Reversible power flow on a DC line

Short answer

In an HVDC line with thyristor converters, power reversal is achieved by reversing voltage polarity, not current direction. Normally α1<90° (rectifier) and α2>90° (inverter); for reversal, α1>90° and α2<90°, making Vd negative while Id direction stays fixed. Current flows only if α1+α2<180°, and for low line resistance α2≈180°–α1.

With the help of suitable circuit diagram, describe the operation of reversible power flow on DC line.

In a DC (HVDC) line with thyristor converters at both ends, the direction of current cannot reverse because thyristors conduct only one way. Power flow is reversed by reversing the polarity of the DC voltage, which is done by changing the firing angles: the rectifier becomes an inverter and the inverter becomes a rectifier.

Circuit

   AC sys 1                         AC sys 2
     |   Conv 1      R, Ld      Conv 2   |
     +--[3-ph full]--+--/\/\--+--[3-ph full]--+
        bridge  Vd1 (+)  Id -> (+) Vd2'  bridge
                 |               |
                 +---------------+
 Vd1 = Vdo cos a1     Vd2' = -Vdo cos a2

Both converters are three-phase fully controlled bridges whose average output is Vdocos⁡αV_{do}\cos\alpha: positive for 0<α<90°0 < \alpha < 90° (rectifier) and negative for 90°<α<180°90° < \alpha < 180° (inverter).

Operation

Let both converters have the same no-load voltage Vdo=32VLπV_{do} = \dfrac{3\sqrt{2}V_L}{\pi} and the line resistance be RR. Converter 1 gives Vd1=Vdocos⁡α1V_{d1} = V_{do}\cos\alpha_1. Converter 2 is connected in opposition, so its terminal voltage seen by the line is Vd2′=−Vdocos⁡α2V_{d2}' = -V_{do}\cos\alpha_2. Thyristors allow current IdI_d in one direction only:

Id=Vd1−Vd2′R=Vdo(cos⁡α1+cos⁡α2)R≥0I_d = \frac{V_{d1} - V_{d2}'}{R} = \frac{V_{do}(\cos\alpha_1 + \cos\alpha_2)}{R} \ge 0

Power sent by converter 1 and received by converter 2:

P1=Vdocos⁡α1 Id,P2=−Vdocos⁡α2 Id,P1−P2=Id2RP_1 = V_{do}\cos\alpha_1\,I_d, \qquad P_2 = -V_{do}\cos\alpha_2\,I_d, \qquad P_1 - P_2 = I_d^2R

Case 1: power from system 1 to system 2.

  • α1<90°\alpha_1 < 90°: converter 1 is a rectifier (Vd1>0V_{d1} > 0, P1>0P_1 > 0).
  • α2>90°\alpha_2 > 90°: converter 2 is an inverter (cos⁡α2<0\cos\alpha_2 < 0, P2>0P_2 > 0 delivered to system 2).
  • Line voltage is positive at the top conductor.

Case 2: power from system 2 to system 1 (reversal).

  • Make α1>90°\alpha_1 > 90°: converter 1 becomes an inverter (Vd1<0V_{d1} < 0).
  • Make α2<90°\alpha_2 < 90°: converter 2 becomes a rectifier.
  • The current direction stays the same; only the polarity of the DC line voltage reverses, so P=VdIdP = V_dI_d changes sign.

Condition for current flow in both cases:

cos⁡α1+cos⁡α2>0  ⇒  cos⁡α1>cos⁡(180°−α2)  ⇒  α1+α2<180°\cos\alpha_1 + \cos\alpha_2 > 0 \;\Rightarrow\; \cos\alpha_1 > \cos(180° - \alpha_2) \;\Rightarrow\; \alpha_1 + \alpha_2 < 180°

For a line of small resistance, IdRI_dR is small, so

α1+α2≈180°,i.e. α2≈180°−α1\alpha_1 + \alpha_2 \approx 180°, \quad \text{i.e. } \alpha_2 \approx 180° - \alpha_1

The magnitude of IdI_d (and power) is set by how much α1+α2\alpha_1 + \alpha_2 is less than 180°180°; the direction of power is set by which converter has α<90°\alpha < 90°.

Modeα1\alpha_1α2\alpha_2Line polarityPower
Normal<90°< 90° (rectifier)>90°> 90° (inverter)+1 → 2
Reversed>90°> 90° (inverter)<90°< 90° (rectifier)−2 → 1

Practical sequence for reversal

  1. Reduce the current order to a minimum value.
  2. Increase α1\alpha_1 beyond 90°90° and decrease α2\alpha_2 below 90°90° gradually; the line voltage passes through zero and reverses.
  3. Raise the current order again; power now flows from system 2 to system 1.

No switching of conductors is needed and reversal takes only a fraction of a second, which is an important advantage of HVDC links.