Frequency dependent load and speed deviation
Short answer
Frequency-independent load (e.g., lighting) is constant with frequency; frequency-dependent load (e.g., motors) varies, adding damping D. A load increase causes frequency to fall, and D limits the deviation. The transfer function of speed deviation due to load change is ΔΩ(s) = –1/(2Hs + D), with inertia H and damping D.
What do you understand by frequency dependent and independent load? What are the roles of these load on change in frequency? Deduce the transfer function of speed deviation due to load change, including effect of these type of load and inertia.
Loads are of two types according to how their power depends on frequency:
- Frequency independent loads take the same power at any frequency. Examples: resistive loads such as lighting and heating.
- Frequency dependent loads change their power with frequency. Example: motor loads (fans, pumps, compressors), whose power varies with speed. For small changes their effect is written as .
So the total electrical load change is
where = frequency-independent load change and = load damping constant (% change in load for 1 % change in frequency, typically 1–2).
Role on frequency change
- A rise in frequency-independent load creates an unbalance , which causes the frequency to fall.
- The frequency-dependent load opposes the change: as frequency falls, motor loads take less power. This "self-regulation" reduces the unbalance and helps the system reach a new steady frequency even without a governor.
- A larger gives a smaller frequency deviation and faster settling.
Transfer function of speed deviation
Inertia (rotating mass): for small changes, in per unit, the swing equation is
where = inertia constant (s) and = speed deviation (pu). Taking the Laplace transform,
Load damping: as shown above, the composite load (frequency-insensitive part plus motor part) gives
Substituting,
With the turbine power constant (, no governor action):
dPm=0 + +--------------+
------>(+)->| 1 |----+--> d(omega)
^ - | 2Hs + D | |
| +--------------+ |
dPL
For a step load :
- Inertia sets the initial rate of fall () and the time constant .
- Damping sets the final deviation . If all load were frequency independent (), : speed would keep falling linearly without limit.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Speed control by inertia and load damping · Power Plant Equipment, chapter 2 · asked 6×
- Excitation system with stabilizing transformer: transfer function · Power Plant Equipment, chapter 3 · asked 13×
- Water turbine transfer function and characteristics · Power Plant Equipment, chapter 2 · asked 2×
- Function of excitation system and its transfer function · Power Plant Equipment, chapter 3 · asked 2×
- Load sharing: 250/500 MW, frequency falls to 49.5 Hz · Power Plant Equipment, chapter 2 · asked 2×
- Speed droop in sharing common load · Power Plant Equipment, chapter 2 · asked 2×
- Two-inertia rotational system transfer function and T-I analogy · Control Systems, chapter 2
- Wave function significance; time independent equation · Engineering Physics, chapter 10 · asked 2×
- Equivalent inertia, speed profile and quadrants (Fig 2b) · Utilization of Electrical Energy, chapter 2
- Wave function and time dependent Schrödinger equation · Engineering Physics, chapter 10 · asked 2×