Generator choice and SCR versus stability

Short answer

Factors: MVA/pf, voltage, speed/poles, shaft type, reactances/SCR, inertia, efficiency, insulation, cooling, excitation, NGT grounding, grid spec, transport limits. Lower SCR means higher Xd, so maximum power Pmax = EV·SCR decreases, load angle increases for same power, and synchronizing power coefficient reduces, lowering steady-state and transient stability margins.

Discuss the various factors which should be considered for the choice of generator during the design of a power plant. Also clarify analytically that lower the short circuit ratio (SCR), lower be the stability of the system.

Factors for the choice of generator

  1. Rating (MVA) and power factor: S=Pturbine ηg/cos⁡ϕS = P_{turbine}\,\eta_g / \cos\phi; power factor usually 0.85–0.9 lagging so the unit can supply reactive power. Some overload margin (e.g. 10%) is often specified.
  2. Rated voltage: usually 6.6 kV or 11 kV for hydro units (higher, e.g. 13.8–15.75 kV, for very large units); chosen with GSU and bus/cable cost.
  3. Speed and number of poles: fixed by the turbine: N=120f/pN = 120f/p. Hydro units are slow, salient-pole machines with many poles.
  4. Shaft arrangement: vertical (large Francis/Kaplan) or horizontal (small Pelton/Francis).
  5. Reactances and SCR: Xd′′X''_d sets fault level and breaker rating; SCR and XdX_d set stability and voltage regulation.
  6. Inertia constant (GD²): larger inertia limits speed rise on load rejection and improves stability, but costs more.
  7. Efficiency and losses: high efficiency (above 97–98%) saves energy over the plant life.
  8. Insulation and temperature rise: class F insulation with class B temperature rise is common; altitude derating above 1000 m.
  9. Cooling: air-cooled (open or closed with air–water coolers) for hydro.
  10. Excitation system: brushless for small/medium units, static for large units.
  11. Neutral grounding: high-resistance grounding via NGT.
  12. Grid requirements: capability curve, reactive power range, fault ride-through, harmonics.
  13. Transport and erection limits: weight and size on hill roads; split stator if needed.
  14. Standards and cost: IEC 60034; capital cost versus loss capitalisation.

Lower SCR gives lower stability (analytical proof)

Short circuit ratio (SCR) is the ratio of field current needed to produce rated open-circuit voltage to the field current needed to circulate rated armature current on a sustained three-phase short circuit:

SCR=If (rated OC voltage)If (rated SC current)≈1Xd (p.u., saturated)SCR = \frac{I_f\ (\text{rated OC voltage})}{I_f\ (\text{rated SC current})} \approx \frac{1}{X_d\,(\text{p.u., saturated})}

Typical values: salient-pole hydro generators 1.0–1.5; cylindrical-rotor turbo generators 0.5–0.7.

Analytical relation with stability

Power delivered by a generator (neglecting resistance and saliency) to an infinite bus:

P=EVXdsin⁡δ=E V (SCR)sin⁡δP = \frac{E V}{X_d}\sin\delta = E\,V\,(SCR)\sin\delta
  • Maximum (steady-state limit) power: Pmax=EVXd=E V (SCR)P_{max} = \dfrac{EV}{X_d} = E\,V\,(SCR). Lower SCR → lower PmaxP_{max}.
  • Load angle for given load: sin⁡δ=PE V (SCR)\sin\delta = \dfrac{P}{E\,V\,(SCR)}. Lower SCR → larger δ\delta, closer to the 90° limit.
  • Synchronizing power coefficient: Ps=dPdδ=E V (SCR)cos⁡δP_s = \dfrac{dP}{d\delta} = E\,V\,(SCR)\cos\delta. Lower SCR → smaller restoring torque after a disturbance.

Numerical illustration (E=1.8E = 1.8 p.u. kept the same, V=1V = 1 p.u., P=0.85P = 0.85 p.u.):

SCRXdX_d (p.u.)PmaxP_{max} (p.u.)δ\deltaPsP_s (p.u./rad)Margin (Pmax−P)/Pmax(P_{max}-P)/P_{max}
1.20.8332.1623.17°1.98660.6%
1.01.0001.8028.18°1.58752.8%
0.61.6671.0851.91°0.66621.3%

So the lower the SCR, the lower the stability margin (higher δ\delta, smaller PmaxP_{max} and PsP_s).

Physically, a low SCR means a high synchronous reactance, i.e. weak magnetic coupling between rotor and stator through a small air gap; the generator must swing to a larger angle to transmit the same power, leaving less margin before it slips a pole.