- 2075 Asoj · 15 marks
Biaxial column 500x600, 1300 kN
Short answer
Short column; no slenderness effect. Use 12-16 mm bars (p=0.80%) and 8 mm ties @250 mm c/c; biaxial interaction ratio is 0.796, so safe.
Determine the longitudinal and transverse reinforcement in bi-axially loaded column having the following parameters: Unsupported length of column = 3.10 m; Size of column = 500 mm x 600 mm; Factored moment, = 125 kN.m; Factored load, = 1300 kN; Factored moment, = 200 kN.m. Use M25 concrete and Fe 500 steel. Take reinforcement in four side. Sketch the details.
Data and assumptions
- Column 500 mm (width ) × 600 mm (depth ); kN; MPa, MPa. Clear cover 40 mm (IS 456 cl. 26.4.2.1), 8 mm ties.
- Moments: about major axis (x-x) = 125 kN·m; about minor axis (y-y) = 200 kN·m.
- Sizes are given as with ; moments act about the major axis (depth ) and about the minor axis (depth ).
Slenderness
| Axis | (mm) | Dimension (mm) | dim | Type |
|---|---|---|---|---|
| x-x (about major) | 3100 | 600 | 5.17 | short |
| y-y (about minor) | 3100 | 500 | 6.20 | short |
Both ratios are below 12, so the column is short; no additional moment is required.
Minimum eccentricity (cl. 25.4)
- About x-x: mm (min. 20 mm); adopt 26.2 mm; kN·m
- About y-y: mm (min. 20 mm); adopt 22.9 mm; kN·m
Design moments
- Design moments: kN·m, kN·m (not less than the minimum-eccentricity values).
Longitudinal reinforcement
Bars are chosen so that lies between 0.8% (minimum) and 4% (practical maximum; IS 456 cl. 26.5.3.1 allows 6%). The uniaxial capacities , at are read from the SP-16 interaction charts for rectangular sections; here they are computed by strain compatibility with the IS 456 stress block and the design stress-strain curve of steel (same basis as the charts), with effective cover .
| Trial | (%) | ||||||
|---|---|---|---|---|---|---|---|
| 12-16 φ | 0.80 | 0.093 | 409.9 | 333.0 | 0.306 | 1.18 | 0.796 ✓ |
Check
kN , so (IS 456 cl. 39.6; linear between 1.0 at 0.2 and 2.0 at 0.8).
The interaction condition is satisfied; the section is safe.
Provide 12-16 mm bars ( mm², ), within 0.8% to 4%.
Lateral ties
- Diameter mm → provide 8 mm.
- Pitch (least lateral dimension, , 300 mm) mm → provide 8 mm ties @ 250 mm c/c.
Detailing
CROSS-SECTION 500 x 600
+-------------------------+
| o o o o |
| |
| |
| o o |
| |
| |
| |
| o o |
| |
| |
| o o o o |
+-------------------------+
o = 16 mm bars, ties 8 mm @ 250 c/c
Answer: 500 × 600 mm column with 12-16 mm longitudinal bars () and 8 mm ties @ 250 mm c/c.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Biaxial column 400x600, Fe500 · Design of RCC Structure, chapter 10
- Biaxial column 400x600, 1500 kN · Design of RCC Structure, chapter 10
- Biaxial short square column, 800 kN · Design of RCC Structure, chapter 10
- Footing 300x400 column, factored moment 120 kNm · Design of RCC Structure, chapter 11
- Biaxial column 400x500, equal steel all sides · Design of RCC Structure, chapter 10
- Column 350x350, 1440 kN, ductile detailing · Design of RCC Structure, chapter 10 · asked 2×
- Design steps of axially loaded brick column · Concrete Technology and Masonry Structure, chapter 8
- Built-up column, battens, 6 m unsupported, 1200 kN · Design of Steel and Timber Structure, chapter 6
- Solid Sal column, 500 kN + 50 kNm, 2 m · Design of Steel and Timber Structure, chapter 11
- Corner stresses of 500 x 900 column (300 kN) · Concrete Technology and Masonry Structure, chapter 8 · asked 7×