Footing, 450x500 column, 6#20, uniaxial moment
Short answer
Provide a 4.1 m × 2.3 m footing, 650 mm deep. Along the 4.1 m side, use 12 mm bars @ 130 mm c/c; along the 2.3 m side, place a central band of 21 bars (12 mm @ 105 mm c/c) and outer strips of 7 bars each (12 mm @ 125 mm c/c).
Design an isolated footing for a 450 mm x 500 mm sized column, with 6#20 mm diameter bars. Carrying factored axial load of 1100 kN and factored uniaxial moment of 120 kN-m at the column base. Take the depth of footing 1.5 m and safe bearing capacity of soil 100 kN/m. Use M20 concrete and Fe500 grade steel.
Data and assumptions
- Column 500 mm × 450 mm (long side mm along the footing length); footing concrete M20, steel Fe500; column concrete M20; column bars 6-20 mm.
- Given loads are factored: kN, kN·m. Service loads = factored / 1.5: kN, kN·m.
- Allowable (safe) bearing capacity of soil = 100 kN/m² at 1.5 m depth.
- Column concrete grade assumed M20 (same as footing). Moment acts about the minor axis so that it varies the pressure along the 500 mm side.
- Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth mm (cover + half bar). Load factor 1.5.
Size of footing
Weight of footing and backfill is taken as 10% of the column load.
Eccentricity m, which is less than , so there is no tension under the base. The size is chosen so that
Try m ( m²): kN/m² and kN/m² . Safe.
Factored soil pressure
kN, kN·m. : kN/m², kN/m² (average 116.6 kN/m²). Self-weight does not cause bending in the footing, so it is excluded.
Bending moments and reinforcement
Cantilever projections from the column face: along : mm; along : mm. Along (critical section at the column face on the side of maximum pressure, linear pressure): , with kN/m² at the face and m: kN·m. Along (average pressure): kN·m. Required depth for flexure: is far larger than the moment for mm, so the depth is governed by shear (one-way or punching). Trial mm, mm, found by the shear checks below.
; minimum steel = 0.12% of .
| Direction | (kN·m) | req (mm²) | Provide | prov (mm²) |
|---|---|---|---|---|
| Along (width ) | 483.7 | 1956 | 12 mm @ 130 c/c | 2001 |
| Along (width ) | 204.6 | 3198 | 12 mm @ 140 c/c | 3312 |
For the rectangular footing, the short-direction steel is placed in a central band of width mm in the proportion (IS 456 cl. 34.3.1), where .
- Central band: mm² → 12 mm @ 105 mm c/c (21 bars).
- Each outer strip (900 mm wide): remaining steel 450 mm² or minimum 0.12% = 702 mm², whichever is more → 12 mm @ 125 mm c/c (7 bars).
Check for one-way shear (at distance from the column face)
- Along side: kN, MPa; , MPa (IS 456 Table 19, SP 16 formula). , safe.
- Along side: kN, MPa; , MPa. Safe.
Check for two-way (punching) shear (at from the column face)
- Perimeter mm
- kN (average pressure; the effect of moment transfer is neglected).
- MPa; , MPa. , safe.
Development length
, MPa (M20, deformed bars): 12 mm bars (both directions) → mm. Available length from column face (less 50 mm end cover): 1750 mm along , 875 mm along . Satisfied in both directions.
Bearing stress and transfer of load from column
Column area m². Bearing stress MPa. Permissible bearing stress: column concrete MPa; footing concrete with gives up to 18.00 MPa. The lesser, 9.00 MPa, governs. Capacity of bearing = 2025 kN kN, so the whole load can be transferred by bearing. Provide minimum dowels of 0.5% of column area = 1125 mm²: use 6 bars of 20 mm (1885 mm²) as dowels, same as column bars. Dowel length in compression mm (and the same lap with the column bars). Available depth in footing = 650 - 50 - 24 = 576 mm ; dowels are bent at the bottom with 90° bends.
Detailing
PLAN ELEVATION
+------------------+ col
| # # # # # # | | |
| # +------+ # # | _|_|__
| # | col | # # | |_____| <- D = 650 mm
| # +------+ # # | bars both ways
| # # # # # # |
+------------------+
L = 4.1 m, B = 2.3 m
- Bottom mesh: 12 mm @ 130 c/c along (lower layer); along (upper layer), 12 mm @ 105 c/c in the central 2.3 m band and 12 mm @ 125 c/c in each outer strip, 50 mm clear cover; dowels 6-20 mm.
Answer: Footing 4.1 m × 2.3 m × 650 mm thick; 12 mm @ 130 c/c along the length; along the width, 12 mm @ 105 c/c in the central 2.3 m band and 12 mm @ 125 c/c in the outer strips.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Footing 300x400 column, factored moment 120 kNm · Design of RCC Structure, chapter 11
- Footing 350x350, 8-16 mm bars, reversible moment · Design of RCC Structure, chapter 11
- Isolated footing 400x400, service moment 120 kNm · Design of RCC Structure, chapter 11 · asked 2×
- Footing, 1250 kN column load, depth 1.8 m · Design of RCC Structure, chapter 11
- Isolated footing 450x450, service moment 110 kNm · Design of RCC Structure, chapter 11 · asked 2×
- Isolated footing 450x450, 1600 kN service · Design of RCC Structure, chapter 11
- Brick column design for 80 kN axial load · Concrete Technology and Masonry Structure, chapter 8
- Base plate for ISHB 450, 1400 kN · Design of Steel and Timber Structure, chapter 6 · asked 2×
- Built-up column, lacing, 8 m, 1100 kN · Design of Steel and Timber Structure, chapter 6 · asked 4×
- Timber column under axial load and bending · Design of Timber and Masonry Structures, chapter 3