- 2080 Bhadra · 14 marks
Footing with load transfer check, 1000 kN
Short answer
Use a 3.4 m x 3.4 m square footing, overall depth 500 mm (d=440 mm). Reinforcement: 16 mm bars @205 mm c/c both ways. One-way and two-way shear are safe; load transfer check shows that column bars as dowels can carry the excess 60 kN, so the connection is adequate.
Design an isolated footing supporting a square column 400 mm x 400 mm with 8-20 longitudinal reinforcement. The column is subjected to axial service load of 1000 kN. Consider base of footing is 1 m below the ground level. Take allowable bearing capacity of soil 100 kN/m, M15 concrete and Fe 415 steel. Also check transfer of load from column to footing.
Data and assumptions
- Column 400 mm × 400 mm (long side mm along the footing length); footing concrete M15, steel Fe415; column concrete M20; column bars 8-20 mm.
- Service load kN.
- Allowable (safe) bearing capacity of soil = 100 kN/m² at 1.0 m depth.
- Column concrete grade is not given; M20 is assumed for the column (footing is M15).
- Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth mm (cover + half bar). Load factor 1.5.
Size of footing
Weight of footing and backfill is taken as 10% of the column load.
Provide a square footing m, area = 11.56 m² 11.00 m².
Factored soil pressure
kN. kN/m².
Bending moments and reinforcement
Cantilever projections from the column face: along : mm; along : mm. : kN·m, kN·m. Required depth for flexure: is far larger than the moment for mm, so the depth is governed by shear (one-way or punching). Trial mm, mm, found by the shear checks below.
; minimum steel = 0.12% of .
| Direction | (kN·m) | req (mm²) | Provide | prov (mm²) |
|---|---|---|---|---|
| Along (width ) | 496.3 | 3331 | 16 mm @ 205 c/c | 3335 |
| Along (width ) | 496.3 | 3331 | 16 mm @ 205 c/c | 3335 |
Check for one-way shear (at distance from the column face)
- Along side: kN, MPa; , MPa (Table 19). , safe.
- Along side: kN, MPa; , MPa. Safe.
Check for two-way (punching) shear (at from the column face)
- Perimeter mm
- kN (average pressure; the effect of moment transfer is neglected).
- MPa; , MPa. , safe.
Development length
, MPa (M15, deformed bars): 16 mm bars (both directions) → mm. Available length from column face (less 50 mm end cover): 1450 mm along , 1450 mm along . Satisfied in both directions.
Bearing stress and transfer of load from column
Column area m². Bearing stress MPa. Permissible bearing stress: column concrete MPa; footing concrete with gives up to 13.50 MPa. The lesser, 9.00 MPa, governs. Capacity of bearing = 1440 kN kN, so the excess 60 kN must be carried by dowels: mm²; the column bars (8-20 mm, 2513 mm²) are continued into the footing as dowels - adequate. Dowel length in compression mm (and the same lap with the column bars). Available depth in footing = 500 - 50 - 32 = 418 mm ; dowels are bent at the bottom with 90° bends.
Detailing
PLAN (3.4 m x 3.4 m)
+------------------------------------+
| | | | | | | | | | |
|--+---+---+---+---+---+---+---+---+-|
| | | | | | | | | | |
|--+---+---+---+---+---+---+---+---+-|
| | | | +----------+ | | | |
|--+---+---+-| column |--+---+---+-|
| | | | +----------+ | | | |
|--+---+---+---+---+---+---+---+---+-|
| | | | | | | | | | |
|--+---+---+---+---+---+---+---+---+-|
| | | | | | | | | | |
+------------------------------------+
| = bars along B, - = bars along L: 16 mm @ 205 c/c both ways
ELEVATION
| column |
| |
+---------------+----------+---------------+
| (dowels) | D = 500 mm
| o o o o o o o o o o o o o | bottom mesh, 50 mm cover
+------------------------------------------+
<---------------- 3400 mm ----------------->
- Bottom mesh: 16 mm @ 205 c/c along (lower layer), 16 mm @ 205 c/c along (upper layer), 50 mm clear cover; dowels 8-20 mm.
Answer: Footing 3.4 m × 3.4 m × 500 mm thick; 16 mm @ 205 c/c along the length and 16 mm @ 205 c/c along the width.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Isolated square footing, 650 kN service · Design of RCC Structure, chapter 11 · asked 2×
- Isolated square footing, 600 kN and 50 kNm · Design of RCC Structure, chapter 11 · asked 2×
- Isolated footing 450x450, 1600 kN service · Design of RCC Structure, chapter 11
- Isolated footing 400x400, 1200 kN service · Design of RCC Structure, chapter 11
- Isolated footing 450x450, service moment 110 kNm · Design of RCC Structure, chapter 11 · asked 2×
- Isolated footing 400x400, service moment 120 kNm · Design of RCC Structure, chapter 11 · asked 2×
- Brick column design for 80 kN axial load · Concrete Technology and Masonry Structure, chapter 8
- Slab base for ISHB 350@710.2, 1000 kN · Design of Steel and Timber Structure, chapter 6 · asked 2×
- Slab base for SC 220, 1000 kN, M30 · Design of Steel and Timber Structure, chapter 6
- Square footing size in clay, 750 kN · Foundation Engineering, chapter 6