Isolated square footing, 650 kN service
Short answer
Provide a 2.1 m square footing, 450 mm thick. Reinforcement: 12 mm bars @ 205 mm c/c both ways. Provide 8 dowels of 16 mm diameter.
Design an isolated square footing foundation of uniform thickness for a 400 mm x 400 mm column subjected to an axial load of 650 kN at service state. Consider safe bearing capacity of soil as 170 kN/m and concrete of M20 and steel grade of Fe500. Show the reinforcements in plan and in section of footing.
Data and assumptions
- Column 400 mm × 400 mm (long side mm along the footing length); footing concrete M20, steel Fe500; column concrete M20; column bars 8-16 mm.
- Service load kN.
- Allowable (safe) bearing capacity of soil = 170 kN/m².
- Column bars assumed 8-16 mm.
- Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth mm (cover + half bar). Load factor 1.5.
Size of footing
Weight of footing and backfill is taken as 10% of the column load.
Provide a square footing m, area = 4.41 m² 4.21 m².
Factored soil pressure
kN. kN/m².
Bending moments and reinforcement
Cantilever projections from the column face: along : mm; along : mm. : kN·m, kN·m. Required depth for flexure: is far larger than the moment for mm, so the depth is governed by shear (one-way or punching). Trial mm, mm, found by the shear checks below.
; minimum steel = 0.12% of .
| Direction | (kN·m) | req (mm²) | Provide | prov (mm²) |
|---|---|---|---|---|
| Along (width ) | 167.7 | 1134 | 12 mm @ 205 c/c | 1159 |
| Along (width ) | 167.7 | 1134 | 12 mm @ 205 c/c | 1159 |
Check for one-way shear (at distance from the column face)
- Along side: kN, MPa; , MPa (IS 456 Table 19, SP 16 formula). , safe.
- Along side: kN, MPa; , MPa. Safe.
Check for two-way (punching) shear (at from the column face)
- Perimeter mm
- kN (average pressure; the effect of moment transfer is neglected).
- MPa; , MPa. , safe.
Development length
, MPa (M20, deformed bars): 12 mm bars (both directions) → mm. Available length from column face (less 50 mm end cover): 800 mm along , 800 mm along . Satisfied in both directions.
Bearing stress and transfer of load from column
Column area m². Bearing stress MPa. Permissible bearing stress: column concrete MPa; footing concrete with gives up to 18.00 MPa. The lesser, 9.00 MPa, governs. Capacity of bearing = 1440 kN kN, so the whole load can be transferred by bearing. Provide minimum dowels of 0.5% of column area = 800 mm²: use 8 bars of 16 mm (1608 mm²) as dowels, same as column bars. Dowel length in compression mm (and the same lap with the column bars). Available depth in footing = 450 - 50 - 24 = 376 mm ; dowels are bent at the bottom with 90° bends.
Detailing
PLAN ELEVATION
+------------------+ col
| # # # # # # | | |
| # +------+ # # | _|_|__
| # | col | # # | |_____| <- D = 450 mm
| # +------+ # # | bars both ways
| # # # # # # |
+------------------+
L = 2.1 m, B = 2.1 m
- Bottom mesh: 12 mm @ 205 c/c along (lower layer), 12 mm @ 205 c/c along (upper layer), 50 mm clear cover; dowels 8-16 mm.
Answer: Footing 2.1 m × 2.1 m × 450 mm thick; 12 mm @ 205 c/c along the length and 12 mm @ 205 c/c along the width.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Isolated square footing, 600 kN and 50 kNm · Design of RCC Structure, chapter 11 · asked 2×
- Isolated footing 450x450, 1600 kN service · Design of RCC Structure, chapter 11
- Isolated footing 400x400, service moment 120 kNm · Design of RCC Structure, chapter 11 · asked 2×
- Isolated footing 400x400, 1200 kN service · Design of RCC Structure, chapter 11
- Isolated footing 450x450, service moment 110 kNm · Design of RCC Structure, chapter 11 · asked 2×
- Footing, 1250 kN column load, depth 1.8 m · Design of RCC Structure, chapter 11
- Footing with load transfer check, 1000 kN · Design of RCC Structure, chapter 11
- Brick column design for 80 kN axial load · Concrete Technology and Masonry Structure, chapter 8
- Safe axial load on a timber column · Design of Timber and Masonry Structures, chapter 3
- Soil exploration, safe bearing capacity, improvement · Building Technology, chapter 2
- Allowable load of 400 mm pile, layered soil · Foundation Engineering, chapter 8