Chapter 11 · 6 hours
Design of Footings
IOE past exam questions
Past questions and answers
24 questions set from this chapter, 1 of them more than once; 1 is most repeated (set, or a close variant set, in 3 or more exams). Most repeated first.
- Most repeated · 3 of 25 exams
- Asked 3 times
- 2081 Bhadra · 4 marks
- 2075 Asoj · 5 marks
- 2069 Chaitra · 6 marks
Describe/explain in details all the design steps of R.C.C mat foundation design.
Answer
A mat (raft) foundation is a large, continuous slab that supports the whole building (or several columns) and spreads the load over the full plan area. It is used when soil is weak, when isolated footings would cover more than about half the plan area, or to reduce differential settlement.
Design steps
- Collect the data: column loads and positions (dead + live, and moments), safe bearing capacity of the soil, grades of concrete and steel, depth of foundation.
- Find the resultant of all column loads, , and its position . Choose the plan size of the mat (with edge projections) so that its centroid coincides, or nearly coincides, with the resultant. Eccentricity resultant - centroid should be small.
- Area: (10% allowance for self-weight), and check that net upward pressure
- Choose the method of analysis:
- Rigid (conventional) method: if the column spacing is less than (where ), the mat is taken as rigid. Contact pressure is linear. The mat is divided into strips between the column lines, each strip is analysed as a continuous beam under the pressure and the column loads, and the shear and bending moment diagrams are drawn.
- Flexible method (beam on elastic foundation, or finite element/ plate on springs), when the mat is not rigid.
- Thickness: determine the depth from punching shear around the heaviest columns (at ) and one-way shear at from the face of the column or wall (shear reinforcement is avoided when possible). Check also the bending requirement.
- Bending moments and reinforcement: calculate positive and negative moments in each strip in both directions; design steel at top and bottom in each direction (top steel at the supports (columns), bottom steel at mid-span). Provide minimum steel of 0.12% each way.
- Check the development length, the bearing at the column base and the settlement.
- Detailing: top and bottom mesh in both directions, extra bars at columns, cover 50 mm (75 mm if cast against the soil without blinding), dowels for the column bars, construction joints and waterproofing if below ground water.
A mat can be a plain slab, a slab with beams (ribbed), or a cellular/ box type.
- 2082 Baisakh · 12 marks
Design an isolated footing for a column of size 450 mm x 450 mm with 8-20 mm diameter bars as longitudinal reinforcement in order to carry a service axial load of 1000 kN and service moment of 110 kNm. Take the safe bearing capacity of soil as 140 kN/m. Use M20 concrete and Fe 415 steel.
Similar questions: Isolated footing 400x400, service moment 120 kNm (2081 Bhadra)
Answer
Data and assumptions
- Column 450 mm × 450 mm (long side mm along the footing length); footing concrete M20, steel Fe415; column concrete M20; column bars 8-20 mm.
- Service load kN, service moment kN·m.
- Allowable (safe) bearing capacity of soil = 140 kN/m².
- The service moment acts about one axis.
- Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth mm (cover + half bar). Load factor 1.5.
Size of footing
Weight of footing and backfill is taken as 10% of the column load.
Eccentricity m, which is less than , so there is no tension under the base. The size is chosen so that
Try m ( m²): kN/m² and kN/m² . Safe.
Factored soil pressure
kN, kN·m. : kN/m², kN/m² (average 163.0 kN/m²). Self-weight does not cause bending in the footing, so it is excluded.
Bending moments and reinforcement
Cantilever projections from the column face: along : mm; along : mm. Along (critical section at the column face on the side of maximum pressure, linear pressure): kN·m. Along (average pressure): kN·m. Required depth for flexure: is far larger than the moment for mm, so the depth is governed by shear (one-way or punching). Trial mm, mm, found by the shear checks below.
; minimum steel = 0.12% of .
| Direction | (kN·m) | req (mm²) | Provide | prov (mm²) |
|---|---|---|---|---|
| Along (width ) | 630.5 | 2844 | 16 mm @ 160 c/c | 2890 |
| Along (width ) | 279.0 | 3360 | 12 mm @ 130 c/c | 3480 |
For the rectangular footing, the short-direction steel is placed in a central band of width mm in the proportion (IS 456 cl. 34.3.1), where .
- Central band: mm² → 12 mm @ 100 mm c/c (22 bars).
- Each outer strip (850 mm wide): remaining steel 453 mm² or minimum 0.12% = 714 mm², whichever is more → 12 mm @ 120 mm c/c (7 bars).
Check for one-way shear (at distance from the column face)
- Along side: kN, MPa; , MPa (Table 19). , safe.
- Along side: kN, MPa; , MPa. Safe.
Check for two-way (punching) shear (at from the column face)
- Perimeter mm
- kN (average pressure; the effect of moment transfer is neglected).
- MPa; , MPa. , safe.
Development length
, MPa (M20, deformed bars): 16 mm bars → mm; 12 mm bars → mm. Available length from column face (less 50 mm end cover): 1725 mm along , 875 mm along . Satisfied in both directions.
Bearing stress and transfer of load from column
Column area m². Bearing stress MPa. Permissible bearing stress: column concrete MPa; footing concrete with gives up to 18.00 MPa. The lesser, 9.00 MPa, governs. Capacity of bearing = 1822 kN kN, so the whole load can be transferred by bearing. Provide minimum dowels of 0.5% of column area = 1012 mm²: use 8 bars of 20 mm (2513 mm²) as dowels, same as column bars. Dowel length in compression mm (and the same lap with the column bars). Available depth in footing = 700 - 50 - 28 = 622 mm ; dowels are bent at the bottom with 90° bends.
Detailing
PLAN ELEVATION
+------------------+ col
| # # # # # # | | |
| # +------+ # # | _|_|__
| # | col | # # | |_____| <- D = 700 mm
| # +------+ # # | bars both ways
| # # # # # # |
+------------------+
L = 4.0 m, B = 2.3 m
- Bottom mesh: 16 mm @ 160 c/c along (lower layer), 12 mm @ 130 c/c along (upper layer), 50 mm clear cover; dowels 8-20 mm.
Answer: Footing 4.0 m × 2.3 m × 700 mm thick; 16 mm @ 160 c/c along the length and 12 mm @ 130 c/c along the width.
- 2081 Bhadra · 12 marks
Design an isolated footing for a column of size 400 mm x 400 mm with 8-25 mm diameter bars as longitudinal reinforcement in order to carry a service axial load of 1200 kN and service moment of 120 kNm. Take the safe bearing capacity of soil as 150 kN/m. Use M20 concrete and Fe 415 steel.
Similar questions: Isolated footing 450x450, service moment 110 kNm (2082 Baisakh)
Answer
Data and assumptions
- Column 400 mm × 400 mm (long side mm along the footing length); footing concrete M20, steel Fe415; column concrete M20; column bars 8-25 mm.
- Service load kN, service moment kN·m.
- Allowable (safe) bearing capacity of soil = 150 kN/m².
- Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth mm (cover + half bar). Load factor 1.5.
Size of footing
Weight of footing and backfill is taken as 10% of the column load.
Eccentricity m, which is less than , so there is no tension under the base. The size is chosen so that
Try m ( m²): kN/m² and kN/m² . Safe.
Factored soil pressure
kN, kN·m. : kN/m², kN/m² (average 178.6 kN/m²). Self-weight does not cause bending in the footing, so it is excluded.
Bending moments and reinforcement
Cantilever projections from the column face: along : mm; along : mm. Along (critical section at the column face on the side of maximum pressure, linear pressure): kN·m. Along (average pressure): kN·m. Required depth for flexure: is far larger than the moment for mm, so the depth is governed by shear (one-way or punching). Trial mm, mm, found by the shear checks below.
; minimum steel = 0.12% of .
| Direction | (kN·m) | req (mm²) | Provide | prov (mm²) |
|---|---|---|---|---|
| Along (width ) | 817.4 | 3179 | 16 mm @ 150 c/c | 3217 |
| Along (width ) | 375.0 | 4032 | 16 mm @ 205 c/c | 4119 |
For the rectangular footing, the short-direction steel is placed in a central band of width mm in the proportion (IS 456 cl. 34.3.1), where .
- Central band: mm² → 16 mm @ 160 mm c/c (15 bars).
- Each outer strip (900 mm wide): remaining steel 550 mm² or minimum 0.12% = 864 mm², whichever is more → 16 mm @ 180 mm c/c (5 bars).
Check for one-way shear (at distance from the column face)
- Along side: kN, MPa; , MPa (Table 19). , safe.
- Along side: kN, MPa; , MPa. Safe.
Check for two-way (punching) shear (at from the column face)
- Perimeter mm
- kN (average pressure; the effect of moment transfer is neglected).
- MPa; , MPa. , safe.
Development length
, MPa (M20, deformed bars): 16 mm bars → mm; 16 mm bars → mm. Available length from column face (less 50 mm end cover): 1850 mm along , 950 mm along . Satisfied in both directions.
Bearing stress and transfer of load from column
Column area m². Bearing stress MPa. Permissible bearing stress: column concrete MPa; footing concrete with gives up to 18.00 MPa. The lesser, 9.00 MPa, governs. Capacity of bearing = 1440 kN kN, so the excess 360 kN must be carried by dowels: mm²; the column bars (8-25 mm, 3927 mm²) are continued into the footing as dowels - adequate. Dowel length in compression mm (and the same lap with the column bars). Available depth in footing = 800 - 50 - 32 = 718 mm ; dowels are bent at the bottom with 90° bends.
Detailing
PLAN ELEVATION
+------------------+ col
| # # # # # # | | |
| # +------+ # # | _|_|__
| # | col | # # | |_____| <- D = 800 mm
| # +------+ # # | bars both ways
| # # # # # # |
+------------------+
L = 4.2 m, B = 2.4 m
- Bottom mesh: 16 mm @ 150 c/c along (lower layer), 16 mm @ 205 c/c along (upper layer), 50 mm clear cover; dowels 8-25 mm.
Answer: Footing 4.2 m × 2.4 m × 800 mm thick; 16 mm @ 150 c/c along the length and 16 mm @ 205 c/c along the width.
- 2078 Bhadra · 12 marks
Design an isolated square footing foundation of uniform thickness for a 400 mm x 400 mm column subjected to an axial load of 650 kN at service state. Consider safe bearing capacity of soil as 170 kN/m and concrete of M20 and steel grade of Fe500. Show the reinforcements in plan and in section of footing.
Similar questions: Isolated square footing, 600 kN and 50 kNm (2067 Asar (old course))
Answer
Data and assumptions
- Column 400 mm × 400 mm (long side mm along the footing length); footing concrete M20, steel Fe500; column concrete M20; column bars 8-16 mm.
- Service load kN.
- Allowable (safe) bearing capacity of soil = 170 kN/m².
- Column bars assumed 8-16 mm.
- Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth mm (cover + half bar). Load factor 1.5.
Size of footing
Weight of footing and backfill is taken as 10% of the column load.
Provide a square footing m, area = 4.41 m² 4.21 m².
Factored soil pressure
kN. kN/m².
Bending moments and reinforcement
Cantilever projections from the column face: along : mm; along : mm. : kN·m, kN·m. Required depth for flexure: is far larger than the moment for mm, so the depth is governed by shear (one-way or punching). Trial mm, mm, found by the shear checks below.
; minimum steel = 0.12% of .
| Direction | (kN·m) | req (mm²) | Provide | prov (mm²) |
|---|---|---|---|---|
| Along (width ) | 167.7 | 1134 | 12 mm @ 205 c/c | 1159 |
| Along (width ) | 167.7 | 1134 | 12 mm @ 205 c/c | 1159 |
Check for one-way shear (at distance from the column face)
- Along side: kN, MPa; , MPa (Table 19). , safe.
- Along side: kN, MPa; , MPa. Safe.
Check for two-way (punching) shear (at from the column face)
- Perimeter mm
- kN (average pressure; the effect of moment transfer is neglected).
- MPa; , MPa. , safe.
Development length
, MPa (M20, deformed bars): 12 mm bars → mm; 12 mm bars → mm. Available length from column face (less 50 mm end cover): 800 mm along , 800 mm along . Satisfied in both directions.
Bearing stress and transfer of load from column
Column area m². Bearing stress MPa. Permissible bearing stress: column concrete MPa; footing concrete with gives up to 18.00 MPa. The lesser, 9.00 MPa, governs. Capacity of bearing = 1440 kN kN, so the whole load can be transferred by bearing. Provide minimum dowels of 0.5% of column area = 800 mm²: use 8 bars of 16 mm (1608 mm²) as dowels, same as column bars. Dowel length in compression mm (and the same lap with the column bars). Available depth in footing = 450 - 50 - 24 = 376 mm ; dowels are bent at the bottom with 90° bends.
Detailing
PLAN ELEVATION
+------------------+ col
| # # # # # # | | |
| # +------+ # # | _|_|__
| # | col | # # | |_____| <- D = 450 mm
| # +------+ # # | bars both ways
| # # # # # # |
+------------------+
L = 2.1 m, B = 2.1 m
- Bottom mesh: 12 mm @ 205 c/c along (lower layer), 12 mm @ 205 c/c along (upper layer), 50 mm clear cover; dowels 8-16 mm.
Answer: Footing 2.1 m × 2.1 m × 450 mm thick; 12 mm @ 205 c/c along the length and 12 mm @ 205 c/c along the width.
- 2067 Asar (old course) · 10 marks
Design an isolated square footing foundation of uniform thickness for a 400 mm x 400 mm column subjected to an axial load of 600 kN and a moment of 50 kNm at service state. Consider bearing capacity of soil as 150 kN/m and concrete grade M20 and steel grade Fe415.
Similar questions: Isolated square footing, 650 kN service (2078 Bhadra)
Answer
Data and assumptions
- Column 400 mm × 400 mm (long side mm along the footing length); footing concrete M20, steel Fe415; column concrete M20; column bars 8-16 mm.
- Service load kN, service moment kN·m.
- Allowable (safe) bearing capacity of soil = 150 kN/m².
- Square footing as required by the question; column bars assumed 8-16 mm.
- Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth mm (cover + half bar). Load factor 1.5.
Size of footing
Weight of footing and backfill is taken as 10% of the column load.
Eccentricity m, which is less than , so there is no tension under the base. The size is chosen so that
Try m ( m²): kN/m² and kN/m² . Safe.
Factored soil pressure
kN, kN·m. : kN/m², kN/m² (average 156.2 kN/m²). Self-weight does not cause bending in the footing, so it is excluded.
Bending moments and reinforcement
Cantilever projections from the column face: along : mm; along : mm. Along (critical section at the column face on the side of maximum pressure, linear pressure): kN·m. Along (average pressure): kN·m. Required depth for flexure: is far larger than the moment for mm, so the depth is governed by shear (one-way or punching). Trial mm, mm, found by the shear checks below.
; minimum steel = 0.12% of .
| Direction | (kN·m) | req (mm²) | Provide | prov (mm²) |
|---|---|---|---|---|
| Along (width ) | 204.9 | 1506 | 12 mm @ 180 c/c | 1508 |
| Along (width ) | 187.5 | 1374 | 12 mm @ 195 c/c | 1392 |
Check for one-way shear (at distance from the column face)
- Along side: kN, MPa; , MPa (Table 19). , safe.
- Along side: kN, MPa; , MPa. Safe.
Check for two-way (punching) shear (at from the column face)
- Perimeter mm
- kN (average pressure; the effect of moment transfer is neglected).
- MPa; , MPa. , safe.
Development length
, MPa (M20, deformed bars): 12 mm bars → mm; 12 mm bars → mm. Available length from column face (less 50 mm end cover): 950 mm along , 950 mm along . Satisfied in both directions.
Bearing stress and transfer of load from column
Column area m². Bearing stress MPa. Permissible bearing stress: column concrete MPa; footing concrete with gives up to 18.00 MPa. The lesser, 9.00 MPa, governs. Capacity of bearing = 1440 kN kN, so the whole load can be transferred by bearing. Provide minimum dowels of 0.5% of column area = 800 mm²: use 8 bars of 16 mm (1608 mm²) as dowels, same as column bars. Dowel length in compression mm (and the same lap with the column bars). Available depth in footing = 450 - 50 - 24 = 376 mm ; dowels are bent at the bottom with 90° bends.
Detailing
PLAN ELEVATION
+------------------+ col
| # # # # # # | | |
| # +------+ # # | _|_|__
| # | col | # # | |_____| <- D = 450 mm
| # +------+ # # | bars both ways
| # # # # # # |
+------------------+
L = 2.4 m, B = 2.4 m
- Bottom mesh: 12 mm @ 180 c/c along (lower layer), 12 mm @ 195 c/c along (upper layer), 50 mm clear cover; dowels 8-16 mm.
Answer: Footing 2.4 m × 2.4 m × 450 mm thick; 12 mm @ 180 c/c along the length and 12 mm @ 195 c/c along the width.
- 2065 Shrawan (old course) · 7 marks
Describe the steps for design of a rectangular RC footing. Why is shear reinforcement not provided in footing?
Answer
Steps for design of a rectangular RC footing (isolated)
A rectangular footing is used when the column is rectangular, when there is a moment on the column, or when there is a space restriction on one side.
- Load and area: take the column service load (add about 10% for the weight of footing and backfill) and the safe bearing capacity .
- Dimensions: choose so that the projections on both sides of the column are about equal, i.e. ratio of column sides, with . If the column carries a moment , check and with .
- Factored upward soil pressure: () (or the maximum pressure for a footing with moment). The self-weight is not included in bending and shear design.
- Depth from the greater of: (a) one-way shear at a distance from the column face, and (b) punching shear at from the column face (permissible stress ), and the bending requirement. Adopt and .
- Bending moment at the face of the column in each direction: Find in each direction (minimum 0.12% of ).
- Distribution of steel: long-direction bars are spread uniformly over the width . For short-direction bars, a fraction of the total () is concentrated in a central band of width ; the rest is spread equally in the two outer portions (IS 456 cl. 34.3.1).
- Checks: one-way shear in both directions, punching shear, development length of the bars ( available length from the face of the column), and bearing at the column-footing interface; provide dowels.
- Detail: bars at the bottom, with 50 mm cover, plan and sections.
Why shear reinforcement is not provided in a footing
- A footing is a thick member, and its depth is made large enough that the shear stress is less than the permissible shear stress of concrete (for both one-way and punching shear). The concrete alone carries the shear, so stirrups are not needed.
- Stirrups in a thick, heavy slab cast against soil are difficult to place and hold, and would cause congestion.
- Bent-up bars or shear reinforcement are not efficient against punching in a thick footing, and the depth is easily increased at little cost.
- Increasing the depth also gives rigidity, so the assumption of a uniform soil pressure is better satisfied.
- 2082 Bhadra · 10+2+2 marks
Design an isolated footing for a column of size 500 mm x 500 mm, and carrying a service axial load of 1600 kN. Assume soil with an allowable bearing capacity of 125 kN/m at a depth of 1.25 m below ground. Assume Fe500 TMT steel for both column and footing, and M25 grade concrete for the footing and M25 grade concrete for the column. Make construction drawings in plan and elevation.
Answer
Data and assumptions
- Column 500 mm × 500 mm (long side mm along the footing length); footing concrete M25, steel Fe500; column concrete M25; column bars 8-20 mm.
- Service load kN.
- Allowable (safe) bearing capacity of soil = 125 kN/m² at 1.25 m depth.
- Depth of foundation 1.25 m is used only for the cover to the base; weight of footing and soil taken as 10% of the column load.
- Column bars assumed 8-20 mm (not given).
- Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth mm (cover + half bar). Load factor 1.5.
Size of footing
Weight of footing and backfill is taken as 10% of the column load.
Provide a square footing m, area = 14.44 m² 14.08 m².
Factored soil pressure
kN. kN/m².
Bending moments and reinforcement
Cantilever projections from the column face: along : mm; along : mm. : kN·m, kN·m. Required depth for flexure: is far larger than the moment for mm, so the depth is governed by shear (one-way or punching). Trial mm, mm, found by the shear checks below.
; minimum steel = 0.12% of .
| Direction | (kN·m) | req (mm²) | Provide | prov (mm²) |
|---|---|---|---|---|
| Along (width ) | 859.7 | 3192 | 12 mm @ 130 c/c | 3306 |
| Along (width ) | 859.7 | 3192 | 12 mm @ 130 c/c | 3306 |
Check for one-way shear (at distance from the column face)
- Along side: kN, MPa; , MPa (Table 19). , safe.
- Along side: kN, MPa; , MPa. Safe.
Check for two-way (punching) shear (at from the column face)
- Perimeter mm
- kN (average pressure; the effect of moment transfer is neglected).
- MPa; , MPa. , safe.
Development length
, MPa (M25, deformed bars): 12 mm bars → mm; 12 mm bars → mm. Available length from column face (less 50 mm end cover): 1600 mm along , 1600 mm along . Satisfied in both directions.
Bearing stress and transfer of load from column
Column area m². Bearing stress MPa. Permissible bearing stress: column concrete MPa; footing concrete with gives up to 22.50 MPa. The lesser, 11.25 MPa, governs. Capacity of bearing = 2812 kN kN, so the whole load can be transferred by bearing. Provide minimum dowels of 0.5% of column area = 1250 mm²: use 8 bars of 20 mm (2513 mm²) as dowels, same as column bars. Dowel length in compression mm (and the same lap with the column bars). Available depth in footing = 700 - 50 - 24 = 626 mm ; dowels are bent at the bottom with 90° bends.
Detailing
PLAN ELEVATION
+------------------+ col
| # # # # # # | | |
| # +------+ # # | _|_|__
| # | col | # # | |_____| <- D = 700 mm
| # +------+ # # | bars both ways
| # # # # # # |
+------------------+
L = 3.8 m, B = 3.8 m
- Bottom mesh: 12 mm @ 130 c/c along (lower layer), 12 mm @ 130 c/c along (upper layer), 50 mm clear cover; dowels 8-20 mm.
Answer: Footing 3.8 m × 3.8 m × 700 mm thick; 12 mm @ 130 c/c along the length and 12 mm @ 130 c/c along the width.
- 2081 Baisakh · 10 marks
Design a footing for supporting a square column of 400 mm x 400 mm. The column carries a service load of 1500 kN. The safe bearing capacity of soil is 150 kN/m. Use M20 concrete and Fe415 grade steel.
Answer
Data and assumptions
- Column 400 mm × 400 mm (long side mm along the footing length); footing concrete M20, steel Fe415; column concrete M20; column bars 8-20 mm.
- Service load kN.
- Allowable (safe) bearing capacity of soil = 150 kN/m².
- Column bars not given; 8-20 mm assumed. Loads are service loads.
- Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth mm (cover + half bar). Load factor 1.5.
Size of footing
Weight of footing and backfill is taken as 10% of the column load.
Provide a square footing m, area = 11.56 m² 11.00 m².
Factored soil pressure
kN. kN/m².
Bending moments and reinforcement
Cantilever projections from the column face: along : mm; along : mm. : kN·m, kN·m. Required depth for flexure: is far larger than the moment for mm, so the depth is governed by shear (one-way or punching). Trial mm, mm, found by the shear checks below.
; minimum steel = 0.12% of .
| Direction | (kN·m) | req (mm²) | Provide | prov (mm²) |
|---|---|---|---|---|
| Along (width ) | 744.5 | 3633 | 16 mm @ 185 c/c | 3695 |
| Along (width ) | 744.5 | 3633 | 16 mm @ 185 c/c | 3695 |
Check for one-way shear (at distance from the column face)
- Along side: kN, MPa; , MPa (Table 19). , safe.
- Along side: kN, MPa; , MPa. Safe.
Check for two-way (punching) shear (at from the column face)
- Perimeter mm
- kN (average pressure; the effect of moment transfer is neglected).
- MPa; , MPa. , safe.
Development length
, MPa (M20, deformed bars): 16 mm bars → mm; 16 mm bars → mm. Available length from column face (less 50 mm end cover): 1450 mm along , 1450 mm along . Satisfied in both directions.
Bearing stress and transfer of load from column
Column area m². Bearing stress MPa. Permissible bearing stress: column concrete MPa; footing concrete with gives up to 18.00 MPa. The lesser, 9.00 MPa, governs. Capacity of bearing = 1440 kN kN, so the excess 810 kN must be carried by dowels: mm²; the column bars (8-20 mm, 2513 mm²) are continued into the footing as dowels - adequate. Dowel length in compression mm (and the same lap with the column bars). Available depth in footing = 650 - 50 - 32 = 568 mm ; dowels are bent at the bottom with 90° bends.
Detailing
PLAN ELEVATION
+------------------+ col
| # # # # # # | | |
| # +------+ # # | _|_|__
| # | col | # # | |_____| <- D = 650 mm
| # +------+ # # | bars both ways
| # # # # # # |
+------------------+
L = 3.4 m, B = 3.4 m
- Bottom mesh: 16 mm @ 185 c/c along (lower layer), 16 mm @ 185 c/c along (upper layer), 50 mm clear cover; dowels 8-20 mm.
Answer: Footing 3.4 m × 3.4 m × 650 mm thick; 16 mm @ 185 c/c along the length and 16 mm @ 185 c/c along the width.
- 2080 Bhadra · 14 marks
Design an isolated footing supporting a square column 400 mm x 400 mm with 8-20 longitudinal reinforcement. The column is subjected to axial service load of 1000 kN. Consider base of footing is 1 m below the ground level. Take allowable bearing capacity of soil 100 kN/m, M15 concrete and Fe 415 steel. Also check transfer of load from column to footing.
Answer
Data and assumptions
- Column 400 mm × 400 mm (long side mm along the footing length); footing concrete M15, steel Fe415; column concrete M20; column bars 8-20 mm.
- Service load kN.
- Allowable (safe) bearing capacity of soil = 100 kN/m² at 1.0 m depth.
- Column concrete grade is not given; M20 is assumed for the column (footing is M15).
- Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth mm (cover + half bar). Load factor 1.5.
Size of footing
Weight of footing and backfill is taken as 10% of the column load.
Provide a square footing m, area = 11.56 m² 11.00 m².
Factored soil pressure
kN. kN/m².
Bending moments and reinforcement
Cantilever projections from the column face: along : mm; along : mm. : kN·m, kN·m. Required depth for flexure: is far larger than the moment for mm, so the depth is governed by shear (one-way or punching). Trial mm, mm, found by the shear checks below.
; minimum steel = 0.12% of .
| Direction | (kN·m) | req (mm²) | Provide | prov (mm²) |
|---|---|---|---|---|
| Along (width ) | 496.3 | 3331 | 16 mm @ 205 c/c | 3335 |
| Along (width ) | 496.3 | 3331 | 16 mm @ 205 c/c | 3335 |
Check for one-way shear (at distance from the column face)
- Along side: kN, MPa; , MPa (Table 19). , safe.
- Along side: kN, MPa; , MPa. Safe.
Check for two-way (punching) shear (at from the column face)
- Perimeter mm
- kN (average pressure; the effect of moment transfer is neglected).
- MPa; , MPa. , safe.
Development length
, MPa (M15, deformed bars): 16 mm bars → mm; 16 mm bars → mm. Available length from column face (less 50 mm end cover): 1450 mm along , 1450 mm along . Satisfied in both directions.
Bearing stress and transfer of load from column
Column area m². Bearing stress MPa. Permissible bearing stress: column concrete MPa; footing concrete with gives up to 13.50 MPa. The lesser, 9.00 MPa, governs. Capacity of bearing = 1440 kN kN, so the excess 60 kN must be carried by dowels: mm²; the column bars (8-20 mm, 2513 mm²) are continued into the footing as dowels - adequate. Dowel length in compression mm (and the same lap with the column bars). Available depth in footing = 500 - 50 - 32 = 418 mm ; dowels are bent at the bottom with 90° bends.
Detailing
PLAN ELEVATION
+------------------+ col
| # # # # # # | | |
| # +------+ # # | _|_|__
| # | col | # # | |_____| <- D = 500 mm
| # +------+ # # | bars both ways
| # # # # # # |
+------------------+
L = 3.4 m, B = 3.4 m
- Bottom mesh: 16 mm @ 205 c/c along (lower layer), 16 mm @ 205 c/c along (upper layer), 50 mm clear cover; dowels 8-20 mm.
Answer: Footing 3.4 m × 3.4 m × 500 mm thick; 16 mm @ 205 c/c along the length and 16 mm @ 205 c/c along the width.
- 2080 Baisakh · 12 marks
Design an isolated footing for a 450 mm x 500 mm sized column, with 6#20 mm diameter bars. Carrying factored axial load of 1100 kN and factored uniaxial moment of 120 kN-m at the column base. Take the depth of footing 1.5 m and safe bearing capacity of soil 100 kN/m. Use M20 concrete and Fe500 grade steel.
Answer
Data and assumptions
- Column 500 mm × 450 mm (long side mm along the footing length); footing concrete M20, steel Fe500; column concrete M20; column bars 6-20 mm.
- Given loads are factored: kN, kN·m. Service loads = factored / 1.5: kN, kN·m.
- Allowable (safe) bearing capacity of soil = 100 kN/m² at 1.5 m depth.
- Column concrete grade assumed M20 (same as footing). Moment acts about the minor axis so that it varies the pressure along the 500 mm side.
- Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth mm (cover + half bar). Load factor 1.5.
Size of footing
Weight of footing and backfill is taken as 10% of the column load.
Eccentricity m, which is less than , so there is no tension under the base. The size is chosen so that
Try m ( m²): kN/m² and kN/m² . Safe.
Factored soil pressure
kN, kN·m. : kN/m², kN/m² (average 116.6 kN/m²). Self-weight does not cause bending in the footing, so it is excluded.
Bending moments and reinforcement
Cantilever projections from the column face: along : mm; along : mm. Along (critical section at the column face on the side of maximum pressure, linear pressure): kN·m. Along (average pressure): kN·m. Required depth for flexure: is far larger than the moment for mm, so the depth is governed by shear (one-way or punching). Trial mm, mm, found by the shear checks below.
; minimum steel = 0.12% of .
| Direction | (kN·m) | req (mm²) | Provide | prov (mm²) |
|---|---|---|---|---|
| Along (width ) | 463.4 | 1871 | 12 mm @ 135 c/c | 1927 |
| Along (width ) | 204.6 | 3198 | 12 mm @ 140 c/c | 3312 |
For the rectangular footing, the short-direction steel is placed in a central band of width mm in the proportion (IS 456 cl. 34.3.1), where .
- Central band: mm² → 12 mm @ 105 mm c/c (21 bars).
- Each outer strip (900 mm wide): remaining steel 450 mm² or minimum 0.12% = 702 mm², whichever is more → 12 mm @ 125 mm c/c (7 bars).
Check for one-way shear (at distance from the column face)
- Along side: kN, MPa; , MPa (Table 19). , safe.
- Along side: kN, MPa; , MPa. Safe.
Check for two-way (punching) shear (at from the column face)
- Perimeter mm
- kN (average pressure; the effect of moment transfer is neglected).
- MPa; , MPa. , safe.
Development length
, MPa (M20, deformed bars): 12 mm bars → mm; 12 mm bars → mm. Available length from column face (less 50 mm end cover): 1750 mm along , 875 mm along . Satisfied in both directions.
Bearing stress and transfer of load from column
Column area m². Bearing stress MPa. Permissible bearing stress: column concrete MPa; footing concrete with gives up to 18.00 MPa. The lesser, 9.00 MPa, governs. Capacity of bearing = 2025 kN kN, so the whole load can be transferred by bearing. Provide minimum dowels of 0.5% of column area = 1125 mm²: use 6 bars of 20 mm (1885 mm²) as dowels, same as column bars. Dowel length in compression mm (and the same lap with the column bars). Available depth in footing = 650 - 50 - 24 = 576 mm ; dowels are bent at the bottom with 90° bends.
Detailing
PLAN ELEVATION
+------------------+ col
| # # # # # # | | |
| # +------+ # # | _|_|__
| # | col | # # | |_____| <- D = 650 mm
| # +------+ # # | bars both ways
| # # # # # # |
+------------------+
L = 4.1 m, B = 2.3 m
- Bottom mesh: 12 mm @ 135 c/c along (lower layer), 12 mm @ 140 c/c along (upper layer), 50 mm clear cover; dowels 6-20 mm.
Answer: Footing 4.1 m × 2.3 m × 650 mm thick; 12 mm @ 135 c/c along the length and 12 mm @ 140 c/c along the width.
- 2079 Bhadra · 14 marks
Design a footing for a rectangular column of size 30 cm x 35 cm reinforced with 8-20 mm dia. bars. The column is subjected to a factored axial load and moment of 1000 kN and 80 kN-m, respectively. The allowable bearing capacity of soil is 140 kN/m. At a depth of 1.6 m. Use M25 concrete and TMT bars for column and footing both. Sketch all of the reinforcement required.
Answer
Data and assumptions
- Column 350 mm × 300 mm (long side mm along the footing length); footing concrete M25, steel Fe500; column concrete M25; column bars 8-20 mm.
- Given loads are factored: kN, kN·m. Service loads = factored / 1.5: kN, kN·m.
- Allowable (safe) bearing capacity of soil = 140 kN/m² at 1.6 m depth.
- TMT bars taken as Fe500.
- Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth mm (cover + half bar). Load factor 1.5.
Size of footing
Weight of footing and backfill is taken as 10% of the column load.
Eccentricity m, which is less than , so there is no tension under the base. The size is chosen so that
Try m ( m²): kN/m² and kN/m² . Safe.
Factored soil pressure
kN, kN·m. : kN/m², kN/m² (average 164.5 kN/m²). Self-weight does not cause bending in the footing, so it is excluded.
Bending moments and reinforcement
Cantilever projections from the column face: along : mm; along : mm. Along (critical section at the column face on the side of maximum pressure, linear pressure): kN·m. Along (average pressure): kN·m. Required depth for flexure: is far larger than the moment for mm, so the depth is governed by shear (one-way or punching). Trial mm, mm, found by the shear checks below.
; minimum steel = 0.12% of .
| Direction | (kN·m) | req (mm²) | Provide | prov (mm²) |
|---|---|---|---|---|
| Along (width ) | 336.6 | 1482 | 12 mm @ 140 c/c | 1535 |
| Along (width ) | 168.4 | 2496 | 12 mm @ 140 c/c | 2585 |
For the rectangular footing, the short-direction steel is placed in a central band of width mm in the proportion (IS 456 cl. 34.3.1), where .
- Central band: mm² → 12 mm @ 110 mm c/c (17 bars).
- Each outer strip (650 mm wide): remaining steel 318 mm² or minimum 0.12% = 507 mm², whichever is more → 12 mm @ 130 mm c/c (5 bars).
Check for one-way shear (at distance from the column face)
- Along side: kN, MPa; , MPa (Table 19). , safe.
- Along side: kN, MPa; , MPa. Safe.
Check for two-way (punching) shear (at from the column face)
- Perimeter mm
- kN (average pressure; the effect of moment transfer is neglected).
- MPa; , MPa. , safe.
Development length
, MPa (M25, deformed bars): 12 mm bars → mm; 12 mm bars → mm. Available length from column face (less 50 mm end cover): 1375 mm along , 750 mm along . Satisfied in both directions.
Bearing stress and transfer of load from column
Column area m². Bearing stress MPa. Permissible bearing stress: column concrete MPa; footing concrete with gives up to 22.50 MPa. The lesser, 11.25 MPa, governs. Capacity of bearing = 1181 kN kN, so the whole load can be transferred by bearing. Provide minimum dowels of 0.5% of column area = 525 mm²: use 8 bars of 20 mm (2513 mm²) as dowels, same as column bars. Dowel length in compression mm (and the same lap with the column bars). Available depth in footing = 650 - 50 - 24 = 576 mm ; dowels are bent at the bottom with 90° bends.
Detailing
PLAN ELEVATION
+------------------+ col
| # # # # # # | | |
| # +------+ # # | _|_|__
| # | col | # # | |_____| <- D = 650 mm
| # +------+ # # | bars both ways
| # # # # # # |
+------------------+
L = 3.2 m, B = 1.9 m
- Bottom mesh: 12 mm @ 140 c/c along (lower layer), 12 mm @ 140 c/c along (upper layer), 50 mm clear cover; dowels 8-20 mm.
Answer: Footing 3.2 m × 1.9 m × 650 mm thick; 12 mm @ 140 c/c along the length and 12 mm @ 140 c/c along the width.
- 2079 Baisakh · 12 marks
Design a RC footing for a column having x-sectional dimension 400 mm x 300 mm, with 8-16 longitudinal reinforcement, column is subjected to axial compressive load of 1000 kN and reversible bending moment 100 kNm. Consider M20 concrete for footing, M25 concrete for column and Fe415 steel grade for both. Take safe bearing capacity of soil is 200 kN/m at a depth at 1.5 m.
Answer
Data and assumptions
- Column 400 mm × 300 mm (long side mm along the footing length); footing concrete M20, steel Fe415; column concrete M25; column bars 8-16 mm.
- Service load kN, service moment kN·m.
- Allowable (safe) bearing capacity of soil = 200 kN/m² at 1.5 m depth.
- Loads are service loads. The moment is reversible, so the same steel is provided on both sides.
- Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth mm (cover + half bar). Load factor 1.5.
Size of footing
Weight of footing and backfill is taken as 10% of the column load.
Eccentricity m, which is less than , so there is no tension under the base. The size is chosen so that
Try m ( m²): kN/m² and kN/m² . Safe.
Factored soil pressure
kN, kN·m. : kN/m², kN/m² (average 231.5 kN/m²). Self-weight does not cause bending in the footing, so it is excluded.
Bending moments and reinforcement
Cantilever projections from the column face: along : mm; along : mm. Along (critical section at the column face on the side of maximum pressure, linear pressure): kN·m. Along (average pressure): kN·m. Required depth for flexure: is far larger than the moment for mm, so the depth is governed by shear (one-way or punching). Trial mm, mm, found by the shear checks below.
; minimum steel = 0.12% of .
| Direction | (kN·m) | req (mm²) | Provide | prov (mm²) |
|---|---|---|---|---|
| Along (width ) | 569.5 | 2209 | 16 mm @ 160 c/c | 2262 |
| Along (width ) | 234.4 | 3456 | 16 mm @ 205 c/c | 3531 |
For the rectangular footing, the short-direction steel is placed in a central band of width mm in the proportion (IS 456 cl. 34.3.1), where .
- Central band: mm² → 16 mm @ 150 mm c/c (12 bars).
- Each outer strip (900 mm wide): remaining steel 576 mm² or minimum 0.12% = 864 mm², whichever is more → 16 mm @ 180 mm c/c (5 bars).
Check for one-way shear (at distance from the column face)
- Along side: kN, MPa; , MPa (Table 19). , safe.
- Along side: kN, MPa; , MPa. Safe.
Check for two-way (punching) shear (at from the column face)
- Perimeter mm
- kN (average pressure; the effect of moment transfer is neglected).
- MPa; , MPa. , safe.
Development length
, MPa (M20, deformed bars): 16 mm bars → mm; 16 mm bars → mm. Available length from column face (less 50 mm end cover): 1550 mm along , 700 mm along . Where it falls short, bars must be extended/bent up at the ends; provide 90° bends at the ends.
Bearing stress and transfer of load from column
Column area m². Bearing stress MPa. Permissible bearing stress: column concrete MPa; footing concrete with gives up to 18.00 MPa. The lesser, 11.25 MPa, governs. Capacity of bearing = 1350 kN kN, so the excess 150 kN must be carried by dowels: mm²; the column bars (8-16 mm, 1608 mm²) are continued into the footing as dowels - adequate. Dowel length in compression mm (and the same lap with the column bars). Available depth in footing = 800 - 50 - 32 = 718 mm , adequate.
Detailing
PLAN ELEVATION
+------------------+ col
| # # # # # # | | |
| # +------+ # # | _|_|__
| # | col | # # | |_____| <- D = 800 mm
| # +------+ # # | bars both ways
| # # # # # # |
+------------------+
L = 3.6 m, B = 1.8 m
- Bottom mesh: 16 mm @ 160 c/c along (lower layer), 16 mm @ 205 c/c along (upper layer), 50 mm clear cover; dowels 8-16 mm.
Answer: Footing 3.6 m × 1.8 m × 800 mm thick; 16 mm @ 160 c/c along the length and 16 mm @ 205 c/c along the width.
- 2076 Chaitra · 13 marks
Design a RC footing to carry a column load of 1250 kN from 400 x 400 mm square column having 20 mm diameter bar as longitudinal steel. The bearing capacity of soil is 140 kN/m. Consider the depth of foundation as 1.8 m. Take unit weight of earth as 18 kN/m. Use M20 concrete mix and Fe415 grade steel. Also sketch the reinforcements in plan and section.
Answer
Data and assumptions
- Column 400 mm × 400 mm (long side mm along the footing length); footing concrete M20, steel Fe415; column concrete M20; column bars 6-20 mm.
- Service load kN.
- Allowable (safe) bearing capacity of soil = 140 kN/m² at 1.8 m depth, soil unit weight 18 kN/m³.
- Bearing capacity is taken as the gross value at the foundation level.
- Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth mm (cover + half bar). Load factor 1.5.
Size of footing
Net safe bearing capacity = kN/m² (this takes care of the weight of footing and backfill).
Provide a square footing m, area = 12.25 m² 11.62 m².
Factored soil pressure
kN. kN/m².
Bending moments and reinforcement
Cantilever projections from the column face: along : mm; along : mm. : kN·m, kN·m. Required depth for flexure: is far larger than the moment for mm, so the depth is governed by shear (one-way or punching). Trial mm, mm, found by the shear checks below.
; minimum steel = 0.12% of .
| Direction | (kN·m) | req (mm²) | Provide | prov (mm²) |
|---|---|---|---|---|
| Along (width ) | 643.5 | 3815 | 16 mm @ 180 c/c | 3910 |
| Along (width ) | 643.5 | 3815 | 16 mm @ 180 c/c | 3910 |
Check for one-way shear (at distance from the column face)
- Along side: kN, MPa; , MPa (Table 19). , safe.
- Along side: kN, MPa; , MPa. Safe.
Check for two-way (punching) shear (at from the column face)
- Perimeter mm
- kN (average pressure; the effect of moment transfer is neglected).
- MPa; , MPa. , safe.
Development length
, MPa (M20, deformed bars): 16 mm bars → mm; 16 mm bars → mm. Available length from column face (less 50 mm end cover): 1500 mm along , 1500 mm along . Satisfied in both directions.
Bearing stress and transfer of load from column
Column area m². Bearing stress MPa. Permissible bearing stress: column concrete MPa; footing concrete with gives up to 18.00 MPa. The lesser, 9.00 MPa, governs. Capacity of bearing = 1440 kN kN, so the excess 435 kN must be carried by dowels: mm²; the column bars (6-20 mm, 1885 mm²) are continued into the footing as dowels - adequate. Dowel length in compression mm (and the same lap with the column bars). Available depth in footing = 550 - 50 - 32 = 468 mm ; dowels are bent at the bottom with 90° bends.
Detailing
PLAN ELEVATION
+------------------+ col
| # # # # # # | | |
| # +------+ # # | _|_|__
| # | col | # # | |_____| <- D = 550 mm
| # +------+ # # | bars both ways
| # # # # # # |
+------------------+
L = 3.5 m, B = 3.5 m
- Bottom mesh: 16 mm @ 180 c/c along (lower layer), 16 mm @ 180 c/c along (upper layer), 50 mm clear cover; dowels 6-20 mm.
Answer: Footing 3.5 m × 3.5 m × 550 mm thick; 16 mm @ 180 c/c along the length and 16 mm @ 180 c/c along the width.
- 2076 Asoj · 10 marks
Design an isolated footing to carry an axial factored load of 1600 kN. The column is 400 mm by 400 mm in size with 20 mm dia longitudinal bars. The bearing capacity of soil is 180 kN/m. For footing, adopt M20 concrete and 415 grade HSD bars. Check for shear is necessary.
Answer
Data and assumptions
- Column 400 mm × 400 mm (long side mm along the footing length); footing concrete M20, steel Fe415; column concrete M20; column bars 8-20 mm.
- Given loads are factored: kN. Service loads = factored / 1.5: kN.
- Allowable (safe) bearing capacity of soil = 180 kN/m².
- The load of 1600 kN is a factored load.
- Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth mm (cover + half bar). Load factor 1.5.
Size of footing
Weight of footing and backfill is taken as 10% of the column load.
Provide a square footing m, area = 6.76 m² 6.52 m².
Factored soil pressure
kN. kN/m².
Bending moments and reinforcement
Cantilever projections from the column face: along : mm; along : mm. : kN·m, kN·m. Required depth for flexure: is far larger than the moment for mm, so the depth is governed by shear (one-way or punching). Trial mm, mm, found by the shear checks below.
; minimum steel = 0.12% of .
| Direction | (kN·m) | req (mm²) | Provide | prov (mm²) |
|---|---|---|---|---|
| Along (width ) | 372.3 | 2183 | 12 mm @ 130 c/c | 2262 |
| Along (width ) | 372.3 | 2183 | 12 mm @ 130 c/c | 2262 |
Check for one-way shear (at distance from the column face)
- Along side: kN, MPa; , MPa (Table 19). , safe.
- Along side: kN, MPa; , MPa. Safe.
Check for two-way (punching) shear (at from the column face)
- Perimeter mm
- kN (average pressure; the effect of moment transfer is neglected).
- MPa; , MPa. , safe.
Development length
, MPa (M20, deformed bars): 12 mm bars → mm; 12 mm bars → mm. Available length from column face (less 50 mm end cover): 1050 mm along , 1050 mm along . Satisfied in both directions.
Bearing stress and transfer of load from column
Column area m². Bearing stress MPa. Permissible bearing stress: column concrete MPa; footing concrete with gives up to 18.00 MPa. The lesser, 9.00 MPa, governs. Capacity of bearing = 1440 kN kN, so the excess 160 kN must be carried by dowels: mm²; the column bars (8-20 mm, 2513 mm²) are continued into the footing as dowels - adequate. Dowel length in compression mm (and the same lap with the column bars). Available depth in footing = 550 - 50 - 24 = 476 mm ; dowels are bent at the bottom with 90° bends.
Detailing
PLAN ELEVATION
+------------------+ col
| # # # # # # | | |
| # +------+ # # | _|_|__
| # | col | # # | |_____| <- D = 550 mm
| # +------+ # # | bars both ways
| # # # # # # |
+------------------+
L = 2.6 m, B = 2.6 m
- Bottom mesh: 12 mm @ 130 c/c along (lower layer), 12 mm @ 130 c/c along (upper layer), 50 mm clear cover; dowels 8-20 mm.
Answer: Footing 2.6 m × 2.6 m × 550 mm thick; 12 mm @ 130 c/c along the length and 12 mm @ 130 c/c along the width.
- 2075 Chaitra · 10 marks
Design a R.C.C isolated footing to carry an axial load of 1500 kN. The column is 350 mm x 350 mm in size with 20 mm diameter, 8 Nos longitudinal bars. The bearing capacity of soil is 175 kN/m. Use M20 grade concrete and Fe415 grade steel. Assume missing datas.
Answer
Data and assumptions
- Column 350 mm × 350 mm (long side mm along the footing length); footing concrete M20, steel Fe415; column concrete M20; column bars 8-20 mm.
- Service load kN.
- Allowable (safe) bearing capacity of soil = 175 kN/m².
- Axial load taken as service load; column concrete M20 assumed.
- Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth mm (cover + half bar). Load factor 1.5.
Size of footing
Weight of footing and backfill is taken as 10% of the column load.
Provide a square footing m, area = 9.61 m² 9.43 m².
Factored soil pressure
kN. kN/m².
Bending moments and reinforcement
Cantilever projections from the column face: along : mm; along : mm. : kN·m, kN·m. Required depth for flexure: is far larger than the moment for mm, so the depth is governed by shear (one-way or punching). Trial mm, mm, found by the shear checks below.
; minimum steel = 0.12% of .
| Direction | (kN·m) | req (mm²) | Provide | prov (mm²) |
|---|---|---|---|---|
| Along (width ) | 686.1 | 3350 | 16 mm @ 185 c/c | 3369 |
| Along (width ) | 686.1 | 3350 | 16 mm @ 185 c/c | 3369 |
Check for one-way shear (at distance from the column face)
- Along side: kN, MPa; , MPa (Table 19). , safe.
- Along side: kN, MPa; , MPa. Safe.
Check for two-way (punching) shear (at from the column face)
- Perimeter mm
- kN (average pressure; the effect of moment transfer is neglected).
- MPa; , MPa. , safe.
Development length
, MPa (M20, deformed bars): 16 mm bars → mm; 16 mm bars → mm. Available length from column face (less 50 mm end cover): 1325 mm along , 1325 mm along . Satisfied in both directions.
Bearing stress and transfer of load from column
Column area m². Bearing stress MPa. Permissible bearing stress: column concrete MPa; footing concrete with gives up to 18.00 MPa. The lesser, 9.00 MPa, governs. Capacity of bearing = 1102 kN kN, so the excess 1148 kN must be carried by dowels: mm²; the column bars (8-20 mm, 2513 mm²) are continued into the footing as dowels; provide extra dowels to reach this area. Dowel length in compression mm (and the same lap with the column bars). Available depth in footing = 650 - 50 - 32 = 568 mm ; dowels are bent at the bottom with 90° bends.
Detailing
PLAN ELEVATION
+------------------+ col
| # # # # # # | | |
| # +------+ # # | _|_|__
| # | col | # # | |_____| <- D = 650 mm
| # +------+ # # | bars both ways
| # # # # # # |
+------------------+
L = 3.1 m, B = 3.1 m
- Bottom mesh: 16 mm @ 185 c/c along (lower layer), 16 mm @ 185 c/c along (upper layer), 50 mm clear cover; dowels 8-20 mm.
Answer: Footing 3.1 m × 3.1 m × 650 mm thick; 16 mm @ 185 c/c along the length and 16 mm @ 185 c/c along the width.
- 2074 Chaitra · 10 marks
Design an isolated footing to support a square column of 400 x 400 mm. The column (400 x 400 mm) carries a service load of 1200 kN. The allowable soil pressure is 150 kN/m. Use M20 concrete and Fe415 grade steel. Unit weight of soil above footing base = 18 kN/m. Necessary missing data assume suitably.
Answer
Data and assumptions
- Column 400 mm × 400 mm (long side mm along the footing length); footing concrete M20, steel Fe415; column concrete M20; column bars 8-20 mm.
- Service load kN.
- Allowable (safe) bearing capacity of soil = 150 kN/m² at 1.5 m depth, soil unit weight 18 kN/m³.
- Depth of foundation is not given; 1.5 m is assumed. Column bars assumed 8-20 mm.
- Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth mm (cover + half bar). Load factor 1.5.
Size of footing
Net safe bearing capacity = kN/m² (this takes care of the weight of footing and backfill).
Provide a square footing m, area = 10.24 m² 9.76 m².
Factored soil pressure
kN. kN/m².
Bending moments and reinforcement
Cantilever projections from the column face: along : mm; along : mm. : kN·m, kN·m. Required depth for flexure: is far larger than the moment for mm, so the depth is governed by shear (one-way or punching). Trial mm, mm, found by the shear checks below.
; minimum steel = 0.12% of .
| Direction | (kN·m) | req (mm²) | Provide | prov (mm²) |
|---|---|---|---|---|
| Along (width ) | 551.2 | 3258 | 16 mm @ 195 c/c | 3299 |
| Along (width ) | 551.2 | 3258 | 16 mm @ 195 c/c | 3299 |
Check for one-way shear (at distance from the column face)
- Along side: kN, MPa; , MPa (Table 19). , safe.
- Along side: kN, MPa; , MPa. Safe.
Check for two-way (punching) shear (at from the column face)
- Perimeter mm
- kN (average pressure; the effect of moment transfer is neglected).
- MPa; , MPa. , safe.
Development length
, MPa (M20, deformed bars): 16 mm bars → mm; 16 mm bars → mm. Available length from column face (less 50 mm end cover): 1350 mm along , 1350 mm along . Satisfied in both directions.
Bearing stress and transfer of load from column
Column area m². Bearing stress MPa. Permissible bearing stress: column concrete MPa; footing concrete with gives up to 18.00 MPa. The lesser, 9.00 MPa, governs. Capacity of bearing = 1440 kN kN, so the excess 360 kN must be carried by dowels: mm²; the column bars (8-20 mm, 2513 mm²) are continued into the footing as dowels - adequate. Dowel length in compression mm (and the same lap with the column bars). Available depth in footing = 550 - 50 - 32 = 468 mm ; dowels are bent at the bottom with 90° bends.
Detailing
PLAN ELEVATION
+------------------+ col
| # # # # # # | | |
| # +------+ # # | _|_|__
| # | col | # # | |_____| <- D = 550 mm
| # +------+ # # | bars both ways
| # # # # # # |
+------------------+
L = 3.2 m, B = 3.2 m
- Bottom mesh: 16 mm @ 195 c/c along (lower layer), 16 mm @ 195 c/c along (upper layer), 50 mm clear cover; dowels 8-20 mm.
Answer: Footing 3.2 m × 3.2 m × 550 mm thick; 16 mm @ 195 c/c along the length and 16 mm @ 195 c/c along the width.
- 2074 Asoj · 14 marks
Design a footing for a square column of size 350 mm x 350 mm reinforced with 8-16 mm dia. bars. The column is subjected to a factored axial load and moment of 1100 KN and 60 KN-m, respectively. The allowable bearing capacity of soil is 150 KN/m at a depth of 1.5 m. Use M20 Concrete and Fe 500 steel for footing, and M30 Concrete and Fe 500 steel for column. Assume that the moment is reversible. Sketch the details (Plan and sections).
Answer
Data and assumptions
- Column 350 mm × 350 mm (long side mm along the footing length); footing concrete M20, steel Fe500; column concrete M30; column bars 8-16 mm.
- Given loads are factored: kN, kN·m. Service loads = factored / 1.5: kN, kN·m.
- Allowable (safe) bearing capacity of soil = 150 kN/m² at 1.5 m depth.
- The moment is reversible: same steel on both sides.
- Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth mm (cover + half bar). Load factor 1.5.
Size of footing
Weight of footing and backfill is taken as 10% of the column load.
Eccentricity m, which is less than , so there is no tension under the base. The size is chosen so that
Try m ( m²): kN/m² and kN/m² . Safe.
Factored soil pressure
kN, kN·m. : kN/m², kN/m² (average 185.2 kN/m²). Self-weight does not cause bending in the footing, so it is excluded.
Bending moments and reinforcement
Cantilever projections from the column face: along : mm; along : mm. Along (critical section at the column face on the side of maximum pressure, linear pressure): kN·m. Along (average pressure): kN·m. Required depth for flexure: is far larger than the moment for mm, so the depth is governed by shear (one-way or punching). Trial mm, mm, found by the shear checks below.
; minimum steel = 0.12% of .
| Direction | (kN·m) | req (mm²) | Provide | prov (mm²) |
|---|---|---|---|---|
| Along (width ) | 377.1 | 1512 | 12 mm @ 130 c/c | 1566 |
| Along (width ) | 160.6 | 2772 | 12 mm @ 130 c/c | 2871 |
For the rectangular footing, the short-direction steel is placed in a central band of width mm in the proportion (IS 456 cl. 34.3.1), where .
- Central band: mm² → 12 mm @ 100 mm c/c (18 bars).
- Each outer strip (750 mm wide): remaining steel 408 mm² or minimum 0.12% = 630 mm², whichever is more → 12 mm @ 120 mm c/c (6 bars).
Check for one-way shear (at distance from the column face)
- Along side: kN, MPa; , MPa (Table 19). , safe.
- Along side: kN, MPa; , MPa. Safe.
Check for two-way (punching) shear (at from the column face)
- Perimeter mm
- kN (average pressure; the effect of moment transfer is neglected).
- MPa; , MPa. , safe.
Development length
, MPa (M20, deformed bars): 12 mm bars → mm; 12 mm bars → mm. Available length from column face (less 50 mm end cover): 1425 mm along , 675 mm along . Where it falls short, bars must be extended/bent up at the ends; provide 90° bends at the ends.
Bearing stress and transfer of load from column
Column area m². Bearing stress MPa. Permissible bearing stress: column concrete MPa; footing concrete with gives up to 18.00 MPa. The lesser, 13.50 MPa, governs. Capacity of bearing = 1654 kN kN, so the whole load can be transferred by bearing. Provide minimum dowels of 0.5% of column area = 612 mm²: use 8 bars of 16 mm (1608 mm²) as dowels, same as column bars. Dowel length in compression mm (and the same lap with the column bars). Available depth in footing = 700 - 50 - 24 = 626 mm ; dowels are bent at the bottom with 90° bends.
Detailing
PLAN ELEVATION
+------------------+ col
| # # # # # # | | |
| # +------+ # # | _|_|__
| # | col | # # | |_____| <- D = 700 mm
| # +------+ # # | bars both ways
| # # # # # # |
+------------------+
L = 3.3 m, B = 1.8 m
- Bottom mesh: 12 mm @ 130 c/c along (lower layer), 12 mm @ 130 c/c along (upper layer), 50 mm clear cover; dowels 8-16 mm.
Answer: Footing 3.3 m × 1.8 m × 700 mm thick; 12 mm @ 130 c/c along the length and 12 mm @ 130 c/c along the width.
- 2073 Shrawan · 14 marks
Design an isolated footing for a square column 450 mm x 450 mm, reinforcement with 8-20 dia bars and carrying a service load of 1600 kN. Assume bearing capacity of soil as 250 kN/m and depth of foundation as 1.5 m. Adopt M20 concrete and Fe 500 steel. Also check the development length and bearing stress in concrete.
Answer
Data and assumptions
- Column 450 mm × 450 mm (long side mm along the footing length); footing concrete M20, steel Fe500; column concrete M20; column bars 8-20 mm.
- Service load kN.
- Allowable (safe) bearing capacity of soil = 250 kN/m² at 1.5 m depth.
- Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth mm (cover + half bar). Load factor 1.5.
Size of footing
Weight of footing and backfill is taken as 10% of the column load.
Provide a square footing m, area = 7.29 m² 7.04 m².
Factored soil pressure
kN. kN/m².
Bending moments and reinforcement
Cantilever projections from the column face: along : mm; along : mm. : kN·m, kN·m. Required depth for flexure: is far larger than the moment for mm, so the depth is governed by shear (one-way or punching). Trial mm, mm, found by the shear checks below.
; minimum steel = 0.12% of .
| Direction | (kN·m) | req (mm²) | Provide | prov (mm²) |
|---|---|---|---|---|
| Along (width ) | 562.5 | 2268 | 12 mm @ 130 c/c | 2349 |
| Along (width ) | 562.5 | 2268 | 12 mm @ 130 c/c | 2349 |
Check for one-way shear (at distance from the column face)
- Along side: kN, MPa; , MPa (Table 19). , safe.
- Along side: kN, MPa; , MPa. Safe.
Check for two-way (punching) shear (at from the column face)
- Perimeter mm
- kN (average pressure; the effect of moment transfer is neglected).
- MPa; , MPa. , safe.
Development length
, MPa (M20, deformed bars): 12 mm bars → mm; 12 mm bars → mm. Available length from column face (less 50 mm end cover): 1075 mm along , 1075 mm along . Satisfied in both directions.
Bearing stress and transfer of load from column
Column area m². Bearing stress MPa. Permissible bearing stress: column concrete MPa; footing concrete with gives up to 18.00 MPa. The lesser, 9.00 MPa, governs. Capacity of bearing = 1822 kN kN, so the excess 578 kN must be carried by dowels: mm²; the column bars (8-20 mm, 2513 mm²) are continued into the footing as dowels - adequate. Dowel length in compression mm (and the same lap with the column bars). Available depth in footing = 700 - 50 - 24 = 626 mm ; dowels are bent at the bottom with 90° bends.
Detailing
PLAN ELEVATION
+------------------+ col
| # # # # # # | | |
| # +------+ # # | _|_|__
| # | col | # # | |_____| <- D = 700 mm
| # +------+ # # | bars both ways
| # # # # # # |
+------------------+
L = 2.7 m, B = 2.7 m
- Bottom mesh: 12 mm @ 130 c/c along (lower layer), 12 mm @ 130 c/c along (upper layer), 50 mm clear cover; dowels 8-20 mm.
Answer: Footing 2.7 m × 2.7 m × 700 mm thick; 12 mm @ 130 c/c along the length and 12 mm @ 130 c/c along the width.
- 2072 Chaitra · 14 marks
Design an isolated rectangular footing for a column of size 300 mm x 400 mm. The column is carrying 8-20 mm dia bars with M25 concrete. The column is carrying a factored axial load of 1200 kN and the factored moment of 120 kN-m. Sketch the details of designed reinforcements in plan and sections. Also check the bearing stress and development length required. Adopt M20 grade concrete for footing. Grade of steel used is Fe415 [text partly cut off in scan]. Assume bearing capacity of soil = 200 kN/m at 1.25 m below GL.
Answer
Data and assumptions
- Column 400 mm × 300 mm (long side mm along the footing length); footing concrete M20, steel Fe415; column concrete M25; column bars 8-20 mm.
- Given loads are factored: kN, kN·m. Service loads = factored / 1.5: kN, kN·m.
- Allowable (safe) bearing capacity of soil = 200 kN/m² at 1.25 m depth.
- Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth mm (cover + half bar). Load factor 1.5.
Size of footing
Weight of footing and backfill is taken as 10% of the column load.
Eccentricity m, which is less than , so there is no tension under the base. The size is chosen so that
Try m ( m²): kN/m² and kN/m² . Safe.
Factored soil pressure
kN, kN·m. : kN/m², kN/m² (average 227.7 kN/m²). Self-weight does not cause bending in the footing, so it is excluded.
Bending moments and reinforcement
Cantilever projections from the column face: along : mm; along : mm. Along (critical section at the column face on the side of maximum pressure, linear pressure): kN·m. Along (average pressure): kN·m. Required depth for flexure: is far larger than the moment for mm, so the depth is governed by shear (one-way or punching). Trial mm, mm, found by the shear checks below.
; minimum steel = 0.12% of .
| Direction | (kN·m) | req (mm²) | Provide | prov (mm²) |
|---|---|---|---|---|
| Along (width ) | 381.4 | 1707 | 16 mm @ 200 c/c | 1709 |
| Along (width ) | 172.9 | 2604 | 12 mm @ 130 c/c | 2697 |
For the rectangular footing, the short-direction steel is placed in a central band of width mm in the proportion (IS 456 cl. 34.3.1), where .
- Central band: mm² → 12 mm @ 100 mm c/c (17 bars).
- Each outer strip (700 mm wide): remaining steel 380 mm² or minimum 0.12% = 588 mm², whichever is more → 12 mm @ 115 mm c/c (6 bars).
Check for one-way shear (at distance from the column face)
- Along side: kN, MPa; , MPa (Table 19). , safe.
- Along side: kN, MPa; , MPa. Safe.
Check for two-way (punching) shear (at from the column face)
- Perimeter mm
- kN (average pressure; the effect of moment transfer is neglected).
- MPa; , MPa. , safe.
Development length
, MPa (M20, deformed bars): 16 mm bars → mm; 12 mm bars → mm. Available length from column face (less 50 mm end cover): 1300 mm along , 650 mm along . Satisfied in both directions.
Bearing stress and transfer of load from column
Column area m². Bearing stress MPa. Permissible bearing stress: column concrete MPa; footing concrete with gives up to 18.00 MPa. The lesser, 11.25 MPa, governs. Capacity of bearing = 1350 kN kN, so the whole load can be transferred by bearing. Provide minimum dowels of 0.5% of column area = 600 mm²: use 8 bars of 20 mm (2513 mm²) as dowels, same as column bars. Dowel length in compression mm (and the same lap with the column bars). Available depth in footing = 700 - 50 - 28 = 622 mm ; dowels are bent at the bottom with 90° bends.
Detailing
PLAN ELEVATION
+------------------+ col
| # # # # # # | | |
| # +------+ # # | _|_|__
| # | col | # # | |_____| <- D = 700 mm
| # +------+ # # | bars both ways
| # # # # # # |
+------------------+
L = 3.1 m, B = 1.7 m
- Bottom mesh: 16 mm @ 200 c/c along (lower layer), 12 mm @ 130 c/c along (upper layer), 50 mm clear cover; dowels 8-20 mm.
Answer: Footing 3.1 m × 1.7 m × 700 mm thick; 16 mm @ 200 c/c along the length and 12 mm @ 130 c/c along the width.
- 2072 Kartik · 16 marks
Design a rectangle footing to carry a column load of 1150 kN and BM of 250 kN-m from 600 x 600 mm square column with the 20 mm diameter steel. The bearing capacity of soil is 200 kN/m. Consider depth of foundation as 1.5 m. Take unit weight of earth is 17 kN/m. Use M20 concrete and Fe 415 steel.
Answer
Data and assumptions
- Column 600 mm × 600 mm (long side mm along the footing length); footing concrete M20, steel Fe415; column concrete M20; column bars 8-20 mm.
- Service load kN, service moment kN·m.
- Allowable (safe) bearing capacity of soil = 200 kN/m² at 1.5 m depth, soil unit weight 17 kN/m³.
- Loads are service loads.
- Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth mm (cover + half bar). Load factor 1.5.
Size of footing
Net safe bearing capacity = kN/m² (this takes care of the weight of footing and backfill).
Eccentricity m, which is less than , so there is no tension under the base. The size is chosen so that
Try m ( m²): kN/m² and kN/m² . Safe.
Factored soil pressure
kN, kN·m. : kN/m², kN/m² (average 196.0 kN/m²). Self-weight does not cause bending in the footing, so it is excluded.
Bending moments and reinforcement
Cantilever projections from the column face: along : mm; along : mm. Along (critical section at the column face on the side of maximum pressure, linear pressure): kN·m. Along (average pressure): kN·m. Required depth for flexure: is far larger than the moment for mm, so the depth is governed by shear (one-way or punching). Trial mm, mm, found by the shear checks below.
; minimum steel = 0.12% of .
| Direction | (kN·m) | req (mm²) | Provide | prov (mm²) |
|---|---|---|---|---|
| Along (width ) | 711.2 | 2574 | 16 mm @ 170 c/c | 2602 |
| Along (width ) | 250.9 | 4080 | 16 mm @ 195 c/c | 4124 |
For the rectangular footing, the short-direction steel is placed in a central band of width mm in the proportion (IS 456 cl. 34.3.1), where .
- Central band: mm² → 16 mm @ 145 mm c/c (15 bars).
- Each outer strip (900 mm wide): remaining steel 592 mm² or minimum 0.12% = 918 mm², whichever is more → 16 mm @ 175 mm c/c (5 bars).
Check for one-way shear (at distance from the column face)
- Along side: kN, MPa; , MPa (Table 19). , safe.
- Along side: kN, MPa; , MPa. Safe.
Check for two-way (punching) shear (at from the column face)
- Perimeter mm
- kN (average pressure; the effect of moment transfer is neglected).
- MPa; , MPa. , safe.
Development length
, MPa (M20, deformed bars): 16 mm bars → mm; 16 mm bars → mm. Available length from column face (less 50 mm end cover): 1650 mm along , 750 mm along . Where it falls short, bars must be extended/bent up at the ends; provide 90° bends at the ends.
Bearing stress and transfer of load from column
Column area m². Bearing stress MPa. Permissible bearing stress: column concrete MPa; footing concrete with gives up to 18.00 MPa. The lesser, 9.00 MPa, governs. Capacity of bearing = 3240 kN kN, so the whole load can be transferred by bearing. Provide minimum dowels of 0.5% of column area = 1800 mm²: use 8 bars of 20 mm (2513 mm²) as dowels, same as column bars. Dowel length in compression mm (and the same lap with the column bars). Available depth in footing = 850 - 50 - 32 = 768 mm , adequate.
Detailing
PLAN ELEVATION
+------------------+ col
| # # # # # # | | |
| # +------+ # # | _|_|__
| # | col | # # | |_____| <- D = 850 mm
| # +------+ # # | bars both ways
| # # # # # # |
+------------------+
L = 4.0 m, B = 2.2 m
- Bottom mesh: 16 mm @ 170 c/c along (lower layer), 16 mm @ 195 c/c along (upper layer), 50 mm clear cover; dowels 8-20 mm.
Answer: Footing 4.0 m × 2.2 m × 850 mm thick; 16 mm @ 170 c/c along the length and 16 mm @ 195 c/c along the width.
- 2071 Chaitra · 14 marks
Design an isolated footing to carry a column load of 1300 kN and BM of 100 kN-m from both axes of column. Column is 500 mm x 500 mm in size with 25 mm diameter longitudinal steel. The bearing capacity of soil is 220 kN/m. Consider depth of foundation as 1.70 m. Take unit weight of soil as 18.5 kN/m. Use M25 grade concrete and Fe415 steel.
Answer
Data and assumptions
- Column 500 mm × 500 mm (long side mm along the footing length); footing concrete M25, steel Fe415; column concrete M25; column bars 8-25 mm.
- Service load kN, service moment kN·m (about the other axis also 100 kN·m).
- Allowable (safe) bearing capacity of soil = 220 kN/m² at 1.7 m depth, soil unit weight 18.5 kN/m³.
- Loads are service loads; moments of 100 kN·m act about both axes, so a square footing is used.
- Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth mm (cover + half bar). Load factor 1.5.
Size of footing
Net safe bearing capacity = kN/m² (this takes care of the weight of footing and backfill).
Eccentricity m (and 0.077 m in the other direction), which is less than , so there is no tension under the base. The size is chosen so that
Try m ( m²): kN/m² and kN/m² . Safe.
Factored soil pressure
kN, kN·m. : kN/m², kN/m² (average 202.9 kN/m²). Self-weight does not cause bending in the footing, so it is excluded.
Bending moments and reinforcement
Cantilever projections from the column face: along : mm; along : mm. With the maximum pressure assumed over the cantilever (conservative): kN·m, kN·m. Required depth for flexure: is far larger than the moment for mm, so the depth is governed by shear (one-way or punching). Trial mm, mm, found by the shear checks below.
; minimum steel = 0.12% of .
| Direction | (kN·m) | req (mm²) | Provide | prov (mm²) |
|---|---|---|---|---|
| Along (width ) | 689.8 | 3341 | 16 mm @ 185 c/c | 3369 |
| Along (width ) | 689.8 | 3341 | 16 mm @ 185 c/c | 3369 |
Check for one-way shear (at distance from the column face)
- Along side: kN, MPa; , MPa (Table 19). , safe.
- Along side: kN, MPa; , MPa. Safe.
Check for two-way (punching) shear (at from the column face)
- Perimeter mm
- kN (average pressure; the effect of moment transfer is neglected).
- MPa; , MPa. , safe.
Development length
, MPa (M25, deformed bars): 16 mm bars → mm; 16 mm bars → mm. Available length from column face (less 50 mm end cover): 1250 mm along , 1250 mm along . Satisfied in both directions.
Bearing stress and transfer of load from column
Column area m². Bearing stress MPa. Permissible bearing stress: column concrete MPa; footing concrete with gives up to 22.50 MPa. The lesser, 11.25 MPa, governs. Capacity of bearing = 2812 kN kN, so the whole load can be transferred by bearing. Provide minimum dowels of 0.5% of column area = 1250 mm²: use 8 bars of 25 mm (3927 mm²) as dowels, same as column bars. Dowel length in compression mm (and the same lap with the column bars). Available depth in footing = 650 - 50 - 32 = 568 mm ; dowels are bent at the bottom with 90° bends.
Detailing
PLAN ELEVATION
+------------------+ col
| # # # # # # | | |
| # +------+ # # | _|_|__
| # | col | # # | |_____| <- D = 650 mm
| # +------+ # # | bars both ways
| # # # # # # |
+------------------+
L = 3.1 m, B = 3.1 m
- Bottom mesh: 16 mm @ 185 c/c along (lower layer), 16 mm @ 185 c/c along (upper layer), 50 mm clear cover; dowels 8-25 mm.
Answer: Footing 3.1 m × 3.1 m × 650 mm thick; 16 mm @ 185 c/c along the length and 16 mm @ 185 c/c along the width.
- 2069 Chaitra · 14 marks
Design the isolated footing of a column of 350 mm x 500 mm. Column is subjected to design axial load of 2000 kN and design BM of 80 kN-m. Allowable bearing capacity of soil is equal to 175 kN/m.
Answer
Data and assumptions
- Column 500 mm × 350 mm (long side mm along the footing length); footing concrete M20, steel Fe415; column concrete M20; column bars 8-20 mm.
- Given loads are factored: kN, kN·m. Service loads = factored / 1.5: kN, kN·m.
- Allowable (safe) bearing capacity of soil = 175 kN/m².
- The question gives design (factored) loads; M20 concrete and Fe415 steel are assumed, with 8-20 mm column bars.
- Moment acts about the minor axis, varying the pressure along the 500 mm side.
- Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth mm (cover + half bar). Load factor 1.5.
Size of footing
Weight of footing and backfill is taken as 10% of the column load.
Eccentricity m, which is less than , so there is no tension under the base. The size is chosen so that
Try m ( m²): kN/m² and kN/m² . Safe.
Factored soil pressure
kN, kN·m. : kN/m², kN/m² (average 223.0 kN/m²). Self-weight does not cause bending in the footing, so it is excluded.
Bending moments and reinforcement
Cantilever projections from the column face: along : mm; along : mm. Along (critical section at the column face on the side of maximum pressure, linear pressure): kN·m. Along (average pressure): kN·m. Required depth for flexure: is far larger than the moment for mm, so the depth is governed by shear (one-way or punching). Trial mm, mm, found by the shear checks below.
; minimum steel = 0.12% of .
| Direction | (kN·m) | req (mm²) | Provide | prov (mm²) |
|---|---|---|---|---|
| Along (width ) | 760.1 | 2953 | 16 mm @ 155 c/c | 2983 |
| Along (width ) | 413.3 | 3744 | 16 mm @ 205 c/c | 3825 |
For the rectangular footing, the short-direction steel is placed in a central band of width mm in the proportion (IS 456 cl. 34.3.1), where .
- Central band: mm² → 16 mm @ 160 mm c/c (14 bars).
- Each outer strip (800 mm wide): remaining steel 483 mm² or minimum 0.12% = 768 mm², whichever is more → 16 mm @ 200 mm c/c (4 bars).
Check for one-way shear (at distance from the column face)
- Along side: kN, MPa; , MPa (Table 19). , safe.
- Along side: kN, MPa; , MPa. Safe.
Check for two-way (punching) shear (at from the column face)
- Perimeter mm
- kN (average pressure; the effect of moment transfer is neglected).
- MPa; , MPa. , safe.
Development length
, MPa (M20, deformed bars): 16 mm bars → mm; 16 mm bars → mm. Available length from column face (less 50 mm end cover): 1650 mm along , 925 mm along . Satisfied in both directions.
Bearing stress and transfer of load from column
Column area m². Bearing stress MPa. Permissible bearing stress: column concrete MPa; footing concrete with gives up to 18.00 MPa. The lesser, 9.00 MPa, governs. Capacity of bearing = 1575 kN kN, so the excess 425 kN must be carried by dowels: mm²; the column bars (8-20 mm, 2513 mm²) are continued into the footing as dowels - adequate. Dowel length in compression mm (and the same lap with the column bars). Available depth in footing = 800 - 50 - 32 = 718 mm ; dowels are bent at the bottom with 90° bends.
Detailing
PLAN ELEVATION
+------------------+ col
| # # # # # # | | |
| # +------+ # # | _|_|__
| # | col | # # | |_____| <- D = 800 mm
| # +------+ # # | bars both ways
| # # # # # # |
+------------------+
L = 3.9 m, B = 2.3 m
- Bottom mesh: 16 mm @ 155 c/c along (lower layer), 16 mm @ 205 c/c along (upper layer), 50 mm clear cover; dowels 8-20 mm.
Answer: Footing 3.9 m × 2.3 m × 800 mm thick; 16 mm @ 155 c/c along the length and 16 mm @ 205 c/c along the width.
- 2068 Baisakh (old course) · 15 marks
Design a reinforced concrete rectangular footing for a square column of size 450 mm x 450 mm, which is subjected to an axial load of 1650 kN and uni-axial moment of 240 kNm at service state. Consider allowable bearing capacity of soil as 120 kN/m. Show design summary and reinforcement detailing with neat sketch.
Answer
Data and assumptions
- Column 450 mm × 450 mm (long side mm along the footing length); footing concrete M20, steel Fe415; column concrete M20; column bars 8-20 mm.
- Service load kN, service moment kN·m.
- Allowable (safe) bearing capacity of soil = 120 kN/m².
- Materials are not given; M20 and Fe415 are assumed, with 8-20 mm column bars.
- Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth mm (cover + half bar). Load factor 1.5.
Size of footing
Weight of footing and backfill is taken as 10% of the column load.
Eccentricity m, which is less than , so there is no tension under the base. The size is chosen so that
Try m ( m²): kN/m² and kN/m² . Safe.
Factored soil pressure
kN, kN·m. : kN/m², kN/m² (average 140.6 kN/m²). Self-weight does not cause bending in the footing, so it is excluded.
Bending moments and reinforcement
Cantilever projections from the column face: along : mm; along : mm. Along (critical section at the column face on the side of maximum pressure, linear pressure): kN·m. Along (average pressure): kN·m. Required depth for flexure: is far larger than the moment for mm, so the depth is governed by shear (one-way or punching). Trial mm, mm, found by the shear checks below.
; minimum steel = 0.12% of .
| Direction | (kN·m) | req (mm²) | Provide | prov (mm²) |
|---|---|---|---|---|
| Along (width ) | 1522.8 | 5599 | 20 mm @ 175 c/c | 5745 |
| Along (width ) | 731.1 | 5610 | 16 mm @ 195 c/c | 5671 |
For the rectangular footing, the short-direction steel is placed in a central band of width mm in the proportion (IS 456 cl. 34.3.1), where .
- Central band: mm² → 16 mm @ 150 mm c/c (21 bars).
- Each outer strip (1150 mm wide): remaining steel 742 mm² or minimum 0.12% = 1173 mm², whichever is more → 16 mm @ 190 mm c/c (6 bars).
Check for one-way shear (at distance from the column face)
- Along side: kN, MPa; , MPa (Table 19). , safe.
- Along side: kN, MPa; , MPa. Safe.
Check for two-way (punching) shear (at from the column face)
- Perimeter mm
- kN (average pressure; the effect of moment transfer is neglected).
- MPa; , MPa. , safe.
Development length
, MPa (M20, deformed bars): 20 mm bars → mm; 16 mm bars → mm. Available length from column face (less 50 mm end cover): 2475 mm along , 1325 mm along . Satisfied in both directions.
Bearing stress and transfer of load from column
Column area m². Bearing stress MPa. Permissible bearing stress: column concrete MPa; footing concrete with gives up to 18.00 MPa. The lesser, 9.00 MPa, governs. Capacity of bearing = 1822 kN kN, so the excess 652 kN must be carried by dowels: mm²; the column bars (8-20 mm, 2513 mm²) are continued into the footing as dowels - adequate. Dowel length in compression mm (and the same lap with the column bars). Available depth in footing = 850 - 50 - 36 = 764 mm , adequate.
Detailing
PLAN ELEVATION
+------------------+ col
| # # # # # # | | |
| # +------+ # # | _|_|__
| # | col | # # | |_____| <- D = 850 mm
| # +------+ # # | bars both ways
| # # # # # # |
+------------------+
L = 5.5 m, B = 3.2 m
- Bottom mesh: 20 mm @ 175 c/c along (lower layer), 16 mm @ 195 c/c along (upper layer), 50 mm clear cover; dowels 8-20 mm.
Answer: Footing 5.5 m × 3.2 m × 850 mm thick; 20 mm @ 175 c/c along the length and 16 mm @ 195 c/c along the width.
- 2065 Kartik (old course) · 12 marks
Design a RC concrete spread footing of an RC wall having 4 m length and 300 mm width. Total load on wall is equal to 1000 kN at service state. Take M20 and Fe415 grades of concrete and steel respectively, and safe bearing capacity of soil = 150 kN/m.
Answer
Data and assumptions
- Wall 300 mm thick and 4 m long carrying a total service load of 1000 kN, so the load per metre run kN/m. M20 concrete, Fe415 steel, kN/m². The footing is designed for a 1 m length of wall. Cover 50 mm.
Width of footing
(10% added for weight of the footing and backfill.)
Factored pressure and bending moment
kN/m, kN/m² Projection beyond the wall face mm.
Depth
Depth by one-way shear at from the wall face (checked below); trial mm, mm. Flexure check: kN·m kN·m, so the section is under-reinforced.
Reinforcement
mm²/m from (minimum 0.12% of = 450 mm²/m). Adopt 548 mm²/m → provide 10 mm @ 140 mm c/c across the width (561 mm²/m, ). Distribution steel along the wall (0.12% of ) = 450 mm²/m → 8 mm @ 110 mm c/c.
Check for shear
kN/m; MPa < MPa (M20, ). Safe.
Development length
mm; available length mm. Satisfied.
Detailing
SECTION ACROSS WALL
| wall 300 |
| |
_____| |_____
| | D = 375 mm
|_______________________|
o o o o o o o o o o o o <- 10 mm @ 140 c/c
<---------- 1.85 m ------->
Distribution bars 8 mm @ 110 mm c/c are tied above the main bars, parallel to the wall.
Answer: Strip footing 1.85 m wide and 375 mm thick; main bars 10 mm @ 140 mm c/c across the wall, distribution bars 8 mm @ 110 mm c/c.
Questions from Old Question Collection (CE 702) (IOE exam papers from 2065 to 2082 (CE 702, BCE IV/I)) and Old Question Collection (CE 702) (4 IOE papers 2075 to 2079 (only 2079 Baisakh not already in the other file)). Answers are written for this site; check them against your class notes.
Chapter titles and hours from the IOE syllabus ↗