- 2080 Chaitra · 8 marks
HR trickling filter, 5 MLD, RR 1.3
Short answer
Single-stage high-rate trickling filter volume 2229 m³, depth 2.0 m, diameter 37.7 m.
Design a single stage high rate trickling filter for the sewage flow of 5 MLD with re-circulation ratio 1.3. The BOD of raw sewage is 250 mg/l. Primary sedimentation tank removes 30% of BOD and desired final BOD of the effluent is 30 mg/l.
Data and approach
High-rate filter design uses the NRC (National Research Council) equation; is in kg/day of BOD applied to the filter, in m³:
Step 1: BOD applied to the filter and required efficiency
Step 2: Recirculation factor
Step 3: Volume
Step 4: Diameter
Adopt depth m (high-rate filters are 1.8-3 m deep).
Step 5: Checks
Answer: single-stage high-rate filter of volume about 2229.1 m³, depth 2.0 m, diameter 37.7 m.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- HR trickling filter, BOD 280 mg/l · Sanitary Engineering, chapter 7
- HR trickling filter, 5 MLD, RR 1.5 · Sanitary Engineering, chapter 7 · asked 2×
- HR trickling filter, 2.5 MLD; change if standard · Sanitary Engineering, chapter 7
- Effluent BOD of two-stage trickling filter · Sanitary Engineering, chapter 7
- Two-stage trickling filter diameters, 4 MLD · Sanitary Engineering, chapter 7 · asked 2×
- Two-stage trickling filter diameters, 5 MLD · Sanitary Engineering, chapter 7 · asked 2×
- Rectangular sedimentation tank for 10 MLD · Water Supply Engineering, chapter 6
- Plain sedimentation tank for 4 MLD · Water Supply Engineering, chapter 6