Referred quantities in a transformer

Short answer

Referred quantities represent one winding’s values on the other side keeping power and losses unchanged. With K = N₂/N₁: voltage V₂' = V₂/K, current I₂' = K I₂, impedance Z₂' = Z₂/K². Impedance from LV to HV multiplies by turns ratio squared.

Define referred quantities in transformer. Derive the expression for the referred quantities (voltage, current, impedance) in a transformer.

Referred quantities are values of voltage, current and impedance of one winding expressed as equivalent values on the other side, chosen so that power, losses and per-unit drops are unchanged. Referring lets the two windings be joined into a single equivalent circuit without the ideal transformer.

Let K=N2/N1K = N_2/N_1 (transformation ratio).

Referred voltage

Emf per turn is the same in both windings: E1/N1=E2/N2E_1/N_1 = E_2/N_2. So a secondary voltage seen on the primary side is

V2′=N1N2V2=V2KV_2' = \frac{N_1}{N_2}V_2 = \frac{V_2}{K}

and a primary voltage referred to the secondary is V1′=KV1V_1' = K V_1.

Referred current

The secondary load current is balanced by the primary load component: N1I2′=N2I2N_1 I_2' = N_2 I_2 (mmf balance). Hence

I2′=N2N1I2=KI2I_2' = \frac{N_2}{N_1}I_2 = K I_2

and I1′=I1/KI_1' = I_1 / K when the primary current is referred to the secondary. Volt-amperes are unchanged: V2′I2′=(V2/K)(KI2)=V2I2V_2' I_2' = (V_2/K)(K I_2) = V_2 I_2.

Referred resistance

The copper loss must be the same before and after referring:

I2′2R2′=I22R2R2′=R2(I2I2′)2=R2K2\begin{aligned} I_2'^2 R_2' &= I_2^2 R_2 \\ R_2' &= R_2\left(\frac{I_2}{I_2'}\right)^2 = \frac{R_2}{K^2} \end{aligned}

Referred reactance and impedance

The reactive power (or the voltage drop as a fraction of voltage) must be the same:

I2′2X2′=I22X2⇒X2′=X2K2Z2′=V2′I2′=V2/KKI2=Z2K2\begin{aligned} I_2'^2 X_2' &= I_2^2 X_2 \Rightarrow X_2' = \frac{X_2}{K^2} \\ Z_2' &= \frac{V_2'}{I_2'} = \frac{V_2/K}{K I_2} = \frac{Z_2}{K^2} \end{aligned}

Likewise, primary impedance referred to the secondary: Z1′=K2Z1Z_1' = K^2 Z_1.

Summary

QuantitySecondary referred to primaryPrimary referred to secondary
VoltageV2/KV_2/KKV1K V_1
CurrentKI2K I_2I1/KI_1/K
Impedance (R, X, Z)Z2/K2Z_2/K^2K2Z1K^2 Z_1

Rule of thumb: to move an impedance from LV to HV multiply by (turns ratio)², i.e. HV side always has the larger impedance.

Example: for 2000/200 V (K=0.1K = 0.1), R2=0.02 ΩR_2 = 0.02\ \Omega referred to HV is 0.02/0.01=2 Ω0.02/0.01 = 2\ \Omega, so R01=R1+2 ΩR_{01} = R_1 + 2\ \Omega.