- 2074 Asoj · 14 marks
Footing 350x350, 8-16 mm bars, reversible moment
Short answer
Provide a rectangular footing 3.3 m × 1.8 m, 700 mm deep. Reinforcement: 12 mm bars at 130 mm c/c along length; in short direction, central band 12 mm at 100 mm c/c and outer strips 12 mm at 120 mm c/c.
Design a footing for a square column of size 350 mm x 350 mm reinforced with 8-16 mm dia. bars. The column is subjected to a factored axial load and moment of 1100 KN and 60 KN-m, respectively. The allowable bearing capacity of soil is 150 KN/m at a depth of 1.5 m. Use M20 Concrete and Fe 500 steel for footing, and M30 Concrete and Fe 500 steel for column. Assume that the moment is reversible. Sketch the details (Plan and sections).
Data and assumptions
- Column 350 mm × 350 mm (long side mm along the footing length); footing concrete M20, steel Fe500; column concrete M30; column bars 8-16 mm.
- Given loads are factored: kN, kN·m. Service loads = factored / 1.5: kN, kN·m.
- Allowable (safe) bearing capacity of soil = 150 kN/m² at 1.5 m depth.
- The moment is reversible: same steel on both sides.
- Clear cover 50 mm for the footing (IS 456 cl. 26.4.2.2); effective depth mm (cover + half bar). Load factor 1.5.
Size of footing
Weight of footing and backfill is taken as 10% of the column load.
Eccentricity m, which is less than , so there is no tension under the base. The size is chosen so that
Try m ( m²): kN/m² and kN/m² . Safe.
Factored soil pressure
kN, kN·m. : kN/m², kN/m² (average 185.2 kN/m²). Self-weight does not cause bending in the footing, so it is excluded.
Bending moments and reinforcement
Cantilever projections from the column face: along : mm; along : mm. Along (critical section at the column face on the side of maximum pressure, linear pressure): , with kN/m² at the face and m: kN·m. Along (average pressure): kN·m. Required depth for flexure: is far larger than the moment for mm, so the depth is governed by shear (one-way or punching). Trial mm, mm, found by the shear checks below.
; minimum steel = 0.12% of .
| Direction | (kN·m) | req (mm²) | Provide | prov (mm²) |
|---|---|---|---|---|
| Along (width ) | 387.8 | 1512 (minimum) | 12 mm @ 130 c/c | 1566 |
| Along (width ) | 160.6 | 2772 | 12 mm @ 130 c/c | 2871 |
For the rectangular footing, the short-direction steel is placed in a central band of width mm in the proportion (IS 456 cl. 34.3.1), where .
- Central band: mm² → 12 mm @ 100 mm c/c (18 bars).
- Each outer strip (750 mm wide): remaining steel 408 mm² or minimum 0.12% = 630 mm², whichever is more → 12 mm @ 120 mm c/c (6 bars).
Check for one-way shear (at distance from the column face)
- Along side: kN, MPa; , MPa (IS 456 Table 19, SP 16 formula). , safe.
- Along side: kN, MPa; , MPa. Safe.
Check for two-way (punching) shear (at from the column face)
- Perimeter mm
- kN (average pressure; the effect of moment transfer is neglected).
- MPa; , MPa. , safe.
Development length
, MPa (M20, deformed bars): 12 mm bars (both directions) → mm. Available length from column face (less 50 mm end cover): 1425 mm along (adequate), 675 mm along . Along the available 675 mm is slightly less than mm, so the bars are given 90° bends at the ends (each bend adds an anchorage value of mm), which is adequate.
Bearing stress and transfer of load from column
Column area m². Bearing stress MPa. Permissible bearing stress: column concrete MPa; footing concrete with gives up to 18.00 MPa. The lesser, 13.50 MPa, governs. Capacity of bearing = 1654 kN kN, so the whole load can be transferred by bearing. Provide minimum dowels of 0.5% of column area = 612 mm²: use 8 bars of 16 mm (1608 mm²) as dowels, same as column bars. Dowel length in compression mm (and the same lap with the column bars). Available depth in footing = 700 - 50 - 24 = 626 mm ; dowels are bent at the bottom with 90° bends.
Detailing
PLAN ELEVATION
+------------------+ col
| # # # # # # | | |
| # +------+ # # | _|_|__
| # | col | # # | |_____| <- D = 700 mm
| # +------+ # # | bars both ways
| # # # # # # |
+------------------+
L = 3.3 m, B = 1.8 m
- Bottom mesh: 12 mm @ 130 c/c along (lower layer); along (upper layer), 12 mm @ 100 c/c in the central 1.8 m band and 12 mm @ 120 c/c in each outer strip, 50 mm clear cover; dowels 8-16 mm.
Answer: Footing 3.3 m × 1.8 m × 700 mm thick; 12 mm @ 130 c/c along the length; along the width, 12 mm @ 100 c/c in the central 1.8 m band and 12 mm @ 120 c/c in the outer strips.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Footing 300x400 column, factored moment 120 kNm · Design of RCC Structure, chapter 11
- Footing for 400x300 column, reversible moment · Design of RCC Structure, chapter 11
- Footing for 30x35 cm column, M25 · Design of RCC Structure, chapter 11
- Isolated footing 350x350, 1500 kN · Design of RCC Structure, chapter 11
- Column 350x350, 1440 kN, ductile detailing · Design of RCC Structure, chapter 10 · asked 2×
- Footing, 450x500 column, 6#20, uniaxial moment · Design of RCC Structure, chapter 11
- Box deodar column, 60 mm planks, 350 kN · Design of Steel and Timber Structure, chapter 11
- Brick column design for 80 kN axial load · Concrete Technology and Masonry Structure, chapter 8
- Allowable load on 30 x 60 cm column · Concrete Technology and Masonry Structure, chapter 8
- Square footing size in clay, 750 kN · Foundation Engineering, chapter 6