Directional static overcurrent relay
Short answer
A directional static overcurrent relay trips only when current exceeds the set value and fault power flows in the tripping direction. It combines a static overcurrent unit with a phase comparator that checks the angle between current and polarizing voltage. The block diagram includes CT/PT inputs, phase-shift network, squaring circuits, coincidence-type phase comparator (operate if coincidence >5 ms), overcurrent level detector with timer, AND logic, and output amplifier driving the CB trip coil.
With the help of neat block diagram, explain the function of directional static overcurrent relay.
A directional static overcurrent relay trips only when (a) the current exceeds the set value and (b) the power (fault current) flows in the tripping direction. It combines a static overcurrent unit with a static phase comparator that checks the angle between the current and a reference (polarising) voltage.
Block diagram
CT PT
│ │
[Aux CT] [Aux PT]
│ │
├──────────┐ [Phase shift τ]
│ │ │
[Rectifier] [Squaring] [Squaring]
│ └────┬───────┘
[Level det.] [Phase comparator]
│ (coincidence > 5 ms)
[Timer] │
└──────┬────────┘
[AND]
│
[Amplifier]
│
[Output relay] ──► CB trip coil
Function of the blocks
- Auxiliary CT and PT: reduce current and voltage to electronic levels and isolate the circuit.
- Phase-shift network: shifts the polarising voltage by the relay characteristic angle (e.g. 30° or 45°) so that maximum sensitivity occurs at the typical fault angle.
- Squaring (zero-crossing) circuits: convert current and voltage to square waves.
- Phase comparator (coincidence circuit): an AND gate measures the time for which both square waves are positive. If coincidence > 5 ms (in a 50 Hz system, i.e. angle within ±90°), the fault is in the forward direction and a directional output is given.
- Overcurrent unit: the current is rectified and compared by a level detector with the plug setting; an RC/digital timer gives definite or inverse time delay.
- AND logic: a trip signal is given only when both the directional and the overcurrent conditions are true.
- Amplifier and output: drive the auxiliary relay/thyristor which energises the CB trip coil.
Principle
Forward fault: −90° < (θ − τ) < +90° → operate
Reverse fault: angle outside ±90° → block
Applications
Ring mains, parallel feeders, and lines fed from both ends; generator and transformer reverse-power or back-feed protection; directional earth-fault protection.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Induction type directional overcurrent relay · Switchgear and Protection, chapter 7
- Static MHO relay · Switchgear and Protection, chapter 8
- Essential components of a static relay · Switchgear and Protection, chapter 8 · asked 5×
- Static differential relay · Switchgear and Protection, chapter 8 · asked 3×
- Static distance relay · Switchgear and Protection, chapter 8 · asked 3×
- Voltage-monitored overcurrent relay timing · Switchgear and Protection, chapter 7
- Armature-controlled DC motor transfer function and block diagram · Control Systems, chapter 2
- PID controller block diagram, transfer function, characteristics · Control Systems, chapter 7
- Frequency counter operation with block diagram · Digital Logic, chapter 11 · asked 14×
- Instrumentation system with block diagram · Basic Electronics Engineering, chapter 7 · asked 3×