Isolated footing 400x400, service moment 120 kNm
Short answer
Adopt a 4.2 m x 2.4 m footing, overall depth 800 mm (d=740 mm). Long-direction reinforcement: 16 mm bars @140 mm c/c; short-direction: central band 16 mm @160 mm c/c and outer strips 16 mm @180 mm c/c. One-way and punching shear checks are satisfied.
Design an isolated footing for a column of size 400 mm x 400 mm with 8-25 mm diameter bars as longitudinal reinforcement in order to carry a service axial load of 1200 kN and service moment of 120 kNm. Take the safe bearing capacity of soil as 150 kN/m. Use M20 concrete and Fe 415 steel.
Data and assumptions
- Column 400 mm × 400 mm (long side mm along the footing length); footing concrete M20, steel Fe415; column concrete M20; column bars 8-25 mm.
- Service load kN, service moment kN·m.
- Allowable (safe) bearing capacity of soil = 150 kN/m².
- Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth mm (cover + half bar). Load factor 1.5.
Size of footing
Weight of footing and backfill is taken as 10% of the column load.
Eccentricity m, which is less than , so there is no tension under the base. The size is chosen so that
Try m ( m²): kN/m² and kN/m² . Safe.
Factored soil pressure
kN, kN·m. : kN/m², kN/m² (average 178.6 kN/m²). Self-weight does not cause bending in the footing, so it is excluded.
Bending moments and reinforcement
Cantilever projections from the column face: along : mm; along : mm. Along (critical section at the column face on the side of maximum pressure): the pressure is 181.0 kN/m² at the face and 204.1 kN/m² at the edge, so per metre width kN·m/m, and kN·m. Along (average pressure): kN·m. Required depth for flexure: is far larger than the moment for mm, so the depth is governed by shear (one-way or punching). Trial mm, mm, found by the shear checks below.
; minimum steel = 0.12% of .
| Direction | (kN·m) | req (mm²) | Provide | prov (mm²) |
|---|---|---|---|---|
| Along (width ) | 850.8 | 3315 | 16 mm @ 140 c/c | 3447 |
| Along (width ) | 375.0 | 4032 (minimum) | 16 mm, banded (below) | 5027 |
For the rectangular footing, the short-direction steel is placed in a central band of width mm in the proportion (IS 456 cl. 34.3.1), where .
- Central band: mm² → 16 mm @ 160 mm c/c (15 bars, 3016 mm²).
- Each outer strip (900 mm wide): remaining steel 550 mm² or minimum 0.12% = 864 mm², whichever is more → 16 mm @ 180 mm c/c (5 bars, 1005 mm²).
Check for one-way shear (at distance from the column face)
- Along side: kN, MPa; , MPa (Table 19). , safe.
- Along side: kN, MPa; , MPa. Safe.
Check for two-way (punching) shear (at from the column face)
- Perimeter mm
- kN (average pressure; the effect of moment transfer is neglected).
- MPa; , MPa. , safe.
Development length
, MPa (M20, deformed bars): 16 mm bars (both directions) → mm. Available length from column face (less 50 mm end cover): 1850 mm along , 950 mm along . Satisfied in both directions.
Bearing stress and transfer of load from column
Column area m². Bearing stress MPa. Permissible bearing stress: column concrete MPa; footing concrete with gives up to 18.00 MPa. The lesser, 9.00 MPa, governs. Capacity of bearing = 1440 kN kN, so the excess 360 kN must be carried by dowels: mm²; the column bars (8-25 mm, 3927 mm²) are continued into the footing as dowels - adequate. Dowel length in compression mm (and the same lap with the column bars). Available depth in footing = 800 - 50 - 32 = 718 mm ; dowels are bent at the bottom with 90° bends.
Detailing
PLAN (4.2 m x 2.4 m; L horizontal)
+--------------------------------------------+
| | | | | | | | | | | | |
|--+---+---+---+---+---+---+---+---+---+---+-|
| | | | | | | | | | | | |
|--+---+---+---+-+----------+--+---+---+---+-|
| | | | | | column | | | | | |
|--+---+---+---+-+----------+--+---+---+---+-|
| | | | | | | | | | | | |
|--+---+---+---+---+---+---+---+---+---+---+-|
| | | | | | | | | | | | |
+--------------------------------------------+
<-0.9 m-><---central band 2.4 m---><-0.9 m->
- = 16 mm @ 140 c/c (along L)
| = 16 mm along B: @ 160 c/c in central band, @ 180 c/c in outer strips
ELEVATION
| column |
| |
+----------------+----------+----------------+
| (dowels) | D = 800 mm
| o o o o o o o o o o o o o o | bottom mesh, 50 mm cover
+--------------------------------------------+
<----------------- 4200 mm ------------------>
- Bottom mesh: 16 mm @ 140 c/c along (lower layer); along (upper layer), 16 mm @ 160 c/c in the central 2.4 m band and 16 mm @ 180 c/c in each 0.9 m outer strip; 50 mm clear cover; dowels 8-25 mm.
Answer: Footing 4.2 m × 2.4 m × 800 mm thick; 16 mm @ 140 c/c along the length; along the width, 16 mm @ 160 c/c in the central 2.4 m band and 16 mm @ 180 c/c in the outer strips.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Isolated footing 450x450, service moment 110 kNm · Design of RCC Structure, chapter 11 · asked 2×
- Isolated footing 400x400, 1200 kN service · Design of RCC Structure, chapter 11
- Footing 300x400 column, factored moment 120 kNm · Design of RCC Structure, chapter 11
- Isolated square footing, 600 kN and 50 kNm · Design of RCC Structure, chapter 11 · asked 2×
- Isolated footing 450x450, 1600 kN service · Design of RCC Structure, chapter 11
- Isolated square footing, 650 kN service · Design of RCC Structure, chapter 11 · asked 2×
- Footing 350x350, 8-16 mm bars, reversible moment · Design of RCC Structure, chapter 11
- Brick column design for 80 kN axial load · Concrete Technology and Masonry Structure, chapter 8
- Check 25 cm x 25 cm Sal column, 200 kN + 20 kNm · Design of Steel and Timber Structure, chapter 11
- Footing size from plate load test curve · Foundation Engineering, chapter 6
- Built-up column with battens, 6 m, 1200 kN · Design of Steel and Timber Structure, chapter 6