Short answer

From V_m=√2×7000×0.4712=4665 V, the active recovery voltage is 4.67 kV peak, oscillation frequency is 82.19 kHz, peak restriking voltage occurs at 6.08 μs, and maximum RRRV is 2.41 kV/μs.

A 3 phase 50 Hz alternator with grounded neutral is connected to a bus bar through a circuit breaker. Due to short circuit on the busbar the circuit breaker trips when the current is 7000 A (rms) as shown in figure. Determine (i) Active recovery voltage (ii) Frequency of oscillation (iii) Time to reach the peak restriking voltage (iv) Maximum RRRV. [Figure: Alternator A with grounded neutral, series inductance L = 1.5 mH/phase, shunt capacitance C = 0.0025 μF/phase to ground, then the circuit breaker and a fault on the busbar.]

When the CB interrupts the busbar fault, the voltage across its contacts rises from zero towards the system voltage as an L–C oscillation (the restriking voltage). Its steady value after the transient is the recovery voltage.

  A (alternator)    L=1.5 mH      CB
 (~)---------------^^^^^^----+---o/ o---+ bus
  |                          |          |  fault
 earth                    C=0.0025 μF   X
                             |
                            earth

Method

At fault current zero the system voltage is at its peak V_m (current lags by about 90°). The voltage across the opening contacts then follows the L–C transient (resistance neglected):

v(t) = V_m (1 − cos ω_n t),   ω_n = 1/√(LC)
peak  = 2 V_m      at ω_n t = π     (t = 1/(2 f_n))
dv/dt = V_m ω_n sin ω_n t
max   = V_m ω_n    at ω_n t = π/2   (t = 1/(4 f_n))

The source voltage is not given, so it is obtained from the fault current limited by the generator reactance: V_m = √2 × I × ωL (phase peak).

Data

L = 1.5 mH/phase, C = 0.0025 μF/phase, I = 7000 A rms, f = 50 Hz.

(i) Active recovery voltage

X_L = 2π × 50 × 1.5×10⁻³ = 0.4712 Ω
V_m = √2 × 7000 × 0.4712
    = 4665 V ≈ 4.67 kV (peak, per phase)

(ii) Frequency of oscillation

√(LC) = √(1.5×10⁻³ × 0.0025×10⁻⁶) = 1.9365×10⁻⁶ s
f_n   = 1 / (2π × 1.9365×10⁻⁶)
      = 82 187 Hz ≈ 82.19 kHz
ω_n   = 5.164 × 10⁵ rad/s

(iii) Time to reach peak restriking voltage

t = 1 / (2 f_n) = 1 / (2 × 82 187)
  = 6.084 × 10⁻⁶ s = 6.08 μs
Peak restriking voltage = 2 V_m = 9.33 kV

(iv) Maximum RRRV

RRRV_max = V_m ω_n
         = 4665 × 5.164×10⁵
         = 2.409 × 10⁹ V/s ≈ 2.41 kV/μs
(occurs at t = 1/(4 f_n) = 3.04 μs)

Answer: (i) active recovery voltage = 4.67 kV (peak); (ii) f_n = 82.19 kHz; (iii) t = 6.08 μs; (iv) maximum RRRV = 2.41 kV/μs.