Factors in choosing a generator
Short answer
Generator selection factors: MVA rating from turbine output and power factor (0.85–0.9), voltage (6.6–11 kV), speed/poles (N=120f/p), shaft arrangement, reactances and SCR, inertia constant, efficiency above 97%, insulation class F/B, air cooling, excitation (brushless or static), high-resistance neutral grounding, grid requirements, transport limits, and cost.
Discuss the various factors which should be considered for the choice of generator during the design of a power plant.
The generator must match the turbine, the grid and the site. The main factors are:
- Rating (MVA) and power factor: ; power factor usually 0.85–0.9 lagging so the unit can supply reactive power. Some overload margin (e.g. 10%) is often specified.
- Rated voltage: usually 6.6 kV or 11 kV for hydro units (higher, e.g. 13.8–15.75 kV, for very large units); chosen with GSU and bus/cable cost.
- Speed and number of poles: fixed by the turbine: . Hydro units are slow, salient-pole machines with many poles.
- Shaft arrangement: vertical (large Francis/Kaplan) or horizontal (small Pelton/Francis).
- Reactances and SCR: sets fault level and breaker rating; SCR and set stability and voltage regulation.
- Inertia constant (GD²): larger inertia limits speed rise on load rejection and improves stability, but costs more.
- Efficiency and losses: high efficiency (above 97–98%) saves energy over the plant life.
- Insulation and temperature rise: class F insulation with class B temperature rise is common; altitude derating above 1000 m.
- Cooling: air-cooled (open or closed with air–water coolers) for hydro.
- Excitation system: brushless for small/medium units, static for large units.
- Neutral grounding: high-resistance grounding via NGT.
- Grid requirements: capability curve, reactive power range, fault ride-through, harmonics.
- Transport and erection limits: weight and size on hill roads; split stator if needed.
- Standards and cost: IEC 60034; capital cost versus loss capitalisation.
Example
For a 10 MW turbine output, , pf 0.85: generator rating MVA, 11 kV, 50 Hz; if the turbine speed is 600 rpm, poles .
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Generator choice and SCR versus stability · Power Plant Design, chapter 4
- Generator choice and significance of SCR · Power Plant Design, chapter 4
- Design: 260 m head plant, generator lead · Power Plant Design, chapter 4 · asked 5×
- Design: 245 m head plant, standby generator · Power Plant Design, chapter 4 · asked 14×
- Choice of generator circuit breaker · Power Plant Design, chapter 4 · asked 2×
- Design: 360 m head plant, 132 kV · Power Plant Design, chapter 4 · asked 5×
- Factors for choosing stations; offset types · Surveying I, chapter 3
- Factors in power and lighting system design · Industrial Power Distribution and Illumination, chapter 5
- Firm power and plant load factors · Hydro Power, chapter 3
- Factors affecting choice of BIL · Transmission and Distribution System Design, chapter 3