Isolated footing 450x450, service moment 110 kNm

Short answer

Use a 4.0 m x 2.3 m footing, overall depth 700 mm (d=640 mm). Provide 16 mm bars @150 mm c/c along the longer direction; in the short direction, place a central band of 12 mm bars @100 mm c/c and outer strips of 12 mm @120 mm c/c. One-way and two-way shear are safe.

Design an isolated footing for a column of size 450 mm x 450 mm with 8-20 mm diameter bars as longitudinal reinforcement in order to carry a service axial load of 1000 kN and service moment of 110 kNm. Take the safe bearing capacity of soil as 140 kN/m2^2. Use M20 concrete and Fe 415 steel.

Data and assumptions

  • Column 450 mm × 450 mm (long side a=450a=450 mm along the footing length); footing concrete M20, steel Fe415; column concrete M20; column bars 8-20 mm.
  • Service load P=1000P = 1000 kN, service moment M=110M = 110 kN·m.
  • Allowable (safe) bearing capacity of soil = 140 kN/m².
  • The service moment acts about one axis.
  • Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth d=D−60d = D - 60 mm (cover + half bar). Load factor 1.5.

Size of footing

Weight of footing and backfill is taken as 10% of the column load.

Areq=1.1 Pqa=1.1×1000.0140=7.86 m2A_{req} = \frac{1.1\,P}{q_a} = \frac{1.1 \times 1000.0}{140} = 7.86\ \text{m}^2

Eccentricity e=M/P=110.0/1000.0=0.110e = M/P = 110.0/1000.0 = 0.110 m, which is less than L/6L/6, so there is no tension under the base. The size is chosen so that

qmax=1.1PBL(1+6eL)≤qaq_{max} = 1.1\frac{P}{BL}\left(1 + \frac{6e}{L}\right) \le q_a

Try L×B=4.0×2.3L \times B = 4.0 \times 2.3 m (A=9.20A = 9.20 m²): qmax=139.3q_{max} = 139.3 kN/m² ≤140.0\le 140.0 and qmin=99.8q_{min} = 99.8 kN/m² >0> 0. Safe.

Factored soil pressure

Pu=1.5×1000.0=1500.0P_u = 1.5 \times 1000.0 = 1500.0 kN, Mu=165.0M_u = 165.0 kN·m. pu=PuBL(1±6eL)p_u = \dfrac{P_u}{BL}\left(1 \pm \dfrac{6e}{L}\right): pu,max=189.9p_{u,max} = 189.9 kN/m², pu,min=136.1p_{u,min} = 136.1 kN/m² (average 163.0 kN/m²). Self-weight does not cause bending in the footing, so it is excluded.

Bending moments and reinforcement

Cantilever projections from the column face: along LL: (4000−450)/2=1775(4000 - 450)/2 = 1775 mm; along BB: (2300−450)/2=925(2300 - 450)/2 = 925 mm. Along LL (critical section at the column face on the side of maximum pressure): the pressure is 166.1 kN/m² at the face and 189.9 kN/m² at the edge, so per metre width M=166.1×1.77522+(189.9−166.1)×1.77523=261.6+25.0=286.6M = 166.1 \times \dfrac{1.775^2}{2} + (189.9 - 166.1) \times \dfrac{1.775^2}{3} = 261.6 + 25.0 = 286.6 kN·m/m, and Mu,L=286.6×2.3=659.3M_{u,L} = 286.6 \times 2.3 = 659.3 kN·m. Along BB (average pressure): Mu,B=279.0M_{u,B} = 279.0 kN·m. Required depth for flexure: Mu,lim=0.138fckbd2M_{u,lim} = 0.138 f_{ck} b d^2 is far larger than the moment for d=640d = 640 mm, so the depth is governed by shear (one-way or punching). Trial D=700D = 700 mm, d=640d = 640 mm, found by the shear checks below.

Ast=0.5fckfy[1−1−4.6Mufckbd2]bdA_{st} = \dfrac{0.5 f_{ck}}{f_y}\left[1 - \sqrt{1 - \dfrac{4.6 M_u}{f_{ck} b d^2}}\right] b d; minimum steel = 0.12% of bDbD.

DirectionMuM_u (kN·m)AstA_{st} req (mm²)ProvideAstA_{st} prov (mm²)
Along LL (width BB)659.3298016 mm @ 150 c/c3083
Along BB (width LL)279.03360 (minimum)12 mm, banded (below)4184

For the rectangular footing, the short-direction steel is placed in a central band of width B=2300B = 2300 mm in the proportion 2β+1=21.74+1=0.730\dfrac{2}{\beta+1} = \dfrac{2}{1.74+1} = 0.730 (IS 456 cl. 34.3.1), where β=L/B\beta = L/B.

  • Central band: 0.730×3360=24530.730 \times 3360 = 2453 mm² → 12 mm @ 100 mm c/c (23 bars, 2601 mm²).
  • Each outer strip (850 mm wide): remaining steel 453 mm² or minimum 0.12% = 714 mm², whichever is more → 12 mm @ 120 mm c/c (7 bars, 792 mm²).

Check for one-way shear (at distance dd from the column face)

  • Along LL side: Vu=475.9V_u = 475.9 kN, τv=VuBd=0.323\tau_v = \dfrac{V_u}{B d} = 0.323 MPa; pt=0.209%p_t = 0.209\%, τc=0.327\tau_c = 0.327 MPa (Table 19). τv<τc\tau_v < \tau_c, safe.
  • Along BB side: Vu=185.9V_u = 185.9 kN, τv=0.073\tau_v = 0.073 MPa; pt=0.16%p_t = 0.16\%, τc≈0.29\tau_c \approx 0.29 MPa. Safe.

Check for two-way (punching) shear (at d/2d/2 from the column face)

  • Perimeter bo=2[(a+d)+(c+d)]=2[(450+640)+(450+640)]=4360b_o = 2[(a + d) + (c + d)] = 2[(450+640) + (450+640)] = 4360 mm
  • Vu=Pu−pu(a+d)(c+d)=1500.0−163.0×1.090×1.090=1306.3V_u = P_u - p_u (a+d)(c+d) = 1500.0 - 163.0 \times 1.090 \times 1.090 = 1306.3 kN (average pressure; the effect of moment transfer is neglected).
  • τv=Vubod=0.468\tau_v = \dfrac{V_u}{b_o d} = 0.468 MPa; ks=0.5+βc=1.00k_s = 0.5 + \beta_c = 1.00, τc′=ks×0.25fck=1.118\tau_c' = k_s \times 0.25\sqrt{f_{ck}} = 1.118 MPa. τv<τc′\tau_v < \tau_c', safe.

Development length

Ld=0.87fyϕ4τbdL_d = \dfrac{0.87 f_y \phi}{4\tau_{bd}}, τbd=1.92\tau_{bd} = 1.92 MPa (M20, deformed bars): 16 mm bars → Ld=752L_d = 752 mm; 12 mm bars → 564564 mm. Available length from column face (less 50 mm end cover): 1725 mm along LL, 875 mm along BB. Satisfied in both directions.

Bearing stress and transfer of load from column

Column area A2=450×450=0.203A_2 = 450\times450 = 0.203 m². Bearing stress =Pu/A2=7.41= P_u/A_2 = 7.41 MPa. Permissible bearing stress: column concrete 0.45fck=9.000.45 f_{ck} = 9.00 MPa; footing concrete 0.45fckA1/A20.45 f_{ck}\sqrt{A_1/A_2} with A1/A2≤2\sqrt{A_1/A_2} \le 2 gives up to 18.00 MPa. The lesser, 9.00 MPa, governs. Capacity of bearing = 1822 kN ≥\ge Pu=1500P_u = 1500 kN, so the whole load can be transferred by bearing. Provide minimum dowels of 0.5% of column area = 1012 mm²: use 8 bars of 20 mm (2513 mm²) as dowels, same as column bars. Dowel length in compression Ldc=0.87fyϕ4×1.25 τbd=752L_{dc} = \dfrac{0.87 f_y\phi}{4 \times 1.25\,\tau_{bd}} = 752 mm (and the same lap with the column bars). Available depth in footing = 700 - 50 - 28 = 622 mm <Ldc< L_{dc}; dowels are bent at the bottom with 90° bends.

Detailing

PLAN (4.0 m x 2.3 m; L horizontal)
+--------------------------------------------+
|  |   |   |   |   |   |   |   |   |   |   | |
|--+---+---+---+---+---+---+---+---+---+---+-|
|  |   |   |   |   |   |   |   |   |   |   | |
|--+---+---+---+-+----------+--+---+---+---+-|
|  |   |   |   | |  column  |  |   |   |   | |
|--+---+---+---+-+----------+--+---+---+---+-|
|  |   |   |   |   |   |   |   |   |   |   | |
|--+---+---+---+---+---+---+---+---+---+---+-|
|  |   |   |   |   |   |   |   |   |   |   | |
+--------------------------------------------+
 <-0.85 m><---central band 2.3 m---><-0.85 m>
- = 16 mm @ 150 c/c (along L)
| = 12 mm along B: @ 100 c/c in central band, @ 120 c/c in outer strips

ELEVATION
                 |  column  |
                 |          |
+----------------+----------+----------------+
|                  (dowels)                  |  D = 700 mm
|  o  o  o  o  o  o  o  o  o  o  o  o  o  o  |  bottom mesh, 50 mm cover
+--------------------------------------------+
<----------------- 4000 mm ------------------>
  • Bottom mesh: 16 mm @ 150 c/c along LL (lower layer); along BB (upper layer), 12 mm @ 100 c/c in the central 2.3 m band and 12 mm @ 120 c/c in each 0.85 m outer strip; 50 mm clear cover; dowels 8-20 mm.

Answer: Footing 4.0 m × 2.3 m × 700 mm thick; 16 mm @ 150 c/c along the length; along the width, 12 mm @ 100 c/c in the central 2.3 m band and 12 mm @ 120 c/c in the outer strips.