HVDC power loss is 2/3 of HVAC

Short answer

Assuming identical conductors with equal current and per-conductor loss p, a 3-phase AC line has total loss 3p while a bipolar DC line has 2p. At the typical power factor 0.943, both lines transmit the same power. Thus, total HVDC loss is exactly 2/3 of the HVAC loss.

Justify that the total power loss of HVDC transmission line is only 2/3th of total power loss in HVAC transmission line. Make assumption that the power loss per conductor is same for both lines and also the transmission capacity of both lines are same.

The claim compares a three-phase HVAC line (3 conductors) with a bipolar HVDC line (2 conductors) of the same power capacity, assuming each conductor has the same loss.

Step 1: Show that both lines carry the same power

Let both lines use the same conductors (same rms current II, resistance RR per conductor) and the same insulation (same peak voltage to earth VmV_m). For DC: Vd=VmV_d = V_m, Id=II_d = I.

Pac=3⋅Vm2⋅Icos⁡ϕ=2.121 VmIcos⁡ϕPdc=2VdId=2VmI\begin{aligned} P_{ac} &= 3\cdot\frac{V_m}{\sqrt{2}}\cdot I\cos\phi = 2.121\,V_mI\cos\phi \\ P_{dc} &= 2V_dI_d = 2V_mI \end{aligned}

Equating, Pdc=PacP_{dc} = P_{ac} when cos⁡ϕ=223=0.943\cos\phi = \dfrac{2\sqrt{2}}{3} = 0.943, which is a typical operating power factor. So a 2-conductor DC line has practically the same capacity as a 3-conductor AC line.

Step 2: Loss per conductor

Since both carry the same current II (rms for AC, DC value for DC) through the same resistance RR:

pac=I2R=pdc=pp_{ac} = I^2R = p_{dc} = p

(This is the given assumption.)

Step 3: Total losses

Lossac=3I2R=3pLossdc=2I2R=2p\begin{aligned} \text{Loss}_{ac} &= 3I^2R = 3p \\ \text{Loss}_{dc} &= 2I^2R = 2p \end{aligned} LossdcLossac=2p3p=23\frac{\text{Loss}_{dc}}{\text{Loss}_{ac}} = \frac{2p}{3p} = \frac{2}{3}

Hence the total power loss of the HVDC line is only 2/3 of that of the HVAC line of the same capacity.

 HVAC:  ===== a  (loss p)      HVDC: ===== +Vd (loss p)
        ===== b  (loss p)            ===== -Vd (loss p)
        ===== c  (loss p)
 Total: 3p                    Total: 2p

Further points

  • Efficiency of DC is also higher because there is no skin effect (AC resistance > DC resistance) and corona loss is lower.
  • No reactive (charging) current flows in a DC line, so the full current rating carries real power.
  • Converter station losses (about 0.5–1% per station) must be added, which is why HVDC pays off only for long distances.

✓ Answer checked by Claude Opus 5.5 (high effort)

All Power Electronics chapter 7 questions →