- 2068 Baisakh (old course) · 15 marks
Rectangular footing, 450x450, uniaxial moment 240 kNm
Short answer
Rectangular footing 5.5 m × 3.2 m, depth 850 mm (effective 790 mm). Longitudinal reinforcement: 20 mm @ 170 mm c/c; transverse: 16 mm @ 195 mm c/c with central band of 16 mm @ 150 mm c/c per IS 456.
Design a reinforced concrete rectangular footing for a square column of size 450 mm x 450 mm, which is subjected to an axial load of 1650 kN and uni-axial moment of 240 kNm at service state. Consider allowable bearing capacity of soil as 120 kN/m. Show design summary and reinforcement detailing with neat sketch.
Data and assumptions
- Column 450 mm × 450 mm (long side mm along the footing length); footing concrete M20, steel Fe415; column concrete M20; column bars 8-20 mm.
- Service load kN, service moment kN·m.
- Allowable (safe) bearing capacity of soil = 120 kN/m².
- Materials are not given; M20 and Fe415 are assumed, with 8-20 mm column bars.
- Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth mm (cover + half bar). Load factor 1.5.
Size of footing
Weight of footing and backfill is taken as 10% of the column load.
Eccentricity m, which is less than , so there is no tension under the base. The size is chosen so that
Try m ( m²): kN/m² and kN/m² . Safe.
Factored soil pressure
kN, kN·m. : kN/m², kN/m² (average 140.6 kN/m²). Self-weight does not cause bending in the footing, so it is excluded.
Bending moments and reinforcement
Cantilever projections from the column face: along : mm; along : mm. Along (critical section at the column face on the side of maximum pressure, linear pressure): , with kN/m² at the face and m: kN·m. Along (average pressure): kN·m. Required depth for flexure: is far larger than the moment for mm, so the depth is governed by shear (one-way or punching). Trial mm, mm, found by the shear checks below.
; minimum steel = 0.12% of .
| Direction | (kN·m) | req (mm²) | Provide | prov (mm²) |
|---|---|---|---|---|
| Along (width ) | 1592.5 | 5869 | 20 mm @ 170 c/c | 5914 |
| Along (width ) | 731.1 | 5610 | 16 mm @ 195 c/c | 5671 |
For the rectangular footing, the short-direction steel is placed in a central band of width mm in the proportion (IS 456 cl. 34.3.1), where .
- Central band: mm² → 16 mm @ 150 mm c/c (21 bars).
- Each outer strip (1150 mm wide): remaining steel 742 mm² or minimum 0.12% = 1173 mm², whichever is more → 16 mm @ 190 mm c/c (6 bars).
Check for one-way shear (at distance from the column face)
- Along side: kN, MPa; , MPa (IS 456 Table 19, SP 16 formula). , safe.
- Along side: kN, MPa; , MPa. Safe.
Check for two-way (punching) shear (at from the column face)
- Perimeter mm
- kN (average pressure; the effect of moment transfer is neglected).
- MPa; , MPa. , safe.
Development length
, MPa (M20, deformed bars): 20 mm bars → mm; 16 mm bars → mm. Available length from column face (less 50 mm end cover): 2475 mm along , 1325 mm along . Satisfied in both directions.
Bearing stress and transfer of load from column
Column area m². Bearing stress MPa. Permissible bearing stress: column concrete MPa; footing concrete with gives up to 18.00 MPa. The lesser, 9.00 MPa, governs. Capacity of bearing = 1822 kN kN, so the excess 652 kN must be carried by dowels: mm²; the column bars (8-20 mm, 2513 mm²) are continued into the footing as dowels, which is adequate. Dowel length in compression mm (and the same lap with the column bars). Available depth in footing = 850 - 50 - 36 = 764 mm , adequate.
Detailing
PLAN ELEVATION
+------------------+ col
| # # # # # # | | |
| # +------+ # # | _|_|__
| # | col | # # | |_____| <- D = 850 mm
| # +------+ # # | bars both ways
| # # # # # # |
+------------------+
L = 5.5 m, B = 3.2 m
- Bottom mesh: 20 mm @ 170 c/c along (lower layer); along (upper layer), 16 mm @ 150 c/c in the central 3.2 m band and 16 mm @ 190 c/c in each outer strip, 50 mm clear cover; dowels 8-20 mm.
Answer: Footing 5.5 m × 3.2 m × 850 mm thick; 20 mm @ 170 c/c along the length; along the width, 16 mm @ 150 c/c in the central 3.2 m band and 16 mm @ 190 c/c in the outer strips.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Isolated footing 450x450, service moment 110 kNm · Design of RCC Structure, chapter 11 · asked 2×
- Isolated square footing, 600 kN and 50 kNm · Design of RCC Structure, chapter 11 · asked 2×
- Footing, 450x500 column, 6#20, uniaxial moment · Design of RCC Structure, chapter 11
- Isolated footing 400x400, service moment 120 kNm · Design of RCC Structure, chapter 11 · asked 2×
- Isolated footing 450x450, 1600 kN service · Design of RCC Structure, chapter 11
- Isolated square footing, 650 kN service · Design of RCC Structure, chapter 11 · asked 2×
- Brick column design for 80 kN axial load · Concrete Technology and Masonry Structure, chapter 8
- Rectangular Sal column, 150 kN + 15 kNm · Design of Steel and Timber Structure, chapter 11
- Square footing size in clay, 750 kN · Foundation Engineering, chapter 6
- Rectangular footing size, 6000 kN · Foundation Engineering, chapter 6