- 2066 Magh (old course) · 8 marks
Open circuit and short circuit tests
Short answer
Open circuit test: apply rated voltage to LV with HV open, measures core loss and shunt parameters R0, X0. Short circuit test: short LV, apply reduced voltage to HV to get rated current, gives full‑load copper loss and series parameters Req, Xeq. Both tests determine efficiency and regulation without full loading.
Describe the open circuit test and short circuit test for a single phase transformer.
The open circuit (OC) and short circuit (SC) tests find the equivalent circuit parameters, the losses and the efficiency of a transformer without loading it fully. They need very little power, which is only the loss of the transformer.
Open circuit test (no-load test)
Purpose: to find the core loss , no-load current and the shunt branch , .
W A
AC o---(W)--(A)----+----------+
supply (V) HV winding open
o-----------------+----------+
LV winding (rated V)
Procedure: the HV winding is left open, and rated voltage at rated frequency is applied to the LV winding (this is safer and needs lower-range instruments). A wattmeter, ammeter and voltmeter are connected on the LV side.
Calculations:
Since is small (2 to 5% of rated), the copper loss is negligible. So the wattmeter reading is the core (iron) loss, constant at all loads.
Short circuit test
Purpose: to find the full-load copper loss and the equivalent resistance, reactance and impedance , , .
W A
AC o---(W)--(A)----+----------+
supply (low V, (V) LV winding
via variac) short-circuited
o-----------------+----------+
HV winding
Procedure: the LV winding is short-circuited with a thick conductor. A low voltage (about 5 to 10% of rated) is applied to the HV winding and slowly increased by a variac until the rated full-load current flows. Wattmeter, ammeter and voltmeter are on the HV side.
Calculations:
Because the applied voltage is low, the flux and hence the core loss are very small (core loss varies as ). So the wattmeter reading is the full-load copper loss.
Uses of the results
- Equivalent circuit parameters, from which regulation is found: .
- Efficiency at any load: .
- The maximum efficiency load .
- Together, the two tests give the transformer's full performance while drawing only the loss power from the supply. This is their advantage over a direct load test.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- OC and SC tests to build transformer equivalent circuit · Electrical Machines I, chapter 2
- Equivalent circuit of 20 kVA 250/2500 V transformer from tests · Electrical Machines I, chapter 2 · asked 3×
- 250/500 V transformer test, equivalent circuit · Electrical Machines, chapter 2
- Equivalent circuit, efficiency and regulation of 5 kVA transformer · Electrical Machines I, chapter 2
- 20 kVA 2200/220 V tests, equivalent circuit LV side · Electrical Machines, chapter 2
- 1000 VA 230/115 V transformer equivalent circuit · Electrical Machines, chapter 2
- Murray loop test for open and short circuit faults · Power System Analysis I, chapter 2 · asked 5×
- Output (kVA) equation of single phase transformer · Electric Machine Design, chapter 3 · asked 3×
- Design: 100 kVA 2200/480 V single phase transformer · Electric Machine Design, chapter 3 · asked 3×
- Single phase vs 3-phase distribution transformer · Transmission and Distribution System Design, chapter 7 · asked 2×