65 / 0.85 = 21.941 kW
At 90 %: Pin2 = 18.65 / 0.90 = 20.722 kW
Power saved:
ΔP = 21.941 − 20.722 = 1.219 kW
(Formula form: ΔP = hp × 0.746 × (1/η1 − 1/η2).)
Annual energy saved:
ΔE = 1.219 kW × 8000 h = 9751.6 kWh/year
Annual cost saving:
Saving = 9751.6 × 7.5 = Rs 73 137 per year
| Item | 85 % motor | 90 % motor |
|---|---|---|
| Output | 18.65 kW | 18.65 kW |
| Input | 21.94 kW | 20.72 kW |
| Energy/year | 175 529 kWh | 165 778 kWh |
| Cost/year | Rs 1 316 471 | Rs 1 243 333 |
If the high-efficiency motor costs, say, Rs 50 000 more, the simple payback is 50 000 / 73 137 ≈ 0.7 year, which shows why energy-efficient motors are recommended in energy audits.
Answer: Annual saving ≈ 9752 kWh, i.e. about Rs 73 140 per year (at full load).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Energy and cost saving from lighting retrofit · Industrial Power Distribution and Illumination, chapter 10
- Cable types and cable for 15 hp motor · Industrial Power Distribution and Illumination, chapter 5 · asked 2×
- Unarmoured cable for 15 hp motor at 79 m · Industrial Power Distribution and Illumination, chapter 5 · asked 2×
- Electronic ballast replacement savings with ToD tariff · Industrial Power Distribution and Illumination, chapter 10
- Drawing hall 40 × 25 × 6 m, 90 lm/m² LED · Industrial Power Distribution and Illumination, chapter 7 · asked 2×
- Technical aspects of energy efficient motors · Industrial Power Distribution and Illumination, chapter 10 · asked 2×
- Energy saving calculation: lighting and motor · Energy Resources, chapter 9
- Annual charge and pf improvement (Rs 65/kVA tariff) · Utilization of Electrical Energy, chapter 6 · asked 3×
- Current, pf and efficiency of 100 hp motor · Electric Machines II, chapter 2
- Break-even hours for two pumps · Engineering Economics, chapter 1
All Industrial Power Distribution and Illumination chapter 10 questions →