Load sharing: 600 MVA (6%) and 500 MVA (4%)

Short answer

Steady-state frequency deviation is –0.24 Hz (59.76 Hz). Unit 1 generates 540 MW and Unit 2 generates 450 MW.

Two generating units have following ratings and droop: Unit 1: 600MVA, R1 = 6%; Unit 2: 500MVA, R2 = 4%. The units are operating in parallel sharing a load of 900 MW at the normal frequency of 60Hz. Unit 1 supplies 500 MW and unit 2 supplies 400MW. If the load is increased by 90MW calculate the steady state frequency deviation and new generation on each unit.

Both units drop along their droop lines to a common frequency; the 90 MW is shared in proportion to Pr/RP_r/R. MVA ratings are used as the MW base.

Method: a unit with droop RR (pu on its own rating PrP_r) and rated frequency f0f_0 changes its output by

ΔP=−PrR f0 Δf=−K Δf\Delta P = -\frac{P_r}{R\,f_0}\,\Delta f = -K\,\Delta f

where K=Pr/(Rf0)K = P_r/(R f_0) is its stiffness in MW/Hz. All units run at the same frequency, so ΔPL=−Δf∑K\Delta P_L = -\Delta f \sum K.

Data: Unit 1: 600 MVA, R1=0.06R_1 = 0.06, 500 MW; Unit 2: 500 MVA, R2=0.04R_2 = 0.04, 400 MW; f0=60f_0 = 60 Hz; ΔPL=90\Delta P_L = 90 MW.

K1=6000.06×60=166.67 MW/HzK2=5000.04×60=208.33 MW/HzΔf=−90166.67+208.33=−90375=−0.24 Hz\begin{aligned} K_1 &= \frac{600}{0.06 \times 60} = 166.67\ \text{MW/Hz} \\ K_2 &= \frac{500}{0.04 \times 60} = 208.33\ \text{MW/Hz} \\ \Delta f &= -\frac{90}{166.67 + 208.33} = -\frac{90}{375} = -0.24\ \text{Hz} \end{aligned}

In per unit: Δf=−0.24/60=−0.004\Delta f = -0.24/60 = -0.004 pu. New frequency =59.76= 59.76 Hz.

ΔP1=166.67×0.24=40 MWΔP2=208.33×0.24=50 MW\begin{aligned} \Delta P_1 &= 166.67 \times 0.24 = 40\ \text{MW} \\ \Delta P_2 &= 208.33 \times 0.24 = 50\ \text{MW} \end{aligned}

Per-unit cross-check (base 1000 MVA): R1=0.06×1000/600=0.1R_1 = 0.06 \times 1000/600 = 0.1, R2=0.04×1000/500=0.08R_2 = 0.04 \times 1000/500 = 0.08; Δf=−0.09/(10+12.5)=−0.004\Delta f = -0.09/(10 + 12.5) = -0.004 pu ✓.

UnitInitial (MW)Increase (MW)New (MW)
150040540
240050450

Answer: Steady-state frequency deviation = −0.24 Hz (−0.004 pu), i.e. 59.76 Hz; Unit 1 = 540 MW, Unit 2 = 450 MW.