- Asked 2/25
- 2067 Asar (old course) · 10 marks
Isolated square footing, 600 kN and 50 kNm
Short answer
Square footing 2.4 m × 2.4 m, depth 450 mm (effective 390 mm). Reinforcement along moment direction: 12 mm @ 170 mm c/c, other direction: 12 mm @ 195 mm c/c; shear checks satisfactory.
Design an isolated square footing foundation of uniform thickness for a 400 mm x 400 mm column subjected to an axial load of 600 kN and a moment of 50 kNm at service state. Consider bearing capacity of soil as 150 kN/m and concrete grade M20 and steel grade Fe415.
Data and assumptions
- Column 400 mm × 400 mm ( mm); footing and column concrete M20, steel Fe415; column bars assumed 8-16 mm.
- Service load kN, service moment kN·m.
- Allowable (safe) bearing capacity of soil = 150 kN/m².
- Square footing, as required by the question.
- Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth mm (cover + half bar). Load factor 1.5.
Size of footing
The weight of the footing and backfill is taken as 10% of the column load.
Eccentricity m, which is less than , so there is no tension under the base. The size is chosen so that
Try m ( m²): kN/m² and kN/m² . Safe.
Factored soil pressure
kN, kN·m. : kN/m², kN/m² (average 156.2 kN/m²). Self-weight does not cause bending in the footing, so it is excluded.
Bending moments and reinforcement
Cantilever projections from the column face: along : mm; along : mm.
Along (critical section at the column face on the side of maximum pressure, linearly varying pressure): pressure at the column face kN/m², so
Along (average pressure): kN·m.
Required depth for flexure: kN·m for mm, far larger than the moments, so the depth is governed by shear (one-way or punching). Trial mm, mm, confirmed by the shear checks below.
; minimum steel = 0.12% of = 1296 mm².
| Direction | (kN·m) | req (mm²) | Provide | prov (mm²) |
|---|---|---|---|---|
| Along (width ) | 215.7 | 1589 | 12 mm @ 170 c/c | 1597 |
| Along (width ) | 187.5 | 1374 | 12 mm @ 195 c/c | 1392 |
Check for one-way shear (at distance from the column face)
- Along side: kN, MPa; , MPa (Table 19). , safe.
- Along side: kN, MPa; , MPa (lowest tabulated value, for ). Safe.
Check for two-way (punching) shear (at from the column face)
- Perimeter mm
- kN (average pressure; the effect of moment transfer is neglected).
- MPa; , limited to ; MPa. , safe.
Development length
, MPa (M20, deformed bars): for 12 mm bars in both directions, mm. Available length from the column face (less 50 mm end cover): 950 mm along and 950 mm along . Satisfied in both directions.
Bearing stress and transfer of load from column
Column area m². Bearing stress MPa. Permissible bearing stress: column concrete MPa; footing concrete with gives up to 18.00 MPa. The lesser, 9.00 MPa, governs. Bearing capacity = 1440 kN kN, so the whole load can be transferred by bearing. Provide minimum dowels of 0.5% of the column area = 800 mm²: use 8 bars of 16 mm (1608 mm²) as dowels, the same as the column bars. Dowel length in compression mm (and the same lap with the column bars). Available depth in the footing = 450 - 50 - 24 = 376 mm ; the dowels are bent at the bottom with 90° bends. (Bends do not count in compression, but this is acceptable here because the dowels are nominal: bearing alone transfers the load.)
Detailing
PLAN ELEVATION
+------------------+ col
| # # # # # # | | |
| # +------+ # # | _|_|__
| # | col | # # | |_____| <- D = 450 mm
| # +------+ # # | bars both ways
| # # # # # # |
+------------------+
L = 2.4 m, B = 2.4 m
- Bottom mesh: 12 mm @ 170 c/c along (lower layer), 12 mm @ 195 c/c along (upper layer), 50 mm clear cover; dowels 8-16 mm.
Answer: Footing 2.4 m × 2.4 m × 450 mm thick; 12 mm @ 170 c/c along the length and 12 mm @ 195 c/c along the width.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Isolated square footing, 650 kN service · Design of RCC Structure, chapter 11 · asked 2×
- Isolated footing 400x400, service moment 120 kNm · Design of RCC Structure, chapter 11 · asked 2×
- Isolated footing 450x450, service moment 110 kNm · Design of RCC Structure, chapter 11 · asked 2×
- Isolated footing 450x450, 1600 kN service · Design of RCC Structure, chapter 11
- Footing 300x400 column, factored moment 120 kNm · Design of RCC Structure, chapter 11
- Rectangular footing, 450x450, uniaxial moment 240 kNm · Design of RCC Structure, chapter 11
- Isolated footing 400x400, 1200 kN service · Design of RCC Structure, chapter 11
- Rectangular Sal column, 150 kN + 15 kNm · Design of Steel and Timber Structure, chapter 11
- Brick column design for 80 kN axial load · Concrete Technology and Masonry Structure, chapter 8
- Solid Sal column, 500 kN + 50 kNm, 2 m · Design of Steel and Timber Structure, chapter 11
- Allowable load of 400 mm pile, layered soil · Foundation Engineering, chapter 8