Static distance relay
Short answer
It measures V/I using electronic comparators. Inputs: V from PT, I·Z_r from transactor; mixing circuit forms signals for mho (S1=I·Z_r−V, S2=V). Phase comparator trips when angle between S1 and S2 within ±90°. Zone timers, then amplifier/thyristor trip. Applications: EHV transmission line main/backup protection, generator loss-of-field.
Describe the working principle of static distance relay with a block diagram and its area of application.
A static distance relay measures the impedance between the relay and the fault using electronic comparators instead of moving discs. It trips when the measured impedance Z = V/I lies inside its set characteristic (impedance, reactance, mho or quadrilateral).
Block diagram
PT ─►[Aux PT]──────► V ─────┐
▼
[Mixing circuit
CT ─►[Transactor]─► I·Zr ─► e.g. mho: S1 = I·Zr − V,
S2 = V ]
│ S1, S2
[Comparator: amplitude
or phase type]
│
[Level detector]
│
[Zone timers T2, T3]
│
[Amplifier]─►[Output]─►Trip
Working principle
- Input stage: the auxiliary PT gives a voltage proportional to the line voltage V. A transactor (air-gap CT) gives a voltage I·Z_r, where Z_r is the replica (set) impedance.
- Mixing circuit forms two signals from V and I·Z_r. Example for a mho relay: S1 = I·Z_r − V and S2 = V.
- Comparator:
- Amplitude comparator (impedance relay): trips when |I·Z_r| > |V|, i.e. Z < Z_r.
- Phase comparator (mho relay): trips when the angle between S1 and S2 is within ±90°, which gives a circle through the origin.
- Level detector checks the comparator output against a threshold and rejects noise.
- Timers: zone 1 is instantaneous; the zone 2 and zone 3 outputs pass through timers (e.g. 0.3 s and 1 s).
- Amplifier and output drive the trip relay/thyristor of the CB.
Characteristics are easy to shape: by changing the mixing networks, the same hardware gives impedance, reactance, mho, offset-mho or quadrilateral characteristics.
Area of application
- Main protection of EHV and HV transmission lines (66–400 kV) with three-zone stepped protection.
- Reactance type for short lines (not affected by arc resistance), mho for long lines (least affected by power swings), and quadrilateral for lines with high fault resistance.
- Carrier-aided schemes (permissive/blocking) for fast clearance over the whole line.
- Back-up for adjacent lines and busbars; loss-of-field protection of generators (offset mho).
- Out-of-step blocking and power-swing detection.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Static differential relay · Switchgear and Protection, chapter 8 · asked 3×
- Impedance type distance relay · Switchgear and Protection, chapter 7
- Static MHO relay · Switchgear and Protection, chapter 8
- Essential components of a static relay · Switchgear and Protection, chapter 8 · asked 5×
- Directional static overcurrent relay · Switchgear and Protection, chapter 8 · asked 2×
- Static differential relay for two-winding transformer · Switchgear and Protection, chapter 8
- CRO block diagram and working · Basic Electronics Engineering, chapter 7
- Working principle of dc generator with diagram · Electrical Machines, chapter 3
- Working principle of a digital telephone exchange · Telecommunications, chapter 4 · asked 4×
- Working principle of FDM · Telecommunications, chapter 3