Footing, 450x500 column, 6#20, uniaxial moment

Short answer

Provide a 4.1 m × 2.3 m footing, 650 mm deep. Along the 4.1 m side, use 12 mm bars @ 130 mm c/c; along the 2.3 m side, place a central band of 21 bars (12 mm @ 105 mm c/c) and outer strips of 7 bars each (12 mm @ 125 mm c/c).

Design an isolated footing for a 450 mm x 500 mm sized column, with 6#20 mm diameter bars. Carrying factored axial load of 1100 kN and factored uniaxial moment of 120 kN-m at the column base. Take the depth of footing 1.5 m and safe bearing capacity of soil 100 kN/m2^2. Use M20 concrete and Fe500 grade steel.

Data and assumptions

  • Column 500 mm × 450 mm (long side a=500a=500 mm along the footing length); footing concrete M20, steel Fe500; column concrete M20; column bars 6-20 mm.
  • Given loads are factored: Pu=1100P_u = 1100 kN, Mu=120M_u = 120 kN·m. Service loads = factored / 1.5: P=733.3P = 733.3 kN, M=80.0M = 80.0 kN·m.
  • Allowable (safe) bearing capacity of soil = 100 kN/m² at 1.5 m depth.
  • Column concrete grade assumed M20 (same as footing). Moment acts about the minor axis so that it varies the pressure along the 500 mm side.
  • Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth d=D−60d = D - 60 mm (cover + half bar). Load factor 1.5.

Size of footing

Weight of footing and backfill is taken as 10% of the column load.

Areq=1.1 Pqa=1.1×733.3100=8.07 m2A_{req} = \frac{1.1\,P}{q_a} = \frac{1.1 \times 733.3}{100} = 8.07\ \text{m}^2

Eccentricity e=M/P=80.0/733.3=0.109e = M/P = 80.0/733.3 = 0.109 m, which is less than L/6L/6, so there is no tension under the base. The size is chosen so that

qmax=1.1PBL(1+6eL)≤qaq_{max} = 1.1\frac{P}{BL}\left(1 + \frac{6e}{L}\right) \le q_a

Try L×B=4.1×2.3L \times B = 4.1 \times 2.3 m (A=9.43A = 9.43 m²): qmax=99.2q_{max} = 99.2 kN/m² ≤100.0\le 100.0 and qmin=71.9q_{min} = 71.9 kN/m² >0> 0. Safe.

Factored soil pressure

Pu=1.5×733.3=1100.0P_u = 1.5 \times 733.3 = 1100.0 kN, Mu=120.0M_u = 120.0 kN·m. pu=PuBL(1±6eL)p_u = \dfrac{P_u}{BL}\left(1 \pm \dfrac{6e}{L}\right): pu,max=135.3p_{u,max} = 135.3 kN/m², pu,min=98.0p_{u,min} = 98.0 kN/m² (average 116.6 kN/m²). Self-weight does not cause bending in the footing, so it is excluded.

Bending moments and reinforcement

Cantilever projections from the column face: along LL: (4100−500)/2=1800(4100 - 500)/2 = 1800 mm; along BB: (2300−450)/2=925(2300 - 450)/2 = 925 mm. Along LL (critical section at the column face on the side of maximum pressure, linear pressure): Mu,L=B[pfx22+(pmax−pf)x23]M_{u,L} = B\left[p_f\dfrac{x^2}{2} + (p_{max}-p_f)\dfrac{x^2}{3}\right], with pf=118.9p_f = 118.9 kN/m² at the face and x=1.8x = 1.8 m: Mu,L=483.7M_{u,L} = 483.7 kN·m. Along BB (average pressure): Mu,B=204.6M_{u,B} = 204.6 kN·m. Required depth for flexure: Mu,lim=0.133fckbd2M_{u,lim} = 0.133 f_{ck} b d^2 is far larger than the moment for d=590d = 590 mm, so the depth is governed by shear (one-way or punching). Trial D=650D = 650 mm, d=590d = 590 mm, found by the shear checks below.

Ast=0.5fckfy[1−1−4.6Mufckbd2]bdA_{st} = \dfrac{0.5 f_{ck}}{f_y}\left[1 - \sqrt{1 - \dfrac{4.6 M_u}{f_{ck} b d^2}}\right] b d; minimum steel = 0.12% of bDbD.

DirectionMuM_u (kN·m)AstA_{st} req (mm²)ProvideAstA_{st} prov (mm²)
Along LL (width BB)483.7195612 mm @ 130 c/c2001
Along BB (width LL)204.6319812 mm @ 140 c/c3312

For the rectangular footing, the short-direction steel is placed in a central band of width B=2300B = 2300 mm in the proportion 2β+1=21.78+1=0.719\dfrac{2}{\beta+1} = \dfrac{2}{1.78+1} = 0.719 (IS 456 cl. 34.3.1), where β=L/B\beta = L/B.

  • Central band: 0.719×3198=22990.719 \times 3198 = 2299 mm² → 12 mm @ 105 mm c/c (21 bars).
  • Each outer strip (900 mm wide): remaining steel 450 mm² or minimum 0.12% = 702 mm², whichever is more → 12 mm @ 125 mm c/c (7 bars).

Check for one-way shear (at distance dd from the column face)

  • Along LL side: Vu=361.2V_u = 361.2 kN, τv=VuBd=0.266\tau_v = \dfrac{V_u}{B d} = 0.266 MPa; pt=0.147%p_t = 0.147\%, τc=0.288\tau_c = 0.288 MPa (IS 456 Table 19, SP 16 formula). τv<τc\tau_v < \tau_c, safe.
  • Along BB side: Vu=160.2V_u = 160.2 kN, τv=0.066\tau_v = 0.066 MPa; pt=0.137%p_t = 0.137\%, τc=0.288\tau_c = 0.288 MPa. Safe.

Check for two-way (punching) shear (at d/2d/2 from the column face)

  • Perimeter bo=2[(a+d)+(c+d)]=2[(500+590)+(450+590)]=4260b_o = 2[(a + d) + (c + d)] = 2[(500+590) + (450+590)] = 4260 mm
  • Vu=Pu−pu(a+d)(c+d)=1100.0−116.6×1.090×1.040=967.8V_u = P_u - p_u (a+d)(c+d) = 1100.0 - 116.6 \times 1.090 \times 1.040 = 967.8 kN (average pressure; the effect of moment transfer is neglected).
  • τv=Vubod=0.385\tau_v = \dfrac{V_u}{b_o d} = 0.385 MPa; ks=0.5+βc=1.00k_s = 0.5 + \beta_c = 1.00, τc′=ks×0.25fck=1.118\tau_c' = k_s \times 0.25\sqrt{f_{ck}} = 1.118 MPa. τv<τc′\tau_v < \tau_c', safe.

Development length

Ld=0.87fyϕ4τbdL_d = \dfrac{0.87 f_y \phi}{4\tau_{bd}}, τbd=1.92\tau_{bd} = 1.92 MPa (M20, deformed bars): 12 mm bars (both directions) → Ld=680L_d = 680 mm. Available length from column face (less 50 mm end cover): 1750 mm along LL, 875 mm along BB. Satisfied in both directions.

Bearing stress and transfer of load from column

Column area A2=500×450=0.225A_2 = 500\times450 = 0.225 m². Bearing stress =Pu/A2=4.89= P_u/A_2 = 4.89 MPa. Permissible bearing stress: column concrete 0.45fck=9.000.45 f_{ck} = 9.00 MPa; footing concrete 0.45fckA1/A20.45 f_{ck}\sqrt{A_1/A_2} with A1/A2≤2\sqrt{A_1/A_2} \le 2 gives up to 18.00 MPa. The lesser, 9.00 MPa, governs. Capacity of bearing = 2025 kN ≥\ge Pu=1100P_u = 1100 kN, so the whole load can be transferred by bearing. Provide minimum dowels of 0.5% of column area = 1125 mm²: use 6 bars of 20 mm (1885 mm²) as dowels, same as column bars. Dowel length in compression Ldc=0.87fyϕ4×1.25 τbd=906L_{dc} = \dfrac{0.87 f_y\phi}{4 \times 1.25\,\tau_{bd}} = 906 mm (and the same lap with the column bars). Available depth in footing = 650 - 50 - 24 = 576 mm <Ldc< L_{dc}; dowels are bent at the bottom with 90° bends.

Detailing

PLAN                      ELEVATION
+------------------+      col
| #  #  #  #  #  # |      | |
| #  +------+  #  # |     _|_|__
| #  | col  |  #  # |    |_____|  <- D = 650 mm
| #  +------+  #  # |    bars both ways
| #  #  #  #  #  # |
+------------------+
 L = 4.1 m, B = 2.3 m
  • Bottom mesh: 12 mm @ 130 c/c along LL (lower layer); along BB (upper layer), 12 mm @ 105 c/c in the central 2.3 m band and 12 mm @ 125 c/c in each outer strip, 50 mm clear cover; dowels 6-20 mm.

Answer: Footing 4.1 m × 2.3 m × 650 mm thick; 12 mm @ 130 c/c along the length; along the width, 12 mm @ 105 c/c in the central 2.3 m band and 12 mm @ 125 c/c in the outer strips.

✓ Answer checked by Claude Opus 5.5 (high effort)