- 2073 Magh · 8 marks
OC and SC tests for efficiency and regulation
Short answer
OC test on LV side at rated voltage gives iron loss. SC test on HV side with LV shorted at rated current gives full-load copper loss and equivalent impedance. Efficiency = output/(output + iron loss + x^2 copper loss). Regulation = I(R cosφ ± X sinφ)/V × 100%.
Discuss how to conduct open-circuit and short-circuit tests on a single phase transformer in the laboratory. From the test results how the efficiency and voltage regulation of the transformer can be determined?
The open-circuit (OC) and short-circuit (SC) tests find the equivalent-circuit parameters, iron loss and copper loss of a transformer without actually loading it, so very little energy is used.
Open-circuit (no-load) test
AC +--(A)--+--[W]--+--------+ +------o
supply| | | | LV | HV open
(var.)| (V) | || | wdg | wdg
+-------+-------+--------+ +------o
- Done on the LV side with HV open, at rated voltage and frequency (using an autotransformer/variac).
- Readings: , , .
- Since is only 2-5% of rated current, copper loss is negligible, so = iron loss .
- From readings: , , , , .
Short-circuit test
AC +--(A)--+--[W]--+--------+ +------+
supply| | | | HV | LV | short
(low) | (V) | || | wdg | wdg | (thick
+-------+-------+--------+ +------+ link)
- Done on the HV side with LV shorted. Voltage is raised slowly from zero until rated current flows; this needs only 5-10% of rated voltage.
- Readings: , , .
- Flux is very small at this low voltage, so iron loss is negligible and = full-load copper loss.
- From readings: , , (referred to HV).
Finding efficiency
At a fraction of full load and power factor :
where is from the OC test and from the SC test (scaled by if the test was not at rated current). Maximum efficiency occurs at .
Finding voltage regulation
Using and (or , ) from the SC test:
(+ for lagging, − for leading pf). Equivalently, where and when the test is at rated current.
Example: if a 10 kVA transformer has W and W, full-load efficiency at upf = .
Advantages: low power consumption, no need for a real load, and both losses found separately so efficiency at any load and pf can be predicted.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- OC and SC tests to build transformer equivalent circuit · Electrical Machines I, chapter 2
- OC/SC test of 2200/110 V, 40 kVA transformer · Electrical Machines I, chapter 2
- Equivalent circuit, efficiency and regulation of 5 kVA transformer · Electrical Machines I, chapter 2
- Efficiency and regulation of 5 kVA transformer · Electrical Machines I, chapter 2
- Loss assumptions in OC and SC tests · Electrical Machines I, chapter 2
- Equivalent circuit of 20 kVA 250/2500 V transformer from tests · Electrical Machines I, chapter 2 · asked 3×
- OC and SC tests, efficiency and regulation · Electrical Machine, chapter 2
- 20 kVA 250/2500 V tests, regulation, efficiency · Electrical Machines, chapter 2
- 5 kVA 220/400 V efficiency and regulation · Electrical Machines, chapter 2
- Open circuit and short circuit tests · Electrical Machines, chapter 2