Short answer

IS 456-2000 controls cracking by limiting bar spacing (slabs: main bars 3d or 300 mm, distribution 5d or 450 mm; beams: Table 15), using small-diameter bars, providing side-face reinforcement for beams >750 mm deep, ensuring minimum steel, limiting cover to 50 mm, and restricting surface crack width to 0.3 mm (0.2 mm in aggressive environments).

Discuss the methods of crack control as per IS 456-2000 in RC structures.

Cracking is a serviceability limit state: cracks spoil the appearance and let moisture reach the steel, causing corrosion. IS 456-2000 does not require a crack width calculation for every member; instead it controls cracking by detailing rules and, where needed, by a check on crack width.

Methods of crack control

  1. Limit the bar spacing (cl. 26.3.3(b), cl. 43 and Table 15).
    • In slabs, the horizontal distance between parallel main bars should not exceed 3d3d or 300 mm, whichever is less; for distribution bars 5d5d or 450 mm.
    • In beams, the clear distance between tension bars is limited by Table 15 (it depends on the service stress, i.e. on fyf_y and the redistribution of moments), e.g. a maximum clear spacing of about 180 to 300 mm.
  2. Use small-diameter bars well distributed around the tension zone instead of a few large bars.
  3. Side-face reinforcement: in beams with overall depth above 750 mm, provide 0.1% of the web area on each face, spaced not more than 300 mm or the web thickness, to control cracks on the sides (cl. 26.5.1.3).
  4. Minimum steel: provide at least the minimum tension steel (e.g. 0.85bd/fy0.85bd/f_y for beams, 0.12-0.15% for slabs) so that cracking does not occur suddenly.
  5. Limit the cover to the tension reinforcement to 50 mm; larger cover needs extra mesh to control cracks. Adequate cover is also needed for durability.
  6. Limit the crack width: the surface width of a crack should not exceed 0.3 mm in members where cracking is not harmful (0.2 mm in aggressive environment, 0.1 mm in severe) - cl. 35.3.2. It is calculated by the formula of Annex F when required.
  7. Control shrinkage and temperature cracks: proper curing, low water-cement ratio, contraction/expansion joints and distribution steel.