Cooling methods for electric machines
Short answer
Cooling can be natural (TENV), self-ventilated via shaft fan, or forced with separate blower. Airflow paths: radial through ducts, axial through core holes, or mixed. Large machines use closed circuits (TEFC), hydrogen cooling, or direct conductor cooling with water; transformers employ ONAN, ONAF, OFAF, etc.
Explain different cooling methods for an electric machine.
Cooling removes the heat produced by losses so that the temperature of the insulation stays within its class limit. Better cooling allows a higher output from the same machine size. Cooling methods are classified as follows.
1. By the way the coolant moves
- Natural cooling: no fan; heat leaves by natural convection and radiation from the frame. Used for small and totally enclosed non-ventilated (TENV) machines.
- Self ventilation: a fan mounted on the machine's own shaft circulates air. Most common for induction motors. Cooling depends on speed.
- Separate (forced) ventilation: an independently driven fan or blower. Used for variable-speed and large machines.
2. By the path of the cooling air
- Radial ventilation: air enters at the ends, flows radially outward through radial ducts between core packets. Used in medium and large machines (above about 20 kW).
- Axial ventilation: air flows along axial holes in the rotor/stator cores. Used in small, high-speed machines.
- Mixed (radial-axial) ventilation: a combination, used in large machines.
radial ventilation (section)
frame |^^^^^^^^^^^^^^^^^^| air out
stator |==| |==| |==| |==|
| duct duct duct|
rotor |==| |==| |==| |==|
air in-> --- shaft --- <-air in
3. By the cooling circuit
- Open circuit: fresh air is drawn from the surroundings and thrown out (drip-proof, screen-protected machines).
- Closed circuit: the same air recirculates through a heat exchanger (air-to-air or air-to-water). Used where the air is dirty or for large machines. TEFC (totally enclosed fan-cooled) motors have an external fan blowing over a finned frame.
4. Other coolants
- Hydrogen cooling of large turbo-alternators. Compared with air, hydrogen has about 7 times the thermal conductivity, about 1.5 times the heat transfer coefficient and only about 1/14 the density. This gives lower windage loss, no oxidation of insulation and less noise.
- Direct (inner) conductor cooling: hydrogen or water flows through hollow conductors. Used in very large turbo-alternators.
5. Transformer cooling methods
| Code | Method |
|---|---|
| AN / AF | Dry type, natural / forced air |
| ONAN | Oil natural, air natural (tank with radiators) |
| ONAF | Oil natural, air forced (fans on radiators) |
| OFAF | Oil forced by pumps, air forced |
| OFWF | Oil forced, water forced (oil-water heat exchanger) |
| ODAF | Oil directed into the windings, air forced |
The choice depends on rating, enclosure, environment and cost. Larger ratings need more intense cooling because losses grow faster (∝ linear dimension³) than surface area (∝ linear dimension²).
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Choice of specific electric loading in induction machine · Electric Machine Design, chapter 4 · asked 3×
- Heating and cooling time constants · Electric Machine Design, chapter 2 · asked 3×
- Transformer heating and cooling time constants (25°C/37.5°C) · Electric Machine Design, chapter 2 · asked 3×
- Transformer heating and cooling time constants (25°C/40°C) · Electric Machine Design, chapter 2 · asked 3×
- New kVA rating with fan cooling (350 kVA) · Electric Machine Design, chapter 2 · asked 2×
- New kVA rating with fan cooling (400 kVA) · Electric Machine Design, chapter 2 · asked 2×
- Machine learning; Boltzmann machines · Artificial Intelligence, chapter 6
- Non-salient power angle relation for salient machines · Electric Machines II, chapter 1
- Power angle characteristics of cylindrical rotor machine · Electric Machines II, chapter 1 · asked 2×
- Construction of synchronous machine and rotor types · Electric Machines II, chapter 1 · asked 2×