OC and SC tests for efficiency and regulation

Short answer

OC test on LV side at rated voltage gives iron loss. SC test on HV side with LV shorted at rated current gives full-load copper loss and equivalent impedance. Efficiency = output/(output + iron loss + x^2 copper loss). Regulation = I(R cosφ ± X sinφ)/V × 100%.

Discuss how to conduct open-circuit and short-circuit tests on a single phase transformer in the laboratory. From the test results how the efficiency and voltage regulation of the transformer can be determined?

The open-circuit (OC) and short-circuit (SC) tests find the equivalent-circuit parameters, iron loss and copper loss of a transformer without actually loading it, so very little energy is used.

Open-circuit (no-load) test

  AC   +--(A)--+--[W]--+--------+      +------o
 supply|       |       |        |  LV  |  HV  open
 (var.)|      (V)      |   ||   | wdg  | wdg
       +-------+-------+--------+      +------o
  • Done on the LV side with HV open, at rated voltage and frequency (using an autotransformer/variac).
  • Readings: V0V_0, I0I_0, P0P_0.
  • Since I0I_0 is only 2-5% of rated current, copper loss is negligible, so P0P_0 = iron loss PiP_i.
  • From readings: cos⁡ϕ0=P0V0I0\cos\phi_0 = \frac{P_0}{V_0I_0}, Iw=I0cos⁡ϕ0I_w = I_0\cos\phi_0, Iμ=I0sin⁡ϕ0I_\mu = I_0\sin\phi_0, R0=V0IwR_0 = \frac{V_0}{I_w}, X0=V0IμX_0 = \frac{V_0}{I_\mu}.

Short-circuit test

  AC   +--(A)--+--[W]--+--------+      +------+
 supply|       |       |        |  HV  |  LV  | short
 (low) |      (V)      |   ||   | wdg  | wdg  | (thick
       +-------+-------+--------+      +------+  link)
  • Done on the HV side with LV shorted. Voltage is raised slowly from zero until rated current flows; this needs only 5-10% of rated voltage.
  • Readings: VscV_{sc}, IscI_{sc}, PscP_{sc}.
  • Flux is very small at this low voltage, so iron loss is negligible and PscP_{sc} = full-load copper loss.
  • From readings: Z01=VscIscZ_{01} = \frac{V_{sc}}{I_{sc}}, R01=PscIsc2R_{01} = \frac{P_{sc}}{I_{sc}^2}, X01=Z012−R012X_{01} = \sqrt{Z_{01}^2 - R_{01}^2} (referred to HV).

Finding efficiency

At a fraction xx of full load and power factor cos⁡ϕ\cos\phi:

η=x Scos⁡ϕx Scos⁡ϕ+Pi+x2Pcu,FL×100\eta = \frac{x\,S\cos\phi}{x\,S\cos\phi + P_i + x^2P_{cu,FL}}\times 100

where PiP_i is from the OC test and Pcu,FLP_{cu,FL} from the SC test (scaled by (Irated/Isc)2(I_{rated}/I_{sc})^2 if the test was not at rated current). Maximum efficiency occurs at x=Pi/Pcu,FLx = \sqrt{P_i/P_{cu,FL}}.

Finding voltage regulation

Using R01R_{01} and X01X_{01} (or R02R_{02}, X02X_{02}) from the SC test:

%Reg=I(Rcos⁡ϕ±Xsin⁡ϕ)V×100\%\text{Reg} = \frac{I(R\cos\phi \pm X\sin\phi)}{V}\times 100

(+ for lagging, − for leading pf). Equivalently, %Reg=%Rcos⁡ϕ±%Xsin⁡ϕ\%\text{Reg} = \%R\cos\phi \pm \%X\sin\phi where %R=PscS×100\%R = \frac{P_{sc}}{S}\times100 and %Z=VscVrated×100\%Z = \frac{V_{sc}}{V_{rated}}\times100 when the test is at rated current.

Example: if a 10 kVA transformer has Pi=100P_i = 100 W and Pcu,FL=200P_{cu,FL} = 200 W, full-load efficiency at upf = 1000010300=97.1%\frac{10000}{10300} = 97.1\%.

Advantages: low power consumption, no need for a real load, and both losses found separately so efficiency at any load and pf can be predicted.