- 2074 Bhadra · 8 marks
TRV numerical: 1.7 mH, 0.0025 μF, 7500 A
Short answer
Using V_m=√2×7500×0.5341=5665 V and the LC transient v=V_m(1−cosωt), the natural frequency is 77.2 kHz, peak TRV is 11.33 kV at 6.48 μs, and maximum RRRV is 2.75 kV/μs at 3.24 μs.
A 50 Hz, three-phase synchronous generator has an inductance per phase of 1.7 mH and its neutral is grounded. It feeds a line through a circuit breaker. The total stray capacitance to ground of the generator and circuit breaker is 0.0025 μF. A fault occurs just beyond the circuit breaker, which opens when the symmetrical short circuit current is 7500 A (rms). Ignoring the first pole to clear factor, determine the following: (i) Natural frequency of oscillations (ii) Peak value of TRV (iii) Time at which peak value of TRV occurs (iv) Maximum rate of rise of TRV (v) Time at which the maximum in part (iv) occurs.
The transient recovery voltage (TRV) is the oscillatory voltage that appears across the CB contacts just after the arc is extinguished at current zero.
Method
At fault current zero the system voltage is at its peak V_m (current lags by about 90°). The voltage across the opening contacts then follows the L–C transient (resistance neglected):
v(t) = V_m (1 − cos ω_n t), ω_n = 1/√(LC)
peak = 2 V_m at ω_n t = π (t = 1/(2 f_n))
dv/dt = V_m ω_n sin ω_n t
max = V_m ω_n at ω_n t = π/2 (t = 1/(4 f_n))
The source voltage is not given, so it is obtained from the fault current limited by the generator reactance: V_m = √2 × I × ωL (phase peak).
Data
L = 1.7 mH, C = 0.0025 μF, I = 7500 A rms, f = 50 Hz, neutral grounded (first-pole-to-clear factor ignored).
X_L = 2π × 50 × 1.7×10⁻³ = 0.5341 Ω
V_m = √2 × 7500 × 0.5341 = 5665 V (peak)
√(LC) = √(1.7×10⁻³ × 0.0025×10⁻⁶) = 2.0616×10⁻⁶ s
(i) Natural frequency
f_n = 1 / (2π × 2.0616×10⁻⁶)
= 77 201 Hz ≈ 77.2 kHz
ω_n = 4.8507 × 10⁵ rad/s
(ii) Peak value of TRV
V_peak = 2 V_m = 2 × 5665 = 11 329 V ≈ 11.33 kV
(iii) Time of peak TRV
t = π / ω_n = 1 / (2 f_n)
= 1 / (2 × 77 201) = 6.477 × 10⁻⁶ s = 6.48 μs
(iv) Maximum rate of rise of TRV
RRRV_max = V_m ω_n
= 5665 × 4.8507×10⁵
= 2.748 × 10⁹ V/s ≈ 2.75 kV/μs
(v) Time of maximum RRRV
t = π / (2 ω_n) = 1 / (4 f_n)
= 3.238 × 10⁻⁶ s = 3.24 μs
Answer: (i) 77.2 kHz; (ii) 11.33 kV; (iii) 6.48 μs; (iv) 2.75 kV/μs; (v) 3.24 μs.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- TRV numerical: 1.5 mH, 0.0025 μF, 7000 A · Switchgear and Protection, chapter 6
- TRV numerical: 1.6 mH, 0.0032 μF, 8000 A · Switchgear and Protection, chapter 6 · asked 2×
- Restriking voltage numerical (6.6 kV, 8 mH) · Switchgear and Protection, chapter 6 · asked 2×
- Restriking voltage numerical (11 kV, 10 mH) · Switchgear and Protection, chapter 6 · asked 2×
- Inductance and capacitance of 4-conductor bundle line · Power System Analysis I, chapter 4
- Per unit circuit of three-generator system, 30 MVA base · Power System Analysis I, chapter 3
- Line currents with isolated and grounded neutral · Power System Analysis II, chapter 4
- Capacitance of double circuit line, 6 mm radius · Power System Analysis I, chapter 4