- 2074 Asoj · 15 marks
Column 35x40 cm, not restrained against rotation
Short answer
Column is short since slenderness ratios are 7.75 and 8.86. Biaxial interaction check is safe with 20-16 mm longitudinal bars (Asc 4021 mm2, 2.87%) and 8 mm ties at 250 mm c/c.
A RC column of size 35 cm x 40 cm with unsupported length of 3.10 m is subjected to a factored axial load of 1500 kN and biaxial moments, = 125 kNm and = 88 kNm. The ends of the column are effectively held in position but not restrained against rotation. Design the column for longitudinal and transverse reinforcements and sketch the details. Use M25 Concrete and Fe500 grade steel.
Data and assumptions
- Column 350 mm (width ) × 400 mm (depth ); kN; MPa, MPa. Clear cover 40 mm (IS 456 cl. 26.4.2.1), 8 mm ties.
- Moments: about major axis (x-x) = 125 kN·m; about minor axis (y-y) = 88 kN·m.
- Held in position but not restrained against rotation at both ends: m (IS 456 Table 28).
- Sizes are given as with ; moments act about the major axis (depth ) and about the minor axis (depth ).
Slenderness
| Axis | (mm) | Dimension (mm) | dim | Type |
|---|---|---|---|---|
| x-x (about major) | 3100 | 400 | 7.75 | short |
| y-y (about minor) | 3100 | 350 | 8.86 | short |
Both ratios are below 12, so the column is short; no additional moment is required.
Minimum eccentricity (cl. 25.4)
- About x-x: mm (min. 20 mm); adopt 20.0 mm; kN·m
- About y-y: mm (min. 20 mm); adopt 20.0 mm; kN·m
Design moments
- Design moments: kN·m, kN·m (not less than the minimum-eccentricity values).
Longitudinal reinforcement
Bars are chosen so that lies between 0.8% (minimum) and 4% (practical maximum; IS 456 cl. 26.5.3.1 allows 6%). The uniaxial capacities , at are read from the SP-16 interaction charts for rectangular sections; here they are computed by strain compatibility with the IS 456 stress block and the design stress-strain curve of steel (same basis as the charts), with effective cover .
| Trial | (%) | ||||||
|---|---|---|---|---|---|---|---|
| 12-20 φ | 2.69 | 0.145 | 175.7 | 145.8 | 0.509 | 1.52 | 1.063 ✗ |
| 8-25 φ | 2.80 | 0.151 | 182.7 | 151.1 | 0.499 | 1.50 | 1.011 ✗ |
| 20-16 φ | 2.87 | 0.140 | 184.7 | 153.6 | 0.494 | 1.49 | 0.995 ✓ |
Check
kN , so (IS 456 cl. 39.6; linear between 1.0 at 0.2 and 2.0 at 0.8).
The interaction condition is satisfied; the section is safe.
Provide 20-16 mm bars ( mm², ), within 0.8% to 4%.
Lateral ties
- Diameter mm → provide 8 mm.
- Pitch (least lateral dimension, , 300 mm) mm → provide 8 mm ties @ 250 mm c/c.
Detailing
CROSS-SECTION 350 x 400
+-------------------------+
| |
| o o o o o o |
| o o |
| |
| o o |
| |
| o o |
| |
| o o |
| o o o o o o |
| |
+-------------------------+
o = 16 mm bars, ties 8 mm @ 250 c/c
Answer: 350 × 400 mm column with 20-16 mm longitudinal bars () and 8 mm ties @ 250 mm c/c.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Biaxial column 400x600, 1500 kN · Design of RCC Structure, chapter 10
- Short column 350x500, M30, 1500 kN · Design of RCC Structure, chapter 10 · asked 2×
- Short column 450x300, 1500 kN, M30 · Design of RCC Structure, chapter 10 · asked 2×
- Short column 35x45 cm, 1800 kN · Design of RCC Structure, chapter 10
- Biaxial column 500x600, 1300 kN · Design of RCC Structure, chapter 10
- Footing 300x400 column, factored moment 120 kNm · Design of RCC Structure, chapter 11
- Built-up column, battens, 6 m unsupported, 1200 kN · Design of Steel and Timber Structure, chapter 6
- Brick column 35 cm x 50 cm allowable load · Concrete Technology and Masonry Structure, chapter 8
- Built-up column with battens, 4 m, 1000 kN · Design of Steel and Timber Structure, chapter 6 · asked 2×
- Braced built-up column, 3 m, 1600 kN · Design of Steel and Timber Structure, chapter 6 · asked 2×