- Asked 2/16
- 2071 Bhadra · 8 marks
- 2076 Bhadra · 6 marks
TRV numerical: 1.6 mH, 0.0032 μF, 8000 A
Short answer
Compute X_L = 2πfL = 0.5027 Ω, then V_m = √2 × I × X_L = 5.69 kV peak. Oscillation frequency f_n = 1/(2π√(LC)) = 70.34 kHz. Time to max RRRV = 1/(4f_n) = 3.55 μs. Max RRRV = V_m × 2πf_n = 2.51 kV/μs.
A 50 Hz 3-phase alternator with grounded neutral has an inductance of 1.6 mH per phase and is connected to the bus-bars through a circuit breaker. The capacitance to earth of the circuit between the alternator and the circuit breaker is 0.0032 μF per phase. Due to a short on the bus-bars the breaker opens when the rms value of the current is 8000 A. Determine the following (i) frequency of oscillation (ii) Active recovery voltage (iii) time for maximum RRRV and (iv) maximum RRRV.
When the breaker interrupts a bus fault fed by an alternator, the voltage across its contacts rises as a transient oscillation of the system L and C. The fault current lags the voltage by nearly 90°, so at current zero the system voltage is at its peak V_m (the active recovery voltage). The restriking voltage is v = V_m(1 − cos ωₙt), which peaks at 2V_m.
The system voltage is not given, so it is found from the fault current. With only the alternator reactance limiting the current:
V_ph(rms) = I × X_L, V_m = √2 × I × X_L
Data
L = 1.6 mH, C = 0.0032 μF, I = 8000 A rms, f = 50 Hz.
(i) Frequency of oscillation
√(LC) = √(1.6×10⁻³ × 0.0032×10⁻⁶)
= 2.2627 × 10⁻⁶ s
f_n = 1 / (2π √(LC))
= 1 / (2π × 2.2627×10⁻⁶)
= 70 337 Hz ≈ 70.34 kHz
ω_n = 2π f_n = 4.4194 × 10⁵ rad/s
(ii) Active recovery voltage
X_L = 2π × 50 × 1.6×10⁻³ = 0.5027 Ω
V_m = √2 × 8000 × 0.5027
= 5687 V ≈ 5.69 kV (peak, phase value)
(The maximum restriking voltage would be 2V_m = 11.37 kV.)
(iii) Time for maximum RRRV
v = V_m (1 − cos ω_n t)
dv/dt = V_m ω_n sin ω_n t
Maximum when ω_n t = π/2:
t = π / (2 ω_n) = 1 / (4 f_n)
= 1 / (4 × 70 337)
= 3.554 × 10⁻⁶ s = 3.55 μs
(iv) Maximum RRRV
RRRV_max = V_m ω_n
= 5687 × 4.4194×10⁵
= 2.513 × 10⁹ V/s
= 2513 V/μs ≈ 2.51 kV/μs
Answer: (i) f_n = 70.34 kHz; (ii) active recovery voltage = 5.69 kV (peak); (iii) t = 3.55 μs; (iv) maximum RRRV = 2.51 kV/μs.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- TRV numerical: 1.7 mH, 0.0025 μF, 7500 A · Switchgear and Protection, chapter 6
- TRV numerical: 1.5 mH, 0.0025 μF, 7000 A · Switchgear and Protection, chapter 6
- Restriking voltage numerical (6.6 kV, 8 mH) · Switchgear and Protection, chapter 6 · asked 2×
- Restriking voltage numerical (11 kV, 10 mH) · Switchgear and Protection, chapter 6 · asked 2×
- Earth fault protection: 20 MVA alternator · Switchgear and Protection, chapter 7
- Why and how the neutral is grounded · Switchgear and Protection, chapter 5 · asked 4×
- Alternator open-circuit emf at 40 Hz · Electrical Machine, chapter 6
- Inductance and capacitance of 4-conductor bundle line · Power System Analysis I, chapter 4
- Delta capacitor per phase for 50 kW motor · Basic Electrical Engineering, chapter 8
- Line currents with isolated and grounded neutral · Power System Analysis II, chapter 4