- 2080 Chaitra · 5+3 marks
Septic tank and dispersion trench, 12 persons
Short answer
Sewage flow 0.672 m³/d; septic tank volume 2.20 m³ (settling 0.672 + digestion 0.510 + storage 1.020), size 2.1×0.7×1.5 m. Infiltration area 672/30 = 22.4 m²; trench width 0.6 m, total length 37.3 m, so two 19.0 m long trenches, 0.6 m wide, gravel bed and perforated pipe.
Assuming 80% contribution of water supply for the sewage, design septic tank and dispersion trenches for a house having 12 persons with an average water supply rate of 70 lpcd. The desludging period of septic tank is 3 years. The infiltration capacity of soil is 30 l/m²/d.
Given: 12 persons, water supply 70 L/c/d, sewage = 80% of supply, desludging every 3 years, infiltration 30 L/m²/d.
Septic tank
- Sewage flow:
- Sewage (settling) zone for 24 h detention:
- Sludge digestion zone:
- Digested sludge storage for 3 years:
Adopt liquid depth m and .
Check: (safe).
Septic tank: internal size (including 0.3 m free board), in two chambers: first chamber m long (2/3), second m (1/3), separated by a partition wall with an opening near mid-depth. Inlet and outlet through T-pipes dipping 0.3 m below water level.
Dispersion trenches
- Infiltration area: (trench bottom area)
- Trench width m, so total length m
- The maximum length per trench is about 30 m, so adopt 2 trenches, each 19.0 m long (22.8 m² provided), 0.6 m wide and 0.6-1.0 m deep, laid at a grade of 1 in 200 to 1 in 300, at 2 m centre-to-centre spacing.
Each trench has a 0.3 m deep layer of gravel (20-40 mm) with a 100 mm perforated (or open-jointed) distribution pipe laid in it, covered with 50 mm of coarse sand/gravel, a filter layer such as geotextile or straw, and then soil. Effluent is fed from a distribution box.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Septic tank and dispersion trenches, 20 users · Sanitary Engineering, chapter 9
- Septic tank and drain field, 22 persons · Sanitary Engineering, chapter 9
- Septic tank and soak pits, hotel of 80 · Sanitary Engineering, chapter 9
- Septic tank and soak pit, 8 persons · Sanitary Engineering, chapter 9 · asked 2×
- Septic tank and soak pit, household of 80 · Sanitary Engineering, chapter 9 · asked 2×
- Septic tank and soak pit, 10 users, 85 l/m²/d · Sanitary Engineering, chapter 9 · asked 2×
- Domestic water supply; septic tank and soak pit · Building Technology, chapter 12
- Design pipes AB and BC, 75 lpcd, tank 6 m high · Water Supply Engineering, chapter 7
- Average demand, village survey 2013, design 25 years · Water Supply Engineering, chapter 3 · asked 2×
- Asphalt Institute design: 5.11×10⁴ ESAL/year, 12 years · Transportation Engineering II, chapter 2