Footing 300x400 column, factored moment 120 kNm
Short answer
Provide a 3.1 m × 1.7 m footing, 700 mm deep. Longitudinal steel 16 mm @ 185 mm c/c; transverse steel central band 12 mm @ 100 mm c/c, outer strips 12 mm @ 115 mm c/c. Bearing stress and development length are satisfactory.
Design an isolated rectangular footing for a column of size 300 mm x 400 mm. The column is carrying 8-20 mm dia bars with M25 concrete. The column is carrying a factored axial load of 1200 kN and the factored moment of 120 kN-m. Sketch the details of designed reinforcements in plan and sections. Also check the bearing stress and development length required. Adopt M20 grade concrete for footing. Grade of steel used is Fe415 [text partly cut off in scan]. Assume bearing capacity of soil = 200 kN/m at 1.25 m below GL.
Data and assumptions
- Column 400 mm × 300 mm (long side mm along the footing length); footing concrete M20, steel Fe415; column concrete M25; column bars 8-20 mm.
- Given loads are factored: kN, kN·m. Service loads = factored / 1.5: kN, kN·m.
- Allowable (safe) bearing capacity of soil = 200 kN/m² at 1.25 m depth.
- Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth mm (cover + half bar). Load factor 1.5.
Size of footing
Weight of footing and backfill is taken as 10% of the column load.
Eccentricity m, which is less than , so there is no tension under the base. The size is chosen so that
Try m ( m²): kN/m² and kN/m² . Safe.
Factored soil pressure
kN, kN·m. : kN/m², kN/m² (average 227.7 kN/m²). Self-weight does not cause bending in the footing, so it is excluded.
Bending moments and reinforcement
Cantilever projections from the column face: along : mm; along : mm. Along (critical section at the column face on the side of maximum pressure, linear pressure): , with kN/m² at the face and m: kN·m. Along (average pressure): kN·m. Required depth for flexure: is far larger than the moment for mm, so the depth is governed by shear (one-way or punching). Trial mm, mm, found by the shear checks below.
; minimum steel = 0.12% of .
| Direction | (kN·m) | req (mm²) | Provide | prov (mm²) |
|---|---|---|---|---|
| Along (width ) | 401.2 | 1799 | 16 mm @ 185 c/c | 1848 |
| Along (width ) | 172.9 | 2604 | 12 mm @ 130 c/c | 2697 |
For the rectangular footing, the short-direction steel is placed in a central band of width mm in the proportion (IS 456 cl. 34.3.1), where .
- Central band: mm² → 12 mm @ 100 mm c/c (17 bars).
- Each outer strip (700 mm wide): remaining steel 380 mm² or minimum 0.12% = 588 mm², whichever is more → 12 mm @ 115 mm c/c (6 bars).
Check for one-way shear (at distance from the column face)
- Along side: kN, MPa; , MPa (IS 456 Table 19, SP 16 formula). , safe.
- Along side: kN, MPa; , MPa. Safe.
Check for two-way (punching) shear (at from the column face)
- Perimeter mm
- kN (average pressure; the effect of moment transfer is neglected).
- MPa; , MPa. , safe.
Development length
, MPa (M20, deformed bars): 16 mm bars → mm; 12 mm bars → mm. Available length from column face (less 50 mm end cover): 1300 mm along , 650 mm along . Satisfied in both directions.
Bearing stress and transfer of load from column
Column area m². Bearing stress MPa. Permissible bearing stress: column concrete MPa; footing concrete with gives up to 18.00 MPa. The lesser, 11.25 MPa, governs. Capacity of bearing = 1350 kN kN, so the whole load can be transferred by bearing. Provide minimum dowels of 0.5% of column area = 600 mm²: use 8 bars of 20 mm (2513 mm²) as dowels, same as column bars. Dowel length in compression mm (and the same lap with the column bars). Available depth in footing = 700 - 50 - 28 = 622 mm ; dowels are bent at the bottom with 90° bends.
Detailing
PLAN ELEVATION
+------------------+ col
| # # # # # # | | |
| # +------+ # # | _|_|__
| # | col | # # | |_____| <- D = 700 mm
| # +------+ # # | bars both ways
| # # # # # # |
+------------------+
L = 3.1 m, B = 1.7 m
- Bottom mesh: 16 mm @ 185 c/c along (lower layer); along (upper layer), 12 mm @ 100 c/c in the central 1.7 m band and 12 mm @ 115 c/c in each outer strip, 50 mm clear cover; dowels 8-20 mm.
Answer: Footing 3.1 m × 1.7 m × 700 mm thick; 16 mm @ 185 c/c along the length; along the width, 12 mm @ 100 c/c in the central 1.7 m band and 12 mm @ 115 c/c in the outer strips.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Isolated footing 400x400, service moment 120 kNm · Design of RCC Structure, chapter 11 · asked 2×
- Isolated footing 450x450, service moment 110 kNm · Design of RCC Structure, chapter 11 · asked 2×
- Footing for 30x35 cm column, M25 · Design of RCC Structure, chapter 11
- Footing, 450x500 column, 6#20, uniaxial moment · Design of RCC Structure, chapter 11
- Footing 350x350, 8-16 mm bars, reversible moment · Design of RCC Structure, chapter 11
- Rectangular footing, 450x450, uniaxial moment 240 kNm · Design of RCC Structure, chapter 11
- Brick column design for 80 kN axial load · Concrete Technology and Masonry Structure, chapter 8
- Rectangular Sal column, 150 kN + 15 kNm · Design of Steel and Timber Structure, chapter 11
- Rectangular footing size, 6000 kN · Foundation Engineering, chapter 6
- Solid Sal column, 75 kN + 12 kNm, 2 m · Design of Steel and Timber Structure, chapter 11