Load sharing: 600 MVA (6%) and 500 MVA (4%)
Short answer
Steady-state frequency deviation is –0.24 Hz (59.76 Hz). Unit 1 generates 540 MW and Unit 2 generates 450 MW.
Two generating units have following ratings and droop: Unit 1: 600MVA, R1 = 6%; Unit 2: 500MVA, R2 = 4%. The units are operating in parallel sharing a load of 900 MW at the normal frequency of 60Hz. Unit 1 supplies 500 MW and unit 2 supplies 400MW. If the load is increased by 90MW calculate the steady state frequency deviation and new generation on each unit.
Both units drop along their droop lines to a common frequency; the 90 MW is shared in proportion to . MVA ratings are used as the MW base.
Method: a unit with droop (pu on its own rating ) and rated frequency changes its output by
where is its stiffness in MW/Hz. All units run at the same frequency, so .
Data: Unit 1: 600 MVA, , 500 MW; Unit 2: 500 MVA, , 400 MW; Hz; MW.
In per unit: pu. New frequency Hz.
Per-unit cross-check (base 1000 MVA): , ; pu ✓.
| Unit | Initial (MW) | Increase (MW) | New (MW) |
|---|---|---|---|
| 1 | 500 | 40 | 540 |
| 2 | 400 | 50 | 450 |
Answer: Steady-state frequency deviation = −0.24 Hz (−0.004 pu), i.e. 59.76 Hz; Unit 1 = 540 MW, Unit 2 = 450 MW.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Load sharing: 600 MVA and 500 MVA, 4%/6% droop · Power Plant Equipment, chapter 2 · asked 2×
- Load sharing: 600 and 500 MVA, 900 MVA load · Power Plant Equipment, chapter 2
- Load sharing: 600 MW and 300 MW, 7%/8% droop · Power Plant Equipment, chapter 2 · asked 2×
- Load sharing: 500 MW and 250 MW, 5%/6% droop · Power Plant Equipment, chapter 2 · asked 2×
- Load sharing: 250 MW and 500 MW, 20%/10% droop · Power Plant Equipment, chapter 2 · asked 2×
- Load sharing: 250 MW and 500 MW, 4%/3% droop · Power Plant Equipment, chapter 2
- Load sharing between two stations in parallel · Electric Machines II, chapter 1
- Parallel transformers and per-unit impedance load sharing · Electrical Machines I, chapter 2