Static MHO relay

Short answer

A static mho relay uses phase comparison of (I·Zr - V) and V; if coincidence exceeds 5 ms, indicating a fault inside the circle through the origin, it trips. It is inherently directional, preferred for long EHV lines, and least affected by power swings.

Explain the working of static MHO relay with the help of block diagram.

A static mho (admittance) relay is a directional distance relay whose characteristic on the R–X diagram is a circle passing through the origin, with diameter Z_r along the line angle. It is realised with a phase comparator using the inputs S1 = I·Z_r − V and S2 = V.

Principle

 Trip when −90° ≤ angle between (I·Z_r − V) and V ≤ +90°
 i.e. Z = V/I lies inside a circle of diameter Z_r
 through the origin.

        X
        │   .--.
        │  /    \   ← Z_r at line angle θ
        │ |  trip|
        │  \    /
        └──'--'──── R
       origin (directional)

Block diagram

 PT ─►[Aux PT]────────► V ──────────┐
                        │           │
 CT ─►[Transactor]─► I·Z_r          │
                        │           │
                 [Mixer: I·Z_r − V] │
                        │ S1        │ S2 = V
                   [Squarer]    [Squarer]
                        └──►[AND]◄──┘
                              │
                [Integrator: coincidence > 5 ms?]
                              │
                       [Level detector]
                              │
                  [Zone timer (zones 2, 3)]
                              │
                [Amplifier]─►[Output]─► Trip

Working

  1. Aux PT gives V; transactor (air-gap transformer) gives a voltage I·Z_r leading the current by the line angle.
  2. Mixing circuit forms S1 = I·Z_r − V; S2 = V (polarising voltage, sometimes memory-polarised to handle close-in faults).
  3. Squarers convert S1 and S2 to square waves.
  4. Coincidence (AND) circuit: output is high while both are positive. If coincidence lasts more than 5 ms (quarter cycle), the angle between S1 and S2 is within ±90° → fault inside the circle.
  5. Integrator and level detector confirm the coincidence time and reject noise.
  6. Zone 1 trips instantly; zone 2 and zone 3 units have timers.
  7. Amplifier and output relay/thyristor trip the CB.

Features

  • Inherently directional (no separate directional unit).
  • Occupies the smallest area on R–X plane, so it is least affected by power swings – preferred for long EHV lines.
  • Static version is fast, accurate and has low burden.